Ground Wire Size Chart: NEC Table 250.122
NEC Table 250.122 (equipment grounding conductor)
Each row is the largest overcurrent device rating it covers. A breaker between two rows uses the next larger row: a 30A breaker falls in the 60A row.
| Breaker, not over | Copper | Al |
|---|---|---|
| 15A | 14 AWG | 12 AWG |
| 20A | 12 AWG | 10 AWG |
| 60A | 10 AWG | 8 AWG |
| 100A | 8 AWG | 6 AWG |
| 200A | 6 AWG | 4 AWG |
| 300A | 4 AWG | 2 AWG |
| 400A | 3 AWG | 1 AWG |
| 500A | 2 AWG | 1/0 AWG |
| 600A | 1 AWG | 2/0 AWG |
| 800A | 1/0 AWG | 3/0 AWG |
| 1000A | 2/0 AWG | 4/0 AWG |
| 1200A | 3/0 AWG | 250 kcmil |
| 1600A | 4/0 AWG | 350 kcmil |
| 2000A | 250 kcmil | 400 kcmil |
| 2500A | 350 kcmil | 600 kcmil |
| 3000A | 400 kcmil | 600 kcmil |
| 4000A | 500 kcmil | 750 kcmil |
| 5000A | 700 kcmil | 1250 kcmil |
| 6000A | 800 kcmil | 1250 kcmil |
Two rules change the table answer. 250.122(A): the equipment grounding conductor is not required to be larger than the circuit conductors supplying the equipment. 250.122(B): if the ungrounded conductors are made larger for any reason other than the 310.15 ampacity adjustments (for voltage drop, for example), a wire-type equipment grounding conductor must be increased in proportion to the increase in circular mil area. NEC 2026 keeps the table and moves the upsizing rule to 250.122(D).
Feeding a sub panel or a generator? The sub panel wire size chart and the generator wire size chart give the ground wire for each feeder size, including the larger ground a long run needs.
Ground wire size by breaker
| Breaker | Copper EGC | Aluminum EGC | Guide |
|---|---|---|---|
| 15A | 14 AWG | 12 AWG | Details |
| 20A | 12 AWG | 10 AWG | Details |
| 25A | 10 AWG | 8 AWG | Details |
| 30A | 10 AWG | 8 AWG | Details |
| 40A | 10 AWG | 8 AWG | Details |
| 50A | 10 AWG | 8 AWG | Details |
| 60A | 10 AWG | 8 AWG | Details |
| 70A | 8 AWG | 6 AWG | Details |
| 80A | 8 AWG | 6 AWG | Details |
| 90A | 8 AWG | 6 AWG | Details |
| 100A | 8 AWG | 6 AWG | Details |
| 125A | 6 AWG | 4 AWG | Details |
| 150A | 6 AWG | 4 AWG | Details |
| 175A | 6 AWG | 4 AWG | Details |
| 200A | 6 AWG | 4 AWG | Details |
| 300A | 4 AWG | 2 AWG | Details |
| 400A | 3 AWG | 1 AWG | Details |
| 500A | 2 AWG | 1/0 AWG | Details |
| 600A | 1 AWG | 2/0 AWG | Details |
| 800A | 1/0 AWG | 3/0 AWG | Details |
| 1000A | 2/0 AWG | 4/0 AWG | Details |
| 1200A | 3/0 AWG | 250 kcmil | Details |
| 1600A | 4/0 AWG | 350 kcmil | Details |
| 2000A | 250 kcmil | 400 kcmil | Details |
Grounding electrode conductor (Table 250.66)
The grounding electrode conductor connects the service to the ground rod, water pipe or concrete-encased electrode. It is sized from the largest service-entrance conductor, not from the breaker.
| Largest Service Conductor (Cu) | Largest Service Conductor (Al) | GEC Copper | GEC Aluminum |
|---|---|---|---|
| 2 AWG or smaller | 1/0 AWG or smaller | 8 AWG | 6 AWG |
| 1 AWG or 1/0 AWG | 2/0 AWG or 3/0 AWG | 6 AWG | 4 AWG |
| 2/0 AWG or 3/0 AWG | 4/0 AWG or 250 kcmil | 4 AWG | 2 AWG |
| Over 3/0 through 350 kcmil | Over 250 through 500 kcmil | 2 AWG | 1/0 AWG |
| Over 350 through 600 kcmil | Over 500 through 900 kcmil | 1/0 AWG | 3/0 AWG |
| Over 600 through 1100 kcmil | Over 900 through 1750 kcmil | 2/0 AWG | 4/0 AWG |
| Over 1100 kcmil | Over 1750 kcmil | 3/0 AWG | 250 kcmil |
Frequently asked questions
What size ground wire do I need for a 200 amp service?
It depends which ground wire. The equipment grounding conductor on a 200A feeder is 6 AWG copper or 4 AWG aluminum per Table 250.122. The grounding electrode conductor from the service to the ground rod or other electrode is sized from the service conductors with Table 250.66, below. See the 200A ground wire page for both.
Is the ground wire sized by the wire or by the breaker?
By the breaker. Table 250.122 sizes the equipment grounding conductor from the rating of the overcurrent device ahead of the circuit, not from the size of the circuit conductors. A breaker rating between two rows uses the next larger row.
What size ground wire for a 60 amp circuit?
10 AWG copper or 8 AWG aluminum. Any breaker over 20A up to 60A uses the same Table 250.122 row.
Code text: NEC Article 250, grounding and bonding.
NEC 2023 references verified February 2026 · Report a mistake