XHH Wire

XHH stands for Cross-linked polyethylene High Heat-resistant. Dry locations where 90C rating needed. XHHW/XHHW-2 preferred when wet rating also needed.
Dry rating90°C
Voltage600V
LocationsDry only

Specifications

PropertyValue
Full nameCross-linked polyethylene High Heat-resistant
Insulation materialCross-linked polyethylene (XLPE)
Outer coveringNone
Temperature rating (dry)90°C (194°F)
Voltage rating600V
Approved locationsDry only

Advantages and limitations

Advantages: ['90C dry rating', 'Good chemical resistance']
Limitations: ['Dry locations only', 'XHHW-2 is more versatile']

XHH wire ampacity chart

Amps for XHH by size from NEC 2023 Table 310.16. Most circuits up to 100A are sized from the 60° or 75° column; which one is explained below the chart.

XHH ampacity in amperes, NEC 2023 Table 310.16: not more than three current-carrying conductors, 30°C (86°F) ambient. Sizes are AWG; “k” means kcmil.
SizeCopperAluminum
60°75°90°60°75°90°
141520*25* - - -
122025*30*1520*25*
103035*40*2530*35*
8405055354045
6556575405055
4708595556575
385100115657585
2951151307590100
111013014585100115
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205
250k215255290170205230
300k240285320195230260
350k260310350210250280
400k280335380225270305
500k320380430260310350

* 240.4(D) limits the breaker on small conductors, whatever the column says: 14 AWG copper 15A, 12 AWG copper 20A, 10 AWG copper 30A, 12 AWG aluminum 15A, 10 AWG aluminum 25A.

XHH is rated 90°C dry, so it can use the columns of NEC 2023 Table 310.16 up to 90°C. The column you actually size with is set by the terminations, per 110.14(C): terminations on circuits of 100A or less, or marked for 14 AWG through 1 AWG, use the 60°C column unless the equipment is listed and marked for 75°C; terminations on larger circuits and conductors use 75°C. The 90°C column is the starting point for heat and bundling derating, not a breaker size.

XHH by itself is not rated for wet locations. Wire marked with a wet rating as well (such as THHN/THWN-2) can use that rating outdoors in conduit.

When to use XHH wire

Dry locations where 90C rating needed. XHHW/XHHW-2 preferred when wet rating also needed.

Common applications for XHH:

NEC code references for XHH

The NEC defines wire insulation types in Table 310.4(1) (formerly Table 310.104(A)). Key sections that apply:

Frequently asked questions about XHH wire

Where can I use XHH wire?

XHH is approved for use in dry only per NEC Table 310.4(1). It has a dry temperature rating of 90°C. Always verify that your specific installation meets the approved location requirements.

What is the temperature rating of XHH?

XHH is rated 90°C in dry locations. The ampacity values in NEC Table 310.16 use the 90°C column for conductors rated at or above 90°C, but actual usable ampacity is limited by the termination temperature (typically 75°C per 110.14(C)).

Other wire insulation types

THHN 90°CTHWN 75°CTHWN-2 90°CXHHW 90°CXHHW-2 90°CRHH 90°CRHW-2 90°CUSE-2TW 60°CNM-B 60°CUF-B 60°CMC Cable 90°CAC Cable (BX) 90°CSER/SEU 75°CPV Wire 90°CTHHW 90°CTHW 75°CTHW-2 90°CRHW 75°CMI 90°CUF 60°CFEP 90°CSIS 90°C
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified February 2026 · Report a mistake