NEC ReferenceNEC 2023 · 2026 · Updated May 2026

NEC Article 334: NM-B Cable (Romex) Rules

NEC Article 334: NM-B Cable (Romex) covers Where NM-B Is Permitted through Ampacity. This guide explains each section with practical interpretation, common mistakes, and how these rules apply to real projects.

334.10 Where NM-B Is Permitted

NM-B (commonly called Romex) is permitted in one- and two-family dwellings and multifamily dwellings of Types III, IV, and V construction (generally wood-frame buildings 3 stories or fewer). It can be run concealed within walls, floors, and ceilings, or exposed in dry locations.

NM-B may also run through air voids of masonry block walls if the location is not subject to dampness. NM-B is the most common residential wiring method in the United States because it is inexpensive, quick to install, and includes the ground conductor built into the cable assembly.

A single run of 12/2 NM-B provides hot, neutral, and ground in one pull.

334.12 Where NM-B Is NOT Permitted

NM-B is NOT permitted in several important locations: any building exceeding 3 floors above grade, commercial buildings of Types I and II construction (steel and concrete frame), embedded in poured concrete or aggregate, exposed in dropped or suspended ceilings used as plenums, in wet or damp locations, in hazardous (classified) locations, or underground (direct burial).

NM-B also cannot be run inside conduit as a general rule, though 334.15 provides specific allowances for short riser protection. These restrictions are why commercial and industrial work relies on conduit with individual THHN conductors or MC cable.

334.30 Securing and Supporting

NM-B must be secured within 12 inches of every box entry and supported at intervals not exceeding 4.5 feet along the run per 334.30. Cable clamps are required at all box entries. Flat NM-B cables (like 14/2 and 12/2) must be stapled flat against the framing member, not on edge, to prevent damage.

Staples must be driven snug but not so tight that they deform or crush the cable jacket. In accessible attics with permanent stairs, cables within 6 feet of the scuttle opening must be protected by guard strips or run through bored holes in joists. Cables running across the tops of ceiling joists must be protected if the attic is accessible.

334.15 Protection from Damage

NEC 300.4 and 334.15 work together to protect NM-B from physical damage. When boring through wood studs, the edge of the hole must be at least 1-1/4 inches from the nearest edge of the stud per 300.4(A)(1). If the hole is closer than 1-1/4 inches, a 1/16-inch thick steel nail plate covering the bored area is required.

Cables run in notches in studs or joists must also be protected by steel plates. In unfinished basements, NM-B may be run along the underside of floor joists if the cable follows the surface of the framing, but cables run at an angle to joists must be protected by running boards or bored through joists.

In garages, cables within 8 feet of the floor are considered subject to physical damage and must be protected by conduit, guard strips, or concealment within the wall.

334.80 Ampacity

NM-B cable contains conductors rated 90C (THHN-equivalent insulation) inside an outer sheath rated 60C. Per NEC 334.80, the ampacity of NM-B must be determined using the 60C column of Table 310.16: 14 AWG = 15A, 12 AWG = 20A, 10 AWG = 30A, 8 AWG = 40A, 6 AWG = 55A.

However, the 90C individual conductor rating provides a critical advantage when derating is required. For temperature correction or bundling adjustment calculations, you start with the 90C ampacity value, apply the correction factors, and then check that the result does not fall below the 60C column ampacity.

This gives NM-B significantly more derating headroom than wire types with only 60C ratings. See our NM-B wire type page for complete ampacity tables with derating pre-computed.

Frequently Asked Questions

What does NEC Article 334 cover?

Article 334 covers nm-b cable (romex) requirements. Key sections include 334.10 Where NM-B Is Permitted and 334.12 Where NM-B Is NOT Permitted. It applies to all electrical installations in the United States.

Where can I find the full text of Article 334?

The full NEC is published by NFPA and available at nfpa.org. Many libraries provide free access. Your local building department also has copies available for reference during permit applications.

Does Article 334 apply to existing wiring?

The NEC applies to new installations, modifications, and additions. Existing wiring that was code-compliant when installed is generally grandfathered unless a renovation triggers an upgrade requirement. Check with your local AHJ (authority having jurisdiction).

When did the current Article 334 requirements take effect?

NEC 2026 is the latest published edition (effective September 2025). NEC 2023 remains the most widely adopted edition by states. Adoption varies - check your state adoption status on our state code pages.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
This guide provides practical interpretation of NEC requirements. Always verify with your local AHJ and the current NEC edition adopted in your jurisdiction. WireRef is a reference tool and does not replace licensed professional judgment.

NEC references verified May 2026