Project GuideNEC 2023 · 2026 · Updated

Whole-House Generator: Complete Wiring Guide

Whole-House Generator: Use 3 AWG copper on a 100A breaker at 240V.
Wire (Cu)3 AWG
Wire (Al)1 AWG
Breaker100A
GFCINot required

Bill of materials

Whole-house standby generators require a transfer switch, properly sized feeder, and compliance with NEC Article 702 (Optional Standby Systems). The transfer switch must be rated for the full generator output and prevents backfeeding the utility grid. Wire sizing depends on the generator output amperage and its output breaker: the generator wire size chart sizes it by kW and by breaker.

The transfer switch rating must match or exceed the generator output. A 22kW generator at 240V produces about 92A, requiring a 100A transfer switch and 3 AWG copper feeder. The generator must have a disconnecting means per 445.18. Grounding depends on the transfer switch. Most home standby installs use a transfer switch with a solid (unswitched) neutral, so the generator is not a separately derived system: its neutral stays unbonded and the grounding electrode connection is at the service. If the transfer switch switches the neutral (4-pole), the generator is separately derived and needs its own bonding jumper and grounding electrode connection per 250.30. Never connect a generator without a transfer switch - backfeeding kills utility workers.

22kW standby generator (100A)

ComponentSpecificationNEC basis
Wire (copper)3 AWG THHNTable 310.16, 110.14(C)
Wire (aluminum alt.)1 AWG THHNTable 310.16, 110.14(C)
Breaker100A double-pole240.4
Voltage240V single-phase
Conduit (EMT)1" EMTChapter 9 Table 4
Max distance (3% VD)184 ft at 240V copper210.19(A) Note 4

14kW standby generator (60A)

ComponentSpecificationNEC basis
Wire (copper)6 AWG THHNTable 310.16, 110.14(C)
Wire (aluminum alt.)4 AWG THHNTable 310.16, 110.14(C)
Breaker60A double-pole240.4
Voltage240V single-phase
Conduit (EMT)3/4" EMTChapter 9 Table 4
Max distance (3% VD)153 ft at 240V copper210.19(A) Note 4

Installation notes

GFCI is not specifically required for this application by NEC, though local amendments may differ. Check with your local building department before starting work.

For the wire run, you have two options: NM-B cable (Romex) for interior runs through framing, or individual THHN conductors in conduit for exposed runs, outdoor installations, or runs through unfinished spaces. NM-B is faster to install but cannot be used outdoors or in conduit. For conduit, use EMT (metallic) or PVC Schedule 40.

Run length matters: every foot of wire adds voltage drop, reducing power to your equipment. The table below shows the exact voltage drop at common distances. If your run exceeds the 3% threshold, upsize one gauge.

Voltage drop by distance

Percentage voltage drop at common run lengths. NEC recommends 3% maximum for branch circuits and 5% for combined feeder plus branch.

Distance3 AWG Co1 AWG Al2 AWG Co
25 ft0.4%0.4%0.3%
50 ft0.8%0.8%0.7%
75 ft1.2%1.3%1.0%
100 ft1.6%1.7%1.3%
150 ft2.5%2.5%1.9%
200 ft3.3%3.4%2.6%

Detailed ampacity: 3 AWG copper, 1 AWG aluminum. Wire size lookup: 100A circuit. Calculators: voltage drop ยท panel load calculator.

Inspection preparation

Before your service upgrade inspection, verify these frequently-checked items:

CheckNEC RefCommon Fail
Service entrance conductors properly sizedNEC 230.42Undersized SE conductors for panel rating
Main breaker matches panel ratingNEC 230.90Main breaker exceeds panel bus bar rating
Grounding electrode conductor properly sizedNEC 250.66GEC too small for service size
Grounding electrode system completeNEC 250.50Missing required electrodes (water pipe, ground rods, Ufer)
Two ground rods (if no Ufer/water pipe)NEC 250.53(A)(2)Single ground rod without resistance test or supplemental electrode

See the full inspection checklist tool for all 13 items with progress tracking.

Frequently asked questions

What wire size do I need for whole-house generator?

Use 3 AWG copper or 1 AWG aluminum on a 100A breaker at 240V. This is based on NEC 2023 Table 310.16 ampacity with 110.14(C) termination limits. The equipment nameplate or installation manual sets the minimum circuit ampacity and maximum breaker; follow it where it differs.

Does whole-house generator require GFCI?

No. GFCI is not required for this application.

What size wire do I need for a home standby generator?

Divide the generator's kW by 240V for nameplate amps, then size the copper or aluminum conductors from Table 310.16 at 75C. 445.13(A) sets 115% of nameplate current; its exception allows 100% when the generator's design prevents overloading, which covers most standby units with a built-in output breaker. The wire must also be protected by that breaker (240.4), so if the generator's breaker is larger than the wire in this table, size the wire to the breaker. The 75C column assumes 75C-rated terminals on the generator and transfer switch (110.14(C)); check the markings and the generator's installation manual. The generator wire size chart also sizes the wire by output breaker and run length.

Generator (240V)Nameplate ampsWire at 100% (built-in overload protection)Wire at 115% (445.13(A))
10 kW41.7A8 Cu / 6 Al8 Cu / 6 Al
14 kW58.3A6 Cu / 4 Al4 Cu / 3 Al
18 kW75.0A4 Cu / 3 Al3 Cu / 2 Al
20 kW83.3A4 Cu / 2 Al3 Cu / 1 Al
22 kW91.7A3 Cu / 1 Al2 Cu / 1/0 Al
24 kW100.0A3 Cu / 1 Al2 Cu / 1/0 Al
26 kW108.3A2 Cu / 1/0 Al1 Cu / 2/0 Al
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified February 2026 · Report a mistake

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.