Electrical Materials List Builder

Pick a project and your one-way run length. The builder lists what to buy: conductor size and type, total wire length, breaker, ground wire, conduit size and the devices the code calls for, each with the NEC section it comes from. Example: a 48A EV charger 50 ft from the panel in EMT takes 6 AWG copper THHN on a 60A breaker with a 10 AWG ground in 3/4 in. EMT.
Panel to equipment, measured along the route
NM-B always uses the 60°C column

6 AWG copper on a 60A breaker, THHN in EMT (75°C terminations), 50 ft one-way. Voltage drop 0.98% at 48A.

  1. 6 AWG THHN/THWN-2 copper, 2 hots (black + red)65 ft each, 130 ft total

    Smallest copper size whose Table 310.16 ampacity (65A at 75°C) covers the 60A breaker. 75°C column: wire, breaker and equipment all marked 75°C (110.14(C)(1)(a)). NEC Table 310.16, 110.14(C), 240.4(D)

    Search Amazon for this (paid link)
  2. 10 AWG THHN/THWN-2 copper, ground (green)65 ft

    Table 250.122 minimum for a 60A breaker is 10 AWG copper. NEC Table 250.122

    Search Amazon for this (paid link)
  3. 3/4 in. EMT conduit5 x 10 ft sticks, plus couplings and connectors

    Smallest trade size that keeps 2 x 6 AWG + 1 x 10 AWG THHN at or under 40% fill (23% here). NEC Chapter 9 Tables 1, 4, 5

    Search Amazon for this (paid link)
  4. 60A 2-pole breaker1, match your panel brand

    48A charger is a continuous load: 125% = 60A, next standard size 60A. NEC 625.41, 625.42

    Search Amazon for this (paid link)
  5. Level 2 EV charger (hardwired)48A rated

    The charger sets the circuit: this list is sized for a charger set to 48A. NEC 625.41

    Search Amazon for this (paid link)
  6. GFCINot a separate breaker for a hardwired charger

    625.54 requires GFCI on EV charging receptacles. A listed hardwired charger has its own ground-fault protection, so no GFCI breaker is added upstream. NEC 625.54

Voltage drop: 0.98% for 6 AWG over 50 ft at 48A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Paid links. As an Amazon Associate WireRef earns from qualifying purchases. Amazon search results mix sizes and types: check each listing matches the line it came from.

How the list is built

Every line links to an Amazon search for that item. There is no single cart: breakers must match your panel brand, and wire is sold in many lengths, so pick each line yourself. Use Copy list to take it to the store or Print for the job file.

Pre-computed materials lists

Common projects at typical run lengths, computed with the same rules as the builder. Each list states the termination rating it assumes; where the project guide and the wire size page lead with the 60°C answer (the 50A spa), so does the list. Paid links: as an Amazon Associate WireRef earns from qualifying purchases.

EV charger, 48A (hardwired), 50 ft run, THHN in EMT

6 AWG copper on a 60A breaker, THHN in EMT (75°C terminations), 50 ft one-way. Voltage drop 0.98% at 48A.

  1. 6 AWG THHN/THWN-2 copper, 2 hots (black + red)65 ft each, 130 ft total

    Smallest copper size whose Table 310.16 ampacity (65A at 75°C) covers the 60A breaker. 75°C column: wire, breaker and equipment all marked 75°C (110.14(C)(1)(a)). NEC Table 310.16, 110.14(C), 240.4(D)

    Search Amazon for this (paid link)
  2. 10 AWG THHN/THWN-2 copper, ground (green)65 ft

    Table 250.122 minimum for a 60A breaker is 10 AWG copper. NEC Table 250.122

    Search Amazon for this (paid link)
  3. 3/4 in. EMT conduit5 x 10 ft sticks, plus couplings and connectors

    Smallest trade size that keeps 2 x 6 AWG + 1 x 10 AWG THHN at or under 40% fill (23% here). NEC Chapter 9 Tables 1, 4, 5

    Search Amazon for this (paid link)
  4. 60A 2-pole breaker1, match your panel brand

    48A charger is a continuous load: 125% = 60A, next standard size 60A. NEC 625.41, 625.42

    Search Amazon for this (paid link)
  5. Level 2 EV charger (hardwired)48A rated

    The charger sets the circuit: this list is sized for a charger set to 48A. NEC 625.41

    Search Amazon for this (paid link)
  6. GFCINot a separate breaker for a hardwired charger

    625.54 requires GFCI on EV charging receptacles. A listed hardwired charger has its own ground-fault protection, so no GFCI breaker is added upstream. NEC 625.54

Voltage drop: 0.98% for 6 AWG over 50 ft at 48A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Full project guide · 60A wire size page

EV charger, 48A (hardwired), 50 ft run, NM-B

4 AWG copper on a 60A breaker, NM-B, 50 ft one-way. Voltage drop 0.62% at 48A.

  1. 4/2 NM-B cable with ground (copper)65 ft

    Smallest copper size whose Table 310.16 ampacity (70A at 60°C) covers the 60A breaker. NM-B is limited to the 60°C column (334.80). The cable's ground must be at least 10 AWG (Table 250.122). NEC Table 310.16, 334.80, 250.122

    Search Amazon for this (paid link)
  2. 60A 2-pole breaker1, match your panel brand

    48A charger is a continuous load: 125% = 60A, next standard size 60A. NEC 625.41, 625.42

    Search Amazon for this (paid link)
  3. Level 2 EV charger (hardwired)48A rated

    The charger sets the circuit: this list is sized for a charger set to 48A. NEC 625.41

    Search Amazon for this (paid link)
  4. GFCINot a separate breaker for a hardwired charger

    625.54 requires GFCI on EV charging receptacles. A listed hardwired charger has its own ground-fault protection, so no GFCI breaker is added upstream. NEC 625.54

Voltage drop: 0.62% for 4 AWG over 50 ft at 48A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Full project guide · 60A wire size page

EV charger, 40A (hardwired), 40 ft run, NM-B

6 AWG copper on a 50A breaker, NM-B, 40 ft one-way. Voltage drop 0.65% at 40A.

  1. 6/2 NM-B cable with ground (copper)50 ft

    Smallest copper size whose Table 310.16 ampacity (55A at 60°C) covers the 50A breaker. NM-B is limited to the 60°C column (334.80). The cable's ground must be at least 10 AWG (Table 250.122). NEC Table 310.16, 334.80, 250.122

    Search Amazon for this (paid link)
  2. 50A 2-pole breaker1, match your panel brand

    40A charger is a continuous load: 125% = 50A, next standard size 50A. NEC 625.41, 625.42

    Search Amazon for this (paid link)
  3. Level 2 EV charger (hardwired)40A rated

    The charger sets the circuit: this list is sized for a charger set to 40A. NEC 625.41

    Search Amazon for this (paid link)
  4. GFCINot a separate breaker for a hardwired charger

    625.54 requires GFCI on EV charging receptacles. A listed hardwired charger has its own ground-fault protection, so no GFCI breaker is added upstream. NEC 625.54

Voltage drop: 0.65% for 6 AWG over 40 ft at 40A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Full project guide · 50A wire size page

EV charger, 32A (hardwired), 60 ft run, THHN in EMT

8 AWG copper on a 40A breaker, THHN in EMT (75°C terminations), 60 ft one-way. Voltage drop 1.24% at 32A.

  1. 8 AWG THHN/THWN-2 copper, 2 hots (black + red)75 ft each, 150 ft total

    Smallest copper size whose Table 310.16 ampacity (50A at 75°C) covers the 40A breaker. 75°C column: wire, breaker and equipment all marked 75°C (110.14(C)(1)(a)). NEC Table 310.16, 110.14(C), 240.4(D)

    Search Amazon for this (paid link)
  2. 10 AWG THHN/THWN-2 copper, ground (green)75 ft

    Table 250.122 minimum for a 40A breaker is 10 AWG copper. NEC Table 250.122

    Search Amazon for this (paid link)
  3. 1/2 in. EMT conduit6 x 10 ft sticks, plus couplings and connectors

    Smallest trade size that keeps 2 x 8 AWG + 1 x 10 AWG THHN at or under 40% fill (31% here). NEC Chapter 9 Tables 1, 4, 5

    Search Amazon for this (paid link)
  4. 40A 2-pole breaker1, match your panel brand

    32A charger is a continuous load: 125% = 40A, next standard size 40A. NEC 625.41, 625.42

    Search Amazon for this (paid link)
  5. Level 2 EV charger (hardwired)32A rated

    The charger sets the circuit: this list is sized for a charger set to 32A. NEC 625.41

    Search Amazon for this (paid link)
  6. GFCINot a separate breaker for a hardwired charger

    625.54 requires GFCI on EV charging receptacles. A listed hardwired charger has its own ground-fault protection, so no GFCI breaker is added upstream. NEC 625.54

Voltage drop: 1.24% for 8 AWG over 60 ft at 32A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Full project guide · 40A wire size page

Electric range, 50A, 40 ft run, NM-B

6 AWG copper on a 50A breaker, NM-B, 40 ft one-way. Voltage drop 0.65% at 40A.

  1. 6/3 NM-B cable with ground (copper)50 ft

    Smallest copper size whose Table 310.16 ampacity (55A at 60°C) covers the 50A breaker. NM-B is limited to the 60°C column (334.80). The cable's ground must be at least 10 AWG (Table 250.122). NEC Table 310.16, 334.80, 250.122

    Search Amazon for this (paid link)
  2. 50A 2-pole breaker1, match your panel brand

    Standard range circuit in this site's circuit data (Electric Range/Oven (50A)). NEC 210.19(A)(3), 220.55

    Search Amazon for this (paid link)
  3. NEMA 14-50 receptacle4-wire, matches the range cord

    New installations use a 4-wire receptacle; 3-wire is existing-only. NEC 250.140

    Search Amazon for this (paid link)

Voltage drop: 0.65% for 6 AWG over 40 ft at 40A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Full project guide · 50A wire size page

Electric dryer, 30A, 40 ft run, NM-B

10 AWG copper on a 30A breaker, NM-B, 40 ft one-way. Voltage drop 0.99% at 24A.

  1. 10/3 NM-B cable with ground (copper)50 ft

    Smallest copper size whose Table 310.16 ampacity (30A at 60°C) covers the 30A breaker. NM-B is limited to the 60°C column (334.80). The cable's ground must be at least 10 AWG (Table 250.122). NEC Table 310.16, 334.80, 250.122

    Search Amazon for this (paid link)
  2. 30A 2-pole GFCI breaker1, match your panel brand

    Standard dryer circuit in this site's circuit data (Electric Dryer (30A)). GFCI protection is required for this circuit (NEC 210.8(A)(10)). NEC 220.54, 210.8(A)(10)

    Search Amazon for this (paid link)
  3. NEMA 14-30 receptacle4-prong

    4-prong receptacle required for new installations. NEC 250.140

    Search Amazon for this (paid link)

Voltage drop: 0.99% for 10 AWG over 40 ft at 24A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Full project guide · 30A wire size page

Tank water heater, 30A, 30 ft run, NM-B

10 AWG copper on a 30A breaker, NM-B, 30 ft one-way. Voltage drop 0.59% at 19A.

  1. 10/2 NM-B cable with ground (copper)40 ft

    Smallest copper size whose Table 310.16 ampacity (30A at 60°C) covers the 30A breaker. NM-B is limited to the 60°C column (334.80). The cable's ground must be at least 10 AWG (Table 250.122). NEC Table 310.16, 334.80, 250.122

    Search Amazon for this (paid link)
  2. 30A 2-pole breaker1, match your panel brand

    Water heaters are continuous loads; this site's circuit data uses a 30A breaker for the standard 4500W tank. NEC 422.13

    Search Amazon for this (paid link)
  3. Disconnecting meansWithin sight, or a breaker lockable open

    A hardwired water heater needs a disconnect within sight of it, or a breaker that can be locked in the open position. NEC 422.31

    Search Amazon for this (paid link)
  4. GFCICord-and-plug units only

    210.8(D) requires GFCI for cord-and-plug connected water heaters. A hardwired unit is exempt, though some jurisdictions read it more broadly: ask your inspector. NEC 210.8(D)

Voltage drop: 0.59% for 10 AWG over 30 ft at 19A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Full project guide · 30A wire size page

Hot tub / spa, 50A, 60 ft run, THWN-2 in PVC

6 AWG copper on a 50A breaker, THWN-2 in PVC (60°C terminations), 60 ft one-way. Voltage drop 1.23% at 50A.

  1. 6 AWG THWN-2 copper, 2 hots (black + red)75 ft each, 150 ft total

    Smallest copper size whose Table 310.16 ampacity (55A at 60°C) covers the 50A breaker. 60°C column: terminations not marked 75°C (110.14(C)(1)(a)). NEC Table 310.16, 110.14(C), 240.4(D)

    Search Amazon for this (paid link)
  2. 6 AWG THWN-2 copper, neutral (white)75 ft

    This site's hot tub data runs a neutral (6/3 with ground). Leave it out only if the spa manual shows a 240V-only connection. Shown full size, same as the hots. NEC 680.42

    Search Amazon for this (paid link)
  3. 10 AWG THWN-2 copper, ground (green)75 ft

    Table 250.122 minimum for a 50A breaker is 10 AWG copper. NEC Table 250.122

    Search Amazon for this (paid link)
  4. 3/4 in. PVC Schedule 40 conduit6 x 10 ft sticks, plus couplings and connectors

    Smallest trade size that keeps 3 x 6 AWG + 1 x 10 AWG THHN at or under 40% fill (34.1% here). NEC Chapter 9 Tables 1, 4, 5

    Search Amazon for this (paid link)
  5. 50A 2-pole GFCI breaker1, match your panel brand

    Breaker size comes from the spa's installation manual; this list is for a spa rated 50A. GFCI protection is required for this circuit (NEC 680.44). NEC 680.42, 680.44

    Search Amazon for this (paid link)
  6. Spa disconnectWithin sight of the spa

    A disconnect within sight of the spa is required. NEC 680.12

    Search Amazon for this (paid link)
  7. Underground warning tape (if buried)75 ft

    Minimum cover for PVC is 18 in. in Table 300.5(A), Column 3 (all locations not otherwise listed). Tape is not NEC-required but is recommended. Underground raceways are wet locations, so the wire must be wet-rated (300.5(B)). NEC Table 300.5(A), 300.5(B)

    Search Amazon for this (paid link)

Voltage drop: 1.23% for 6 AWG over 60 ft at 50A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Full project guide · 50A wire size page

Subpanel feeder, 60A, 75 ft run, THHN in EMT

6 AWG copper on a 60A breaker, THHN in EMT (75°C terminations), 75 ft one-way. Voltage drop 1.47% at 48A.

  1. 6 AWG THHN/THWN-2 copper, 2 hots (black + red)90 ft each, 180 ft total

    Smallest copper size whose Table 310.16 ampacity (65A at 75°C) covers the 60A breaker. 75°C column: wire, breaker and equipment all marked 75°C (110.14(C)(1)(a)). NEC Table 310.16, 110.14(C), 240.4(D)

    Search Amazon for this (paid link)
  2. 6 AWG THHN/THWN-2 copper, neutral (white)90 ft

    Subpanel feeders are 4-wire: two hots, neutral, ground. Shown full size, same as the hots. NEC 250.24(A)(5)

    Search Amazon for this (paid link)
  3. 10 AWG THHN/THWN-2 copper, ground (green)90 ft

    Table 250.122 minimum for a 60A breaker is 10 AWG copper. NEC Table 250.122

    Search Amazon for this (paid link)
  4. 3/4 in. EMT conduit8 x 10 ft sticks, plus couplings and connectors

    Smallest trade size that keeps 3 x 6 AWG + 1 x 10 AWG THHN at or under 40% fill (32.5% here). NEC Chapter 9 Tables 1, 4, 5

    Search Amazon for this (paid link)
  5. 60A 2-pole breaker1, match your panel brand

    Feeder breaker in the main panel for a 60A subpanel feed. NEC 215.2(A), 240.4

    Search Amazon for this (paid link)
  6. Subpanel (load center)Bus rated at least 60A

    The panel must be rated for the feeder breaker that protects it. NEC 408.36

    Search Amazon for this (paid link)
  7. Ground bar kitSeparate from the neutral bar

    In a subpanel the neutral and ground bars stay separate (no bonding screw). NEC 250.24(A)(5)

    Search Amazon for this (paid link)
  8. Grounding electrode (detached building only)Ground rod and clamp at the building

    A subpanel in a detached building needs its own grounding electrode. NEC 250.32

    Search Amazon for this (paid link)

Voltage drop: 1.47% for 6 AWG over 75 ft at 48A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Full project guide · 60A wire size page

Subpanel feeder, 100A, 150 ft run, THWN-2 in PVC

3 AWG copper on a 100A breaker, THWN-2 in PVC (75°C terminations), 150 ft one-way. Voltage drop 2.45% at 80A.

  1. 3 AWG THWN-2 copper, 2 hots (black + red)175 ft each, 350 ft total

    Smallest copper size whose Table 310.16 ampacity (100A at 75°C) covers the 100A breaker. 75°C column: wire, breaker and equipment all marked 75°C (110.14(C)(1)(a)). NEC Table 310.16, 110.14(C), 240.4(D)

    Search Amazon for this (paid link)
  2. 3 AWG THWN-2 copper, neutral (white)175 ft

    Subpanel feeders are 4-wire: two hots, neutral, ground. Shown full size, same as the hots. NEC 250.24(A)(5)

    Search Amazon for this (paid link)
  3. 8 AWG THWN-2 copper, ground (green)175 ft

    Table 250.122 minimum for a 100A breaker is 8 AWG copper. NEC Table 250.122

    Search Amazon for this (paid link)
  4. 1 in. PVC Schedule 40 conduit15 x 10 ft sticks, plus couplings and connectors

    Smallest trade size that keeps 3 x 3 AWG + 1 x 8 AWG THHN at or under 40% fill (39.5% here). NEC Chapter 9 Tables 1, 4, 5

    Search Amazon for this (paid link)
  5. 100A 2-pole breaker1, match your panel brand

    Feeder breaker in the main panel for a 100A subpanel feed. NEC 215.2(A), 240.4

    Search Amazon for this (paid link)
  6. Subpanel (load center)Bus rated at least 100A

    The panel must be rated for the feeder breaker that protects it. NEC 408.36

    Search Amazon for this (paid link)
  7. Ground bar kitSeparate from the neutral bar

    In a subpanel the neutral and ground bars stay separate (no bonding screw). NEC 250.24(A)(5)

    Search Amazon for this (paid link)
  8. Grounding electrode (detached building only)Ground rod and clamp at the building

    A subpanel in a detached building needs its own grounding electrode. NEC 250.32

    Search Amazon for this (paid link)
  9. Underground warning tape (if buried)175 ft

    Minimum cover for PVC is 18 in. in Table 300.5(A), Column 3 (all locations not otherwise listed). Tape is not NEC-required but is recommended. Underground raceways are wet locations, so the wire must be wet-rated (300.5(B)). NEC Table 300.5(A), 300.5(B)

    Search Amazon for this (paid link)

Voltage drop: 2.45% for 3 AWG over 150 ft at 80A, within the 3% recommendation (210.19(A) Informational Note No. 4).

Full project guide · 100A wire size page

Frequently asked questions

Why does NM-B need a bigger wire than THHN in conduit?

NEC 334.80 limits NM-B cable to the 60°C ampacity column. For a 48A EV charger on a 60A breaker that means 4 AWG NM-B, against 6 AWG THHN in conduit when the breaker and charger terminals are marked 75°C.

How much extra wire should I buy?

This builder adds 10% to the one-way run for bends and routing, plus 3 ft at each end to reach the terminals, and rounds up to the next 5 ft. That is a buying allowance, not a code rule. Measure your actual route before you buy.

Does the ground wire get bigger if I upsize for voltage drop?

Yes. NEC 250.122(B) requires the equipment grounding conductor to be increased in proportion to the circular-mil area of the upsized hots. The builder does that automatically when you tick the upsize box.

Is this list enough to pass inspection?

It covers the wire, protection and the devices the code data names. Your jurisdiction may have adopted a different NEC edition or local amendments, and the equipment manual can set a different breaker. 9 states now enforce NEC 2026; check your state and your inspector.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.