NM-B Wire

NEC Quick Answer

NM-B ampacity is limited to the 60C column of NEC Table 310.16 (334.80), even though its conductors are rated 90C; the 90C rating is only the starting point for derating. The insulated power conductors in NM cable are rated 600 volts (334.104).

NEC 2023: Sections 334.80, 334.104

NM-B stands for Nonmetallic Sheathed Cable (Romex). Standard residential wiring (Romex). Individual conductors rated 90°C but ampacity limited to 60°C column per 334.80.
Dry rating60°C
Voltage600V
Locationsdry

Specifications

PropertyValue
Full nameNonmetallic Sheathed Cable (Romex)
Insulation materialPVC on individual conductors, PVC outer sheath
Outer coveringPVC/nylon outer jacket
Temperature rating (dry)60°C (140°F)
Voltage rating600V
Approved locationsdry

NM-B ampacity chart

NEC 334.80 sets NM-B cable ampacity at the 60°C column of Table 310.16, even though the conductors inside are rated 90°C. The 90°C value is only the starting point when you derate for heat or bundling. Copper values from NEC 2023 Table 310.16:

NM-B copper, amperes, NEC 2023 Table 310.16. Sizes are AWG.
SizeAmpacity 60°Breaker90° (derating only)
141515 max*25
122020 max*30
103030 max*40
8404055
65560†75
4707095
38590†115
295100†130

* 240.4(D) limits the breaker on small conductors, whatever the column says: 14 AWG copper 15A, 12 AWG copper 20A, 10 AWG copper 30A, 12 AWG aluminum 15A, 10 AWG aluminum 25A.

† The ampacity is not a standard breaker size, so 240.4(B) allows the next standard size up when the circuit does not feed more than one receptacle for cord-and-plug loads and the load itself stays within the cable ampacity. Otherwise use the next smaller breaker. See Article 240 and the standard breaker sizes.

When to use NM-B wire

Standard residential wiring (Romex). Individual conductors rated 90°C but ampacity limited to 60°C column per 334.80.

Where NM-B may be run, where it is prohibited, how often it must be stapled and how its ampacity is set all come from one NEC article. Before you pull cable, read NEC Article 334: NM-B cable rules for permitted locations (334.10), prohibited locations (334.12), securing and supporting (334.30) and the 60°C ampacity limit (334.80).

Choose NM-B when:

Don't use NM-B when:

Common applications for NM-B:

NEC code references for NM-B

The NEC defines wire insulation types in Table 310.4(1) (formerly Table 310.104(A)). Key sections that apply:

Frequently asked questions about NM-B wire

What does NM-B stand for?

NM-B stands for Non-Metallic sheathed cable, Type B. "NM" indicates the outer sheath is non-metallic (PVC jacket). "B" indicates the current temperature rating standard (90°C on the individual conductors, though ampacity is calculated at 60°C per NEC 334.80). It is commonly known by the brand name "Romex."

Where can I use NM-B (Romex)?

NM-B is approved for dry indoor locations - inside walls, ceilings, and attics of residential and commercial buildings. Where it is allowed depends on the building type (NEC 334.10), not on its height. It is not permitted in wet or damp locations (334.12(B)), and the inside of an outdoor or underground conduit counts as a wet location. Where it is subject to physical damage it must be protected, for example by conduit (334.15(B)). Some local codes require conduit instead of NM-B, so check with your inspector.

Why is NM-B ampacity rated at 60°C when conductors are 90°C?

NEC Section 334.80 requires NM-B ampacity to be based on the 60°C column of Table 310.16, even though the individual conductors inside are rated 90°C. This is because the cable assembly traps heat differently than individual conductors in conduit. The 90°C rating only matters for ambient temperature derating calculations per 310.15(B)(1).

What is the largest NM-B cable available?

NEC 334.104 covers NM cable conductors from 14 AWG through 2 AWG copper (12 AWG through 2 AWG aluminum). Stores mostly stock 14 AWG to 6 AWG; the larger sizes are uncommon. For circuits requiring larger wire (50A and above), most electricians switch to individual THHN conductors in conduit or SER cable.

Other wire insulation types

THHN 90°CTHWN 75°CTHWN-2 90°CXHHW 90°CXHHW-2 90°CRHH 90°CRHW-2 90°CUSE-2TW 60°CUF-B 60°CMC Cable 90°CAC Cable (BX) 90°CSER/SEU 75°CPV Wire 90°CTHHW 90°CTHW 75°CTHW-2 90°CRHW 75°CMI 90°CUF 60°CXHH 90°CFEP 90°CSIS 90°C
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified February 2026 · Report a mistake