RHW Wire

RHW stands for Rubber Heat-resistant Water-resistant. Older wire type in existing installations. Listed in 75C column. Largely replaced by RHW-2.
Dry rating75°C
Wet rating75°C
Voltage600V
LocationsDry, Wet

Specifications

PropertyValue
Full nameRubber Heat-resistant Water-resistant
Insulation materialCross-linked synthetic rubber
Outer coveringMoisture-resistant covering
Temperature rating (dry)75°C (167°F)
Temperature rating (wet)75°C (167°F)
Voltage rating600V
Approved locationsDry, Wet

Advantages and limitations

Advantages: ['Flexible', 'Moisture resistant']
Limitations: ['Larger diameter', 'Largely superseded by RHW-2']

RHW wire ampacity chart

Amps for RHW by size from NEC 2023 Table 310.16. Most circuits up to 100A are sized from the 60° or 75° column; which one is explained below the chart.

RHW ampacity in amperes, NEC 2023 Table 310.16: not more than three current-carrying conductors, 30°C (86°F) ambient. Sizes are AWG; “k” means kcmil.
SizeCopperAluminum
60°75°60°75°
141520* - -
122025*1520*
103035*2530*
840503540
655654050
470855565
3851006575
2951157590
111013085100
1/0125150100120
2/0145175115135
3/0165200130155
4/0195230150180
250k215255170205
300k240285195230
350k260310210250
400k280335225270
500k320380260310

* 240.4(D) limits the breaker on small conductors, whatever the column says: 14 AWG copper 15A, 12 AWG copper 20A, 10 AWG copper 30A, 12 AWG aluminum 15A, 10 AWG aluminum 25A.

RHW is rated 75°C dry, so it can use the columns of NEC 2023 Table 310.16 up to 75°C. The column you actually size with is set by the terminations, per 110.14(C): terminations on circuits of 100A or less, or marked for 14 AWG through 1 AWG, use the 60°C column unless the equipment is listed and marked for 75°C; terminations on larger circuits and conductors use 75°C.

When to use RHW wire

Older wire type in existing installations. Listed in 75C column. Largely replaced by RHW-2.

Common applications for RHW:

NEC code references for RHW

The NEC defines wire insulation types in Table 310.4(1) (formerly Table 310.104(A)). Key sections that apply:

Frequently asked questions about RHW wire

Where can I use RHW wire?

RHW is approved for use in dry, wet per NEC Table 310.4(1). It has a dry temperature rating of 75°C and a wet rating of 75°C. Always verify that your specific installation meets the approved location requirements.

What is the temperature rating of RHW?

RHW is rated 75°C in dry locations and 75°C in wet locations. The ampacity values in NEC Table 310.16 use the 90°C column for conductors rated at or above 90°C, but actual usable ampacity is limited by the termination temperature (typically 75°C per 110.14(C)).

Other wire insulation types

THHN 90°CTHWN 75°CTHWN-2 90°CXHHW 90°CXHHW-2 90°CRHH 90°CRHW-2 90°CUSE-2TW 60°CNM-B 60°CUF-B 60°CMC Cable 90°CAC Cable (BX) 90°CSER/SEU 75°CPV Wire 90°CTHHW 90°CTHW 75°CTHW-2 90°CMI 90°CUF 60°CXHH 90°CFEP 90°CSIS 90°C
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified February 2026 · Report a mistake