Ground Wire Size Chart: NEC Table 250.122

The ground wire (equipment grounding conductor) is sized by the breaker, per NEC Table 250.122. Copper: 14 AWG for 15A, 12 AWG for 20A, 10 AWG for 25A to 60A, 8 AWG up to 100A and 6 AWG up to 200A.

NEC Table 250.122 (equipment grounding conductor)

Each row is the largest overcurrent device rating it covers. A breaker between two rows uses the next larger row: a 30A breaker falls in the 60A row.

Minimum size equipment grounding conductor for grounding raceway and equipment, NEC 2023 Table 250.122. Al = aluminum or copper-clad aluminum.
Breaker, not overCopperAl
15A14 AWG12 AWG
20A12 AWG10 AWG
60A10 AWG8 AWG
100A8 AWG6 AWG
200A6 AWG4 AWG
300A4 AWG2 AWG
400A3 AWG1 AWG
500A2 AWG1/0 AWG
600A1 AWG2/0 AWG
800A1/0 AWG3/0 AWG
1000A2/0 AWG4/0 AWG
1200A3/0 AWG250 kcmil
1600A4/0 AWG350 kcmil
2000A250 kcmil400 kcmil
2500A350 kcmil600 kcmil
3000A400 kcmil600 kcmil
4000A500 kcmil750 kcmil
5000A700 kcmil1250 kcmil
6000A800 kcmil1250 kcmil

Two rules change the table answer. 250.122(A): the equipment grounding conductor is not required to be larger than the circuit conductors supplying the equipment. 250.122(B): if the ungrounded conductors are made larger for any reason other than the 310.15 ampacity adjustments (for voltage drop, for example), a wire-type equipment grounding conductor must be increased in proportion to the increase in circular mil area. NEC 2026 keeps the table and moves the upsizing rule to 250.122(D).

Feeding a sub panel or a generator? The sub panel wire size chart and the generator wire size chart give the ground wire for each feeder size, including the larger ground a long run needs.

Ground wire size by breaker

BreakerCopper EGCAluminum EGCGuide
15A14 AWG12 AWGDetails
20A12 AWG10 AWGDetails
25A10 AWG8 AWGDetails
30A10 AWG8 AWGDetails
40A10 AWG8 AWGDetails
50A10 AWG8 AWGDetails
60A10 AWG8 AWGDetails
70A8 AWG6 AWGDetails
80A8 AWG6 AWGDetails
90A8 AWG6 AWGDetails
100A8 AWG6 AWGDetails
125A6 AWG4 AWGDetails
150A6 AWG4 AWGDetails
175A6 AWG4 AWGDetails
200A6 AWG4 AWGDetails
300A4 AWG2 AWGDetails
400A3 AWG1 AWGDetails
500A2 AWG1/0 AWGDetails
600A1 AWG2/0 AWGDetails
800A1/0 AWG3/0 AWGDetails
1000A2/0 AWG4/0 AWGDetails
1200A3/0 AWG250 kcmilDetails
1600A4/0 AWG350 kcmilDetails
2000A250 kcmil400 kcmilDetails

Grounding electrode conductor (Table 250.66)

The grounding electrode conductor connects the service to the ground rod, water pipe or concrete-encased electrode. It is sized from the largest service-entrance conductor, not from the breaker.

Largest Service Conductor (Cu)Largest Service Conductor (Al)GEC CopperGEC Aluminum
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 AWG or 1/0 AWG2/0 AWG or 3/0 AWG6 AWG4 AWG
2/0 AWG or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 through 350 kcmilOver 250 through 500 kcmil2 AWG1/0 AWG
Over 350 through 600 kcmilOver 500 through 900 kcmil1/0 AWG3/0 AWG
Over 600 through 1100 kcmilOver 900 through 1750 kcmil2/0 AWG4/0 AWG
Over 1100 kcmilOver 1750 kcmil3/0 AWG250 kcmil

Frequently asked questions

What size ground wire do I need for a 200 amp service?

It depends which ground wire. The equipment grounding conductor on a 200A feeder is 6 AWG copper or 4 AWG aluminum per Table 250.122. The grounding electrode conductor from the service to the ground rod or other electrode is sized from the service conductors with Table 250.66, below. See the 200A ground wire page for both.

Is the ground wire sized by the wire or by the breaker?

By the breaker. Table 250.122 sizes the equipment grounding conductor from the rating of the overcurrent device ahead of the circuit, not from the size of the circuit conductors. A breaker rating between two rows uses the next larger row.

What size ground wire for a 60 amp circuit?

10 AWG copper or 8 AWG aluminum. Any breaker over 20A up to 60A uses the same Table 250.122 row.

Code text: NEC Article 250, grounding and bonding.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified February 2026 · Report a mistake