ReferenceNEC 2023 445.13 and Table 310.16 · Updated

Generator wire size chart

Size generator wire twice and use the larger answer. First, NEC 445.13(A): at least 115% of the generator’s nameplate current, or 100% where the generator’s design and operation prevent overloading (the installation manual says whether yours qualifies). Second, the wire must be protected by that output breaker (240.4), so it needs an ampacity at least equal to the breaker rating. A 22 kW generator is 91.7A at 240V: 3 AWG copper or 1 AWG aluminum at 100%, before you check the breaker.
14 kW6 Cu / 4 Al
22 kW3 Cu / 1 Al
26 kW2 Cu / 1/0 Al
RuleNEC 445.13(A)

Generator wire size by kW

Single-phase 240V generator. Nameplate amps = kW × 1000 ÷ 240. Smallest conductors from NEC Table 310.16 at 75°C for the 100% and 115% cases in 445.13(A). AWG unless marked kcmil.
kWAmps100% (overload protected)115%
CopperAlum.CopperAlum.
833.38888
1041.78686
1250.08664
1458.36443
1666.74342
1875.04332
2083.34231
2291.73121/0
24100.03121/0
26108.321/012/0

Many standby generators list a higher rating on propane than on natural gas; use the higher one, or the rated amps printed on the nameplate if it gives them. Assumes individual THWN-2 or XHHW-2 conductors in conduit, generator, transfer switch and breaker terminals marked 75°C, 30°C (86°F) ambient and no more than three current-carrying conductors. On circuits of 100A or less, terminals not marked 75°C need the 60°C column, which is larger (110.14(C)). Source: NEC 2023 445.13(A) and Table 310.16; ampacity values checked November 14, 2026.

Wire size by generator output breaker

The conductors from a generator with a built-in breaker to the transfer switch are protected by that breaker, so they need an ampacity at least equal to its rating. Read the breaker rating on the generator, then use this table. The copper ground is from Table 250.122.

Smallest conductors with a 75°C ampacity at least equal to the breaker rating (NEC Table 310.16), copper equipment ground (Table 250.122), and the longest one-way run that keeps the copper size under 3% voltage drop at 240V with the full breaker rating as load.
BreakerCopperAlum.Ground (Cu)Max run, ft
40A8810115
45A8610102
50A861092
60A6410121
70A438166
80A428145
90A328162
100A318146
110A21/06168
125A12/06186
150A1/03/06196
175A2/04/06212
200A3/0250k6234

A long run from the generator pad to the transfer switch may need larger wire for voltage drop, and the copper ground grows with it (250.122(B)). The sub panel wire size chart gives feeder sizes by distance, and the voltage drop calculator takes your exact load and length.

Portable generator inlet wire size

A portable generator connects through a power inlet box and an interlock or transfer switch. The wire from the inlet to the panel is sized to the inlet’s breaker:

Installing the generator

The transfer switch, the interlock options, the gas line and the permit steps are in the whole house generator wiring guide and the transfer switch guide.

Frequently asked questions

What size wire for a 22kW generator?

A 22 kW generator at 240V is 91.7A. Where the generator’s design prevents overloading, 445.13(A) allows conductors sized at 100%: 3 AWG copper or 1 AWG aluminum. At 115% (105.4A) it is 2 AWG copper or 1/0 AWG aluminum. The wire must also carry the rating of the generator’s output breaker, so check the breaker table above and use the larger size. Sizes are from NEC Table 310.16 at 75°C.

What size wire for a 24kW generator?

A 24 kW generator at 240V is 100.0A. Where the generator’s design prevents overloading, 445.13(A) allows conductors sized at 100%: 3 AWG copper or 1 AWG aluminum. At 115% (115.0A) it is 2 AWG copper or 1/0 AWG aluminum. The wire must also carry the rating of the generator’s output breaker, so check the breaker table above and use the larger size. Sizes are from NEC Table 310.16 at 75°C.

What size wire for a 14kW generator?

A 14 kW generator at 240V is 58.3A. Where the generator’s design prevents overloading, 445.13(A) allows conductors sized at 100%: 6 AWG copper or 4 AWG aluminum. At 115% (67.1A) it is 4 AWG copper or 3 AWG aluminum. The wire must also carry the rating of the generator’s output breaker, so check the breaker table above and use the larger size. Sizes are from NEC Table 310.16 at 75°C.

Why is generator wire sized at 115%?

NEC 445.13(A) requires the conductors from the generator terminals to the first overcurrent device to have an ampacity of at least 115% of the nameplate current. Where the design and operation of the generator prevent overloading, 100% is allowed. NEC 2026 rewords 445.13; check the edition your area enforces.

Can I use aluminum wire for a generator?

Yes, where the generator, transfer switch and breaker terminals are marked for aluminum (often AL/CU or AL9CU). Aluminum needs a larger size for the same ampacity, as in the tables above.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified February 2026 · Report a mistake