Sub panel wire size chart
Sub panel wire size by breaker
| Feeder breaker | Wire size | Ground (Cu) | Max run, ft | ||
|---|---|---|---|---|---|
| Copper | Alum. | Copper | Alum. | ||
| 30A | 10 | 8 | 10 | 96 | 93 |
| 35A | 8 | 8 | 10 | 131 | 80 |
| 40A | 8 | 8 | 10 | 115 | 70 |
| 45A | 8 | 6 | 10 | 102 | 98 |
| 50A | 8 | 6 | 10 | 92 | 88 |
| 60A | 6 | 4 | 10 | 121 | 117 |
| 70A | 4 | 3 | 8 | 166 | 127 |
| 80A | 4 | 2 | 8 | 145 | 140 |
| 90A | 3 | 2 | 8 | 162 | 125 |
| 100A | 3 | 1 | 8 | 146 | 142 |
| 110A | 2 | 1/0 | 6 | 168 | 162 |
| 125A | 1 | 2/0 | 6 | 186 | 180 |
| 150A | 1/0 | 3/0 | 6 | 196 | 190 |
| 175A | 2/0 | 4/0 | 6 | 212 | 205 |
| 200A | 3/0 | 250k | 6 | 234 | 212 |
Sizes are AWG; “k” means kcmil (250k = 250 kcmil). Assumes individual THWN-2 or XHHW-2 conductors in conduit, breaker and panel lugs marked 75°C, 30°C (86°F) ambient and no more than three current-carrying conductors. NEC 240.4(D) is applied to 10 AWG. NM-B cable and 60°C terminals need a larger size: see the wire size page for your breaker. Source: NEC 2023 Tables 310.16 and 250.122, Chapter 9 Table 8; ampacity values checked November 14, 2026.
Wire size by distance
Find the breaker that feeds the sub panel, then read across to the one-way length of the run. These tables size the wire for the code minimum and for a voltage drop under 3% with the full breaker rating flowing at 240V. The NEC recommends 3% on a feeder in an informational note (215.2(A)); it is a design target, not a mandatory limit. If your calculated load is well below the breaker rating, the voltage drop calculator will often show a smaller size is enough.
Copper feeder
| Amps | One-way run, feet | ||||||
|---|---|---|---|---|---|---|---|
| 25 | 50 | 75 | 100 | 150 | 200 | 300 | |
| 30A | 10 | 10 | 10 | 8gnd 8 | 8gnd 8 | 6gnd 6 | 4gnd 4 |
| 35A | 8 | 8 | 8 | 8 | 6gnd 8 | 6gnd 8 | 4gnd 4 |
| 40A | 8 | 8 | 8 | 8 | 6gnd 8 | 4gnd 4 | 3gnd 4 |
| 45A | 8 | 8 | 8 | 8 | 6gnd 8 | 4gnd 4 | 3gnd 4 |
| 50A | 8 | 8 | 8 | 6gnd 8 | 4gnd 4 | 4gnd 4 | 2gnd 4 |
| 60A | 6 | 6 | 6 | 6 | 4gnd 6 | 3gnd 6 | 2gnd 4 |
| 70A | 4 | 4 | 4 | 4 | 4 | 3gnd 6 | 1gnd 4 |
| 80A | 4 | 4 | 4 | 4 | 3gnd 6 | 2gnd 4 | 1/0gnd 3 |
| 90A | 3 | 3 | 3 | 3 | 3 | 2gnd 6 | 1/0gnd 4 |
| 100A | 3 | 3 | 3 | 3 | 2gnd 6 | 1gnd 4 | 2/0gnd 3 |
| 110A | 2 | 2 | 2 | 2 | 2 | 1gnd 4 | 2/0gnd 2 |
| 125A | 1 | 1 | 1 | 1 | 1 | 1/0gnd 4 | 3/0gnd 3 |
| 150A | 1/0 | 1/0 | 1/0 | 1/0 | 1/0 | 2/0gnd 4 | 3/0gnd 4 |
| 175A | 2/0 | 2/0 | 2/0 | 2/0 | 2/0 | 2/0 | 4/0gnd 4 |
| 200A | 3/0 | 3/0 | 3/0 | 3/0 | 3/0 | 3/0 | 250kgnd 4 |
Aluminum feeder
| Amps | One-way run, feet | ||||||
|---|---|---|---|---|---|---|---|
| 25 | 50 | 75 | 100 | 150 | 200 | 300 | |
| 30A | 8 | 8 | 8 | 6gnd 8 | 4gnd 4 | 4gnd 4 | 2gnd 4 |
| 35A | 8 | 8 | 8 | 6gnd 8 | 4gnd 4 | 4gnd 4 | 2gnd 4 |
| 40A | 8 | 8 | 6gnd 8 | 6gnd 8 | 4gnd 4 | 3gnd 4 | 1gnd 3 |
| 45A | 6 | 6 | 6 | 4gnd 6 | 4gnd 6 | 2gnd 4 | 1gnd 4 |
| 50A | 6 | 6 | 6 | 4gnd 6 | 3gnd 6 | 2gnd 4 | 1/0gnd 3 |
| 60A | 4 | 4 | 4 | 4 | 2gnd 8 | 1gnd 6 | 2/0gnd 4 |
| 70A | 3 | 3 | 3 | 3 | 2gnd 6 | 1gnd 4 | 2/0gnd 3 |
| 80A | 2 | 2 | 2 | 2 | 1gnd 6 | 1/0gnd 4 | 3/0gnd 3 |
| 90A | 2 | 2 | 2 | 2 | 1gnd 6 | 2/0gnd 4 | 3/0gnd 3 |
| 100A | 1 | 1 | 1 | 1 | 1/0gnd 6 | 2/0gnd 4 | 4/0gnd 3 |
| 110A | 1/0 | 1/0 | 1/0 | 1/0 | 1/0 | 2/0gnd 4 | 4/0gnd 3 |
| 125A | 2/0 | 2/0 | 2/0 | 2/0 | 2/0 | 3/0gnd 4 | 250kgnd 3 |
| 150A | 3/0 | 3/0 | 3/0 | 3/0 | 3/0 | 4/0gnd 4 | 300kgnd 3 |
| 175A | 4/0 | 4/0 | 4/0 | 4/0 | 4/0 | 4/0 | 350kgnd 3 |
| 200A | 250k | 250k | 250k | 250k | 250k | 250k | 400kgnd 3 |
Example: a 100A sub panel in a detached garage 200 ft from the main panel. The code minimum is 1 AWG aluminum, which stays under 3% only to 142 ft. At 200 ft the table gives 2/0 AWG aluminum (2.65% drop), and the copper ground grows from 8 AWG to 4 AWG to match.
Why the ground wire grows with the feeder
NEC 250.122(B) says that when the feeder conductors are made larger than the minimum, for voltage drop for example, the equipment grounding conductor has to be increased by the same proportion of circular-mil area. The small “gnd” figure in each shaded cell is that larger copper ground. Unshaded cells use the Table 250.122 size in the first table.
What the feeder needs besides the right size
A feeder to a 120/240V sub panel has four conductors: two hots, a neutral and an equipment ground. The neutral bar in the sub panel is kept separate from the ground bar and the enclosure. A sub panel in a detached building also needs its own grounding electrode (NEC 250.32(A)). The steps are in the sub panel installation guide and the detached garage wiring guide.
The smaller sizes NEC 310.12 allows for a dwelling service (2/0 copper or 4/0 aluminum at 200A) apply only to a service or a feeder that carries the whole load of the dwelling. A sub panel that carries part of the load is sized from Table 310.16, as on this page.
For a buried run, check the burial depth chart for the cover your conduit or cable needs, and the standard breaker sizes if your load falls between two ratings.
Frequently asked questions
What size wire do I need for a 100 amp sub panel?
3 AWG copper or 1 AWG aluminum, with a 8 AWG copper equipment ground, for conductors in conduit on 75°C terminals (NEC Table 310.16 and Table 250.122). At 240V and a full 100A load those sizes stay under 3% voltage drop up to 146 ft in copper and 142 ft in aluminum.
What size wire for a 60 amp sub panel?
6 AWG copper or 4 AWG aluminum, with a 10 AWG copper equipment ground, for conductors in conduit on 75°C terminals (NEC Table 310.16 and Table 250.122). At 240V and a full 60A load those sizes stay under 3% voltage drop up to 121 ft in copper and 117 ft in aluminum.
What size wire for a 125 amp sub panel?
1 AWG copper or 2/0 AWG aluminum, with a 6 AWG copper equipment ground, for conductors in conduit on 75°C terminals (NEC Table 310.16 and Table 250.122). At 240V and a full 125A load those sizes stay under 3% voltage drop up to 186 ft in copper and 180 ft in aluminum.
What size aluminum wire for a 150 amp sub panel?
3/0 AWG aluminum, with a 6 AWG copper equipment ground, on 75°C terminals (NEC Table 310.16). That size holds a full 150A load under 3% voltage drop up to 190 ft at 240V. The lugs must be marked for aluminum conductors.
How far can I run a sub panel feeder before I need bigger wire?
It depends on the load and the wire. With the full breaker rating as the load at 240V, the code-minimum copper feeder stays under 3% voltage drop to 121 ft at 60A, 146 ft at 100A and 234 ft at 200A. A 60A copper feeder at 150 ft needs 4 AWG instead of 6 AWG.
Does the ground wire have to be bigger when I upsize for voltage drop?
Yes. NEC 250.122(B) requires the equipment grounding conductor to be increased in proportion to the feeder conductors. For a 100A aluminum feeder upsized from 1 AWG to 2/0 AWG, the copper ground goes from 8 AWG to 4 AWG.
NEC 2023 references verified February 2026