What wire size for a 60 amp circuit?
Building one of these? Get the full materials list: EV charger, 48A (hardwired), Subpanel feeder, 60A.
All valid wire sizes for a 60 amp circuit
A 60 amp circuit handles subpanels, hot tubs, and the most powerful residential EV chargers (48A continuous). The minimum 60 amp wire size is 6 AWG copper or 4 AWG aluminum.
Feeding a sub panel with this circuit? The sub panel wire size chart shows the 60A feeder size against run length, with the ground wire for each case.
Any gauge with ampacity equal to or greater than 60A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.
| Gauge | Material | Capacity | Max distance (3% drop) | Conduit |
|---|---|---|---|---|
| 6 AWG (minimum) | Copper | 65A | 121 ft | 3/4" EMT |
| 4 AWG | Copper | 85A | 194 ft | 1" EMT |
| 3 AWG | Copper | 100A | 243 ft | 1" EMT |
| 2 AWG | Copper | 115A | 309 ft | 1-1/4" EMT |
| 1 AWG | Copper | 130A | 389 ft | 1-1/4" EMT |
| 1/0 AWG | Copper | 150A | 491 ft | 1-1/2" EMT |
| 2/0 AWG | Copper | 175A | 625 ft | 1-1/2" EMT |
| 3/0 AWG | Copper | 200A | 789 ft | 2" EMT |
| 4/0 AWG | Copper | 230A | 1000 ft | 2" EMT |
| 4 AWG (minimum) | Aluminum | 65A | 118 ft | 1" EMT |
| 3 AWG | Aluminum | 75A | 148 ft | 1" EMT |
| 2 AWG | Aluminum | 90A | 188 ft | 1-1/4" EMT |
| 1 AWG | Aluminum | 100A | 238 ft | 1-1/4" EMT |
| 1/0 AWG | Aluminum | 120A | 300 ft | 1-1/2" EMT |
| 2/0 AWG | Aluminum | 135A | 375 ft | 1-1/2" EMT |
| 3/0 AWG | Aluminum | 155A | 476 ft | 2" EMT |
| 4/0 AWG | Aluminum | 180A | 600 ft | 2" EMT |
Maximum wire run distance
One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.
| Gauge | Material | 120V | 208V | 240V | 480V |
|---|---|---|---|---|---|
| 6 AWG | Copper | 61 ft | 106 ft | 121 ft | 243 ft |
| 4 AWG | Copper | 97 ft | 168 ft | 194 ft | 389 ft |
| 3 AWG | Copper | 122 ft | 212 ft | 243 ft | 491 ft |
| 2 AWG | Copper | 154 ft | 267 ft | 309 ft | 625 ft |
| 1 AWG | Copper | 194 ft | 337 ft | 389 ft | 769 ft |
| 1/0 AWG | Copper | 245 ft | 428 ft | 491 ft | 1000 ft |
| 2/0 AWG | Copper | 309 ft | 535 ft | 625 ft | 1250 ft |
| 3/0 AWG | Copper | 389 ft | 681 ft | 789 ft | 1578 ft |
| 4/0 AWG | Copper | 491 ft | 857 ft | 1000 ft | 2000 ft |
| 4 AWG | Aluminum | 59 ft | 102 ft | 118 ft | 236 ft |
| 3 AWG | Aluminum | 74 ft | 128 ft | 148 ft | 297 ft |
| 2 AWG | Aluminum | 94 ft | 163 ft | 188 ft | 375 ft |
| 1 AWG | Aluminum | 118 ft | 205 ft | 238 ft | 476 ft |
| 1/0 AWG | Aluminum | 149 ft | 258 ft | 300 ft | 600 ft |
| 2/0 AWG | Aluminum | 188 ft | 326 ft | 375 ft | 750 ft |
| 3/0 AWG | Aluminum | 238 ft | 410 ft | 476 ft | 937 ft |
| 4/0 AWG | Aluminum | 300 ft | 517 ft | 600 ft | 1200 ft |
Common 60A circuit projects
- 60A subpanel
- hot tub/spa wiring
- Level 2 EV charger (48A)
- 60A sub panel for garage
Frequently asked questions
What is the minimum wire size for a 60 amp circuit?
6 AWG copper or 4 AWG aluminum per NEC 2023 Table 310.16 with 110.14(C) termination limits. For long runs, you may need to upsize for voltage drop. See the max distance table above.
What size NM-B (Romex) for a 60 amp circuit?
NM-B ampacity comes from the 60°C column of NEC Table 310.16 (334.80), so above 30A it can need a larger size than wire in conduit on 75°C terminals. 4 AWG copper NM-B is rated 70A, enough for a 60A breaker. 6 AWG NM-B is rated 55A, which is not a standard breaker size, so 240.4(B) allows it on a 60A breaker when the circuit does not feed more than one receptacle for cord-and-plug loads and the load itself is 55A or less. That does not work for a continuous load such as an EV charger, where the cable ampacity must be at least 125% of the load. NM-B is for dry indoor locations only; outdoors or underground, use wire in conduit or UF-B. See the NM-B ampacity chart.
Can I use aluminum wire for a 60 amp circuit?
Yes. 4 AWG aluminum handles 60A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 6 AWG copper vs aluminum comparison.
How far can I run 6 AWG wire on a 60 amp circuit?
At 240V, 6 AWG copper can run approximately 121 feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.
What breaker size for a 60 amp circuit?
Use a 60A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).
Do I need GFCI on a 60 amp circuit?
GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.
Common products for 6 AWG Copper circuits
As an Amazon Associate we earn from qualifying purchases.
NEC 2023 references verified February 2026 · Report a mistake