Generator wire size chart
Generator wire size by kW
| kW | Amps | 100% (overload protected) | 115% | ||
|---|---|---|---|---|---|
| Copper | Alum. | Copper | Alum. | ||
| 8 | 33.3 | 8 | 8 | 8 | 8 |
| 10 | 41.7 | 8 | 6 | 8 | 6 |
| 12 | 50.0 | 8 | 6 | 6 | 4 |
| 14 | 58.3 | 6 | 4 | 4 | 3 |
| 16 | 66.7 | 4 | 3 | 4 | 2 |
| 18 | 75.0 | 4 | 3 | 3 | 2 |
| 20 | 83.3 | 4 | 2 | 3 | 1 |
| 22 | 91.7 | 3 | 1 | 2 | 1/0 |
| 24 | 100.0 | 3 | 1 | 2 | 1/0 |
| 26 | 108.3 | 2 | 1/0 | 1 | 2/0 |
Many standby generators list a higher rating on propane than on natural gas; use the higher one, or the rated amps printed on the nameplate if it gives them. Assumes individual THWN-2 or XHHW-2 conductors in conduit, generator, transfer switch and breaker terminals marked 75°C, 30°C (86°F) ambient and no more than three current-carrying conductors. On circuits of 100A or less, terminals not marked 75°C need the 60°C column, which is larger (110.14(C)). Source: NEC 2023 445.13(A) and Table 310.16; ampacity values checked November 14, 2026.
Wire size by generator output breaker
The conductors from a generator with a built-in breaker to the transfer switch are protected by that breaker, so they need an ampacity at least equal to its rating. Read the breaker rating on the generator, then use this table. The copper ground is from Table 250.122.
| Breaker | Copper | Alum. | Ground (Cu) | Max run, ft |
|---|---|---|---|---|
| 40A | 8 | 8 | 10 | 115 |
| 45A | 8 | 6 | 10 | 102 |
| 50A | 8 | 6 | 10 | 92 |
| 60A | 6 | 4 | 10 | 121 |
| 70A | 4 | 3 | 8 | 166 |
| 80A | 4 | 2 | 8 | 145 |
| 90A | 3 | 2 | 8 | 162 |
| 100A | 3 | 1 | 8 | 146 |
| 110A | 2 | 1/0 | 6 | 168 |
| 125A | 1 | 2/0 | 6 | 186 |
| 150A | 1/0 | 3/0 | 6 | 196 |
| 175A | 2/0 | 4/0 | 6 | 212 |
| 200A | 3/0 | 250k | 6 | 234 |
A long run from the generator pad to the transfer switch may need larger wire for voltage drop, and the copper ground grows with it (250.122(B)). The sub panel wire size chart gives feeder sizes by distance, and the voltage drop calculator takes your exact load and length.
Portable generator inlet wire size
A portable generator connects through a power inlet box and an interlock or transfer switch. The wire from the inlet to the panel is sized to the inlet’s breaker:
- 30A inlet (L14-30): 10 AWG copper. Its 60°C ampacity is 30A and 240.4(D) limits 10 AWG copper to 30A.
- 50A inlet: 8 AWG copper (50A) only where every terminal is marked 75°C. With 60°C terminals 8 AWG is 40A, so use 6 AWG copper (55A at 60°C).
Installing the generator
The transfer switch, the interlock options, the gas line and the permit steps are in the whole house generator wiring guide and the transfer switch guide.
Frequently asked questions
What size wire for a 22kW generator?
A 22 kW generator at 240V is 91.7A. Where the generator’s design prevents overloading, 445.13(A) allows conductors sized at 100%: 3 AWG copper or 1 AWG aluminum. At 115% (105.4A) it is 2 AWG copper or 1/0 AWG aluminum. The wire must also carry the rating of the generator’s output breaker, so check the breaker table above and use the larger size. Sizes are from NEC Table 310.16 at 75°C.
What size wire for a 24kW generator?
A 24 kW generator at 240V is 100.0A. Where the generator’s design prevents overloading, 445.13(A) allows conductors sized at 100%: 3 AWG copper or 1 AWG aluminum. At 115% (115.0A) it is 2 AWG copper or 1/0 AWG aluminum. The wire must also carry the rating of the generator’s output breaker, so check the breaker table above and use the larger size. Sizes are from NEC Table 310.16 at 75°C.
What size wire for a 14kW generator?
A 14 kW generator at 240V is 58.3A. Where the generator’s design prevents overloading, 445.13(A) allows conductors sized at 100%: 6 AWG copper or 4 AWG aluminum. At 115% (67.1A) it is 4 AWG copper or 3 AWG aluminum. The wire must also carry the rating of the generator’s output breaker, so check the breaker table above and use the larger size. Sizes are from NEC Table 310.16 at 75°C.
Why is generator wire sized at 115%?
NEC 445.13(A) requires the conductors from the generator terminals to the first overcurrent device to have an ampacity of at least 115% of the nameplate current. Where the design and operation of the generator prevent overloading, 100% is allowed. NEC 2026 rewords 445.13; check the edition your area enforces.
Can I use aluminum wire for a generator?
Yes, where the generator, transfer switch and breaker terminals are marked for aluminum (often AL/CU or AL9CU). Aluminum needs a larger size for the same ampacity, as in the tables above.
NEC 2023 references verified February 2026 · Report a mistake