THW-2 Wire

THW-2 stands for Thermoplastic Heat-resistant Water-resistant (90C wet). Upgrade from THW with full 90C rating in both wet and dry. Listed in 90C column of Table 310.16.
Dry rating90°C
Wet rating90°C
Voltage600V
LocationsDry, Wet

Specifications

PropertyValue
Full nameThermoplastic Heat-resistant Water-resistant (90C wet)
Insulation materialPVC
Outer coveringNone
Temperature rating (dry)90°C (194°F)
Temperature rating (wet)90°C (194°F)
Voltage rating600V
Approved locationsDry, Wet

Advantages and limitations

Advantages: ['90C in both wet and dry', 'Can use 90C column for derating']
Limitations: ['Slightly more expensive than THW']

THW-2 wire ampacity chart

Amps for THW-2 by size from NEC 2023 Table 310.16. Most circuits up to 100A are sized from the 60° or 75° column; which one is explained below the chart.

THW-2 ampacity in amperes, NEC 2023 Table 310.16: not more than three current-carrying conductors, 30°C (86°F) ambient. Sizes are AWG; “k” means kcmil.
SizeCopperAluminum
60°75°90°60°75°90°
141520*25* - - -
122025*30*1520*25*
103035*40*2530*35*
8405055354045
6556575405055
4708595556575
385100115657585
2951151307590100
111013014585100115
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205
250k215255290170205230
300k240285320195230260
350k260310350210250280
400k280335380225270305
500k320380430260310350

* 240.4(D) limits the breaker on small conductors, whatever the column says: 14 AWG copper 15A, 12 AWG copper 20A, 10 AWG copper 30A, 12 AWG aluminum 15A, 10 AWG aluminum 25A.

THW-2 is rated 90°C dry, so it can use the columns of NEC 2023 Table 310.16 up to 90°C. The column you actually size with is set by the terminations, per 110.14(C): terminations on circuits of 100A or less, or marked for 14 AWG through 1 AWG, use the 60°C column unless the equipment is listed and marked for 75°C; terminations on larger circuits and conductors use 75°C. The 90°C column is the starting point for heat and bundling derating, not a breaker size.

When to use THW-2 wire

Upgrade from THW with full 90C rating in both wet and dry. Listed in 90C column of Table 310.16.

Common applications for THW-2:

NEC code references for THW-2

The NEC defines wire insulation types in Table 310.4(1) (formerly Table 310.104(A)). Key sections that apply:

Frequently asked questions about THW-2 wire

Where can I use THW-2 wire?

THW-2 is approved for use in dry, wet per NEC Table 310.4(1). It has a dry temperature rating of 90°C and a wet rating of 90°C. Always verify that your specific installation meets the approved location requirements.

What is the temperature rating of THW-2?

THW-2 is rated 90°C in dry locations and 90°C in wet locations. The ampacity values in NEC Table 310.16 use the 90°C column for conductors rated at or above 90°C, but actual usable ampacity is limited by the termination temperature (typically 75°C per 110.14(C)).

Other wire insulation types

THHN 90°CTHWN 75°CTHWN-2 90°CXHHW 90°CXHHW-2 90°CRHH 90°CRHW-2 90°CUSE-2TW 60°CNM-B 60°CUF-B 60°CMC Cable 90°CAC Cable (BX) 90°CSER/SEU 75°CPV Wire 90°CTHHW 90°CTHW 75°CRHW 75°CMI 90°CUF 60°CXHH 90°CFEP 90°CSIS 90°C
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified February 2026 · Report a mistake