Wire Ampacity Chart: NEC Table 310.16 (60/75/90°C)
Ampacity chart: copper and aluminum, amps
| Size | Copper | Aluminum | ||||
|---|---|---|---|---|---|---|
| 60°C | 75°C | 90°C | 60°C | 75°C | 90°C | |
| AWG | ||||||
| 14* | 15 | 20 | 25 | – | – | – |
| 12* | 20 | 25 | 30 | 15 | 20 | 25 |
| 10* | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 | 195 | 230 | 260 | 150 | 180 | 205 |
| kcmil | ||||||
| 250 | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 | 240 | 285 | 320 | 195 | 230 | 260 |
| 350 | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 | 320 | 380 | 430 | 260 | 310 | 350 |
| 600 | 350 | 420 | 475 | 285 | 340 | 385 |
| 700 | 385 | 460 | 520 | 315 | 375 | 425 |
| 750 | 400 | 475 | 535 | 320 | 385 | 435 |
| 800 | 410 | 490 | 555 | 330 | 395 | 445 |
| 900 | 435 | 520 | 585 | 355 | 425 | 480 |
| 1000 | 455 | 545 | 615 | 375 | 445 | 500 |
| 1250 | 495 | 590 | 665 | 405 | 485 | 545 |
| 1500 | 525 | 625 | 705 | 435 | 520 | 585 |
| 1750 | 545 | 650 | 735 | 455 | 545 | 615 |
| 2000 | 555 | 665 | 750 | 470 | 560 | 630 |
*NEC 240.4(D) limits the breaker to 15A for 14 AWG, 20A for 12 AWG and 30A for 10 AWG copper (15A and 25A for 12 and 10 AWG aluminum), whatever the column says. The aluminum columns also apply to copper-clad aluminum. 60°C: TW, UF and NM-B (Romex) per 334.80. 75°C: THW, THWN, XHHW, USE. 90°C: THHN, THWN-2, XHHW-2. On circuits of 100A or less use the 60°C column unless the wire and every terminal are rated 75°C (110.14(C)); the 90°C column is for derating only. Source: NEC 2023 Table 310.16, all values checked against NFPA’s printing of the table on November 14, 2026.
The tables below give the usable ampacity for each insulation type after the 110.14(C) termination limit that applies to most residential and commercial equipment. Select a wire size to see the full derating sequence: base ampacity, temperature correction, bundling adjustment, then the termination limit.
Copper THHN
THHN is rated 90°C, but the equipment terminals cap the usable ampacity (NEC 110.14(C)). On circuits rated 100A or less, or equipment marked for 14 through 1 AWG, use the 60°C column unless both the conductor and the equipment are rated 75°C. The Usable column below assumes 75°C-rated terminations, so check the breaker and device markings before using it. For 14, 12 and 10 AWG, NEC 240.4(D) also caps the breaker size, shown under the Usable value.
| Wire | Usable | 60°C | 75°C | 90°C |
|---|---|---|---|---|
| 14 AWG | 20A Max breaker 15A (240.4(D)) | 15A | 20A | 25A |
| 12 AWG | 25A Max breaker 20A (240.4(D)) | 20A | 25A | 30A |
| 10 AWG | 35A Max breaker 30A (240.4(D)) | 30A | 35A | 40A |
| 8 AWG | 50A | 40A | 50A | 55A |
| 6 AWG | 65A | 55A | 65A | 75A |
| 4 AWG | 85A | 70A | 85A | 95A |
| 3 AWG | 100A | 85A | 100A | 115A |
| 2 AWG | 115A | 95A | 115A | 130A |
| 1 AWG | 130A | 110A | 130A | 145A |
| 1/0 AWG | 150A | 125A | 150A | 170A |
| 2/0 AWG | 175A | 145A | 175A | 195A |
| 3/0 AWG | 200A | 165A | 200A | 225A |
| 4/0 AWG | 230A | 195A | 230A | 260A |
Aluminum THHN
| Wire | Usable | 60°C | 75°C | 90°C |
|---|---|---|---|---|
| 12 AWG | 20A Max breaker 15A (240.4(D)) | 15A | 20A | 25A |
| 10 AWG | 30A Max breaker 25A (240.4(D)) | 25A | 30A | 35A |
| 8 AWG | 40A | 35A | 40A | 45A |
| 6 AWG | 50A | 40A | 50A | 55A |
| 4 AWG | 65A | 55A | 65A | 75A |
| 3 AWG | 75A | 65A | 75A | 85A |
| 2 AWG | 90A | 75A | 90A | 100A |
| 1 AWG | 100A | 85A | 100A | 115A |
| 1/0 AWG | 120A | 100A | 120A | 135A |
| 2/0 AWG | 135A | 115A | 135A | 150A |
| 3/0 AWG | 155A | 130A | 155A | 175A |
| 4/0 AWG | 180A | 150A | 180A | 205A |
Copper XHHW-2
| Wire | Usable | 75°C | 90°C |
|---|---|---|---|
| 14 AWG | 20A Max breaker 15A (240.4(D)) | 20A | 25A |
| 12 AWG | 25A Max breaker 20A (240.4(D)) | 25A | 30A |
| 10 AWG | 35A Max breaker 30A (240.4(D)) | 35A | 40A |
| 8 AWG | 50A | 50A | 55A |
| 6 AWG | 65A | 65A | 75A |
| 4 AWG | 85A | 85A | 95A |
| 3 AWG | 100A | 100A | 115A |
| 2 AWG | 115A | 115A | 130A |
| 1 AWG | 130A | 130A | 145A |
| 1/0 AWG | 150A | 150A | 170A |
| 2/0 AWG | 175A | 175A | 195A |
| 3/0 AWG | 200A | 200A | 225A |
| 4/0 AWG | 230A | 230A | 260A |
Aluminum XHHW-2
| Wire | Usable | 75°C | 90°C |
|---|---|---|---|
| 12 AWG | 20A Max breaker 15A (240.4(D)) | 20A | 25A |
| 10 AWG | 30A Max breaker 25A (240.4(D)) | 30A | 35A |
| 8 AWG | 40A | 40A | 45A |
| 6 AWG | 50A | 50A | 55A |
| 4 AWG | 65A | 65A | 75A |
| 3 AWG | 75A | 75A | 85A |
| 2 AWG | 90A | 90A | 100A |
| 1 AWG | 100A | 100A | 115A |
| 1/0 AWG | 120A | 120A | 135A |
| 2/0 AWG | 135A | 135A | 150A |
| 3/0 AWG | 155A | 155A | 175A |
| 4/0 AWG | 180A | 180A | 205A |
Copper NM-B (Romex)
Build a materials list Pick a project and run length; get wire, breaker, ground and conduit with NEC sections.
Practice ampacity exam questions Ten questions from Table 310.16 and the other NEC tables, each answer cited.
Frequently Asked Questions
What is wire ampacity?
Ampacity is the maximum current (in amps) a conductor can carry continuously without exceeding its temperature rating. NEC Table 310.16 provides ampacity values for conductors in raceway or cable at 30C ambient. The usable ampacity depends on the insulation type, installation conditions, and termination temperature limits per 110.14(C).
What NEC table shows wire ampacity?
NEC Table 310.16 is the primary ampacity table for conductors in raceway, cable, or earth. Table 310.17 covers free-air installations. Table 310.12 covers dwelling service conductors. All tables are based on NEC 2023 (NFPA 70).
What is the ampacity of 12 AWG copper wire?
12 AWG copper THHN is 30A at 90C, 25A at 75C and 20A at 60C per Table 310.16. On circuits of 100A or less, 110.14(C) uses the 60C column unless the conductor and every termination are rated 75C. Either way, 240.4(D) limits 12 AWG copper to a 20A breaker, so it is a 20A circuit wire; the 30A 90C figure is the starting point for derating, not a breaker size. NM-B (Romex) is held to the 60C column, 20A (334.80). See our 12 AWG ampacity page for full derating.
Does wire ampacity change with temperature?
Yes. NEC Table 310.16 assumes 30C (86F) ambient. Higher ambient temperatures reduce ampacity through correction factors from Table 310.15(B)(1). At 40C, a 75C-rated conductor retains 88% of its table ampacity. At 50C (common in attics), it retains only 75%. Use our ampacity calculator to apply temperature correction automatically.
What is the 110.14(C) termination limit?
NEC 110.14(C) limits the temperature rating you can use for ampacity calculations based on the equipment terminals. For circuits 100A or less, use the 60C column unless all terminations are rated 75C. For circuits over 100A, the 75C column applies. That is why 12 AWG THHN (30A at 90C) is a 20A conductor on a typical branch circuit: 60C gives 20A, and 240.4(D) caps its breaker at 20A in any case.
NEC 2023 references verified February 2026 · Report a mistake