Wire Amp Calculator
Calculate the usable ampacity of any conductor after temperature correction, bundling adjustment, and the 110.14(C) termination limit that most amp calculators skip.
How the calculation works
This calculator implements the NEC 2023 ampacity derating chain in four steps. Most online calculators skip step 4, which often controls the final answer.
Step 1: Base ampacity from Table 310.16
Read the conductor’s ampacity from NEC Table 310.16 in the column for its insulation rating. THHN is rated 90°C, so it starts from the 90°C column.
Step 2: Correct for ambient temperature
Above 30°C (86°F), multiply by the correction factor from Table 310.15(B)(1)(1), using the insulation rating’s column, not the termination rating.
Step 3: Adjust for more than three conductors
More than three current-carrying conductors in one raceway or cable multiply by the factor in Table 310.15(C)(1). Equipment grounding conductors do not count, and neither does a neutral that carries only the unbalanced current (310.15(E)(1)).
Step 4: Cap at the termination rating
The result cannot exceed the Table 310.16 value for the terminations’ temperature rating (110.14(C)). On circuits of 100A or less, or terminals marked for 14 through 1 AWG, that is the 60°C column unless the equipment is listed and marked for 75°C. Check the breaker and device markings before choosing 75°C.
Worked example
12 AWG copper THHN, six current-carrying conductors in one raceway, 40°C (104°F) ambient, 75°C terminations: 30A × 0.91 = 27.3A, then × 0.8 = 21.84A. That is under the 25A termination limit, so the usable ampacity is 21A (rounded down), and 240.4(D) still limits the breaker on 12 AWG copper to 20A.
Frequently asked questions
Why does the 110.14(C) termination limit matter?
NEC 110.14(C) requires that conductors be used within the temperature limitations of their terminations. Most circuit breakers, receptacles, and switches are rated for 75C. Even if your THHN wire is rated for 90C, the connection point limits what ampacity you can actually use. This is why "usable ampacity" often differs from the ampacity that appears in simplified charts.
When can I use the 90C column for final ampacity?
You can use the full 90C ampacity only when both ends of the circuit terminate on equipment that is listed and marked for 90C. This is uncommon in residential work but may apply in some industrial installations. The 90C column is always used as the starting point for derating calculations (Steps 2 and 3) per 310.15(B), even when the final ampacity is limited by Step 4.
How do I count current-carrying conductors?
Count all phase and neutral conductors that carry load current. Do not count equipment grounding conductors. Do not count a neutral that carries only unbalanced current from two ungrounded conductors (per 310.15(B)(5) exception). In a typical 120/240V circuit, the neutral carries only the unbalance and does not count. In a 3-phase 4-wire wye system with nonlinear loads, the neutral carries harmonic currents and must be counted.
Does this calculator work for NEC 2026?
NEC 2026 reorganized Article 310 numbering but did not change the fundamental ampacity values in Table 310.16 or the derating methodology. The calculation chain (base ampacity, temperature correction, bundling adjustment, termination limit) remains the same. WireRef will update table references when NEC 2026 is widely adopted. See NEC 2026 changes.
NEC 2023 references verified February 2026 · Report a mistake