NEC 2026 Changes: What's New for Wire Sizing

NEC 2026 (NFPA 70-2026) was published September 2025. Core ampacity values in Table 310.16 are unchanged. If you sized wire correctly under NEC 2023, the same sizing applies under NEC 2026.
PublishedSep 2025
Table 310.16Unchanged
States on NEC 202610 of 50 (November 2026)

What changed in Article 310

TopicNEC 2023NEC 2026Impact
Table 310.16 ampacity valuesCurrent valuesIdenticalNo change
Temperature correction310.15(B)(1)(1)Same sectionNo change
Bundling adjustment310.15(C)(1)Same sectionNo change
Termination limits110.14(C)110.14(C)No change
Minimum conductor size14 AWG copper min16 AWG copper allowed (ampacity listed once checked)Being checked
Copper-clad aluminum (CCA)12 AWG is the smallest size listed14 AWG CCA added (ampacity listed once checked)Being checked
All WireRef ampacity tables and the ampacity calculator produce NEC 2026-valid results because Table 310.16 data is identical between editions.

Why 16 AWG is now allowed

NEC 2026 Section 310.3(A) lowers the minimum conductor size from 14 AWG to 16 AWG copper (and to 14 AWG for copper-clad aluminum). 240.4(D) limits 16 AWG copper to a 10A overcurrent device with continuous loads of 8A or less, and a 10A branch circuit may not supply receptacles (210.18). NEC 2023 Table 310.16 already lists 16 AWG copper, but only in the 90°C column (18A), with no 60°C or 75°C value.

Ampacities not listed yet. We have not yet checked the 2026 ampacities for 16 AWG copper and 14 AWG copper-clad aluminum against the printed NFPA 70-2026 table. We’ll list them once checked against the printed 2026 table. Until then, use the printed 2026 table for any 16 AWG or 14 AWG CCA sizing.

This does not mean you should downsize branch circuits from 14 to 16 AWG. Standard 15A and 20A branch circuits still require 14 AWG or 12 AWG minimum. The 16 AWG allowance is primarily for control, signaling, and equipment circuits.

GFCI and AFCI updates

NEC 2023 was the big expansion cycle for GFCI (kitchens, basements, laundry). NEC 2026 adds refinements:

NewHigh-frequency GFCI
210.8 Informational Note now recognizes devices marked “HF” for VFD and inverter environments. Reduces nuisance tripping from high-frequency leakage.
ChangedEV charging (Art. 625)
Permanently connected EVSE other than at one- and two-family dwellings needs an emergency disconnect 20 to 100 ft from the equipment and in sight of it (625.43). 30A, 50A and 60A receptacles used for EV charging must be listed for EVSE use (625.44). Permanently wired EVSE needs SPGFCI protection starting January 1, 2029 (625.54). See EV charger guide.
ChangedOutdoor outlets (210.8(F))
Dwelling outdoor outlets on circuits up to 60A need GFCI protection (50A in NEC 2023). Listed HVAC equipment needs GFCI or Class C SPGFCI protection from September 1, 2026. See outdoor GFCI.

See all current GFCI requirements by room: kitchen, bathroom, garage, outdoor, basement, laundry, bedroom.

Other notable changes

ChangedArc-flash labeling (110.16)
Mandated on wider range of equipment, aligned with NFPA 70E-2024.
NewSurge protection
Surge protection now required in sleeping areas of fire stations, police stations, and similar emergency-response facilities (dwellings and dormitories were already covered).
ReorganizedCommunications (Ch. 8)
Chapters 1–7 now apply to communications installations via revised Section 90.3, integrating them into the main NEC framework.
MovedLoad calculations (Art. 220 to 120)
Dwelling load calculations relocated from Article 220 to new Article 120. Service/feeder general lighting load drops from 3 to 2 VA/sqft, and the optional calculation’s first tier changes from 10 to 8 kVA at 100%.
NewNon-road EVs (Art. 624)
New article covers electric vehicle equipment for boats, forklifts, golf carts, and other non-road vehicles. Separate from Art. 625 road vehicles.

State adoption status

Each state adopts the NEC on its own schedule. As of November 2026, 10 states enforce NEC 2026 (Arkansas, Colorado, Maine, Maryland, Massachusetts, Minnesota, North Dakota, Oregon, Texas, Wyoming), 21 enforce NEC 2023 and 11 enforce NEC 2020; the rest use an older edition or leave adoption to local jurisdictions. Always verify which edition your local AHJ enforces before starting electrical work.

EditionStatesWireRef data
NEC 202610Ampacity tables apply; check the changes above
NEC 202321The edition WireRef's tables are built from
NEC 202011Ampacity tables apply; some GFCI and receptacle rules differ

What this means for WireRef

WireRef's tables and calculators are built from NEC 2023. The core Table 310.16 ampacity values carry into NEC 2026, so wire sizing answers apply in NEC 2026 states. Load calculations, outdoor GFCI and EV charging rules changed, and pages on those topics say how. Where a page cites a section number, it is the NEC 2023 number unless it says otherwise.

Tools that remain fully accurate: Ampacity calculator · Voltage drop calculator · All ampacity tables · Wire sizing guides · Comparisons

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.