Standard breaker sizes
Standard breaker size chart
| 10 | 15 | 20 | 25 | 30 |
| 35 | 40 | 45 | 50 | 60 |
| 70 | 80 | 90 | 100 | 110 |
| 125 | 150 | 175 | 200 | 225 |
| 250 | 300 | 350 | 400 | 450 |
| 500 | 600 | 700 | 800 | 1000 |
| 1200 | 1600 | 2000 | 2500 | 3000 |
| 4000 | 5000 | 6000 |
Fuses have 4 more standard ratings: 1, 3, 6 and 601 amps. Breakers and fuses with other ratings are permitted; they are just not “standard” for the rules that refer to this list. A given panel accepts only the breakers its label lists. Source: NEC 2023 Table 240.6(A), checked against NFPA’s printing of the table on November 14, 2026.
Continuous load each size can carry
A load that runs for three hours or more is a continuous load. The breaker must be rated at least 125% of it (NEC 210.20(A) for branch circuits, 215.3 for feeders), which is the same as loading a standard breaker to no more than 80% of its rating. Breakers listed for 100% operation are the exception.
| Breaker | Continuous | Breaker | Continuous |
|---|---|---|---|
| 10A | 8A | 70A | 56A |
| 15A | 12A | 80A | 64A |
| 20A | 16A | 90A | 72A |
| 25A | 20A | 100A | 80A |
| 30A | 24A | 110A | 88A |
| 35A | 28A | 125A | 100A |
| 40A | 32A | 150A | 120A |
| 45A | 36A | 175A | 140A |
| 50A | 40A | 200A | 160A |
| 60A | 48A |
When you may use the next size up
Wire ampacities do not always land on a standard breaker size. NEC 240.4(B) lets you use the next standard size above the wire’s ampacity when all three of these are true: the ampacity does not match a standard rating, the next standard rating is 800A or less, and the circuit is not a branch circuit feeding more than one receptacle for cord-and-plug portable loads. The load itself must still be no more than the wire’s ampacity.
| Copper wire | Ampacity | Breaker | How |
|---|---|---|---|
| 8 | 50A | 50A | Exact match |
| 6 | 65A | 70A | Next size up |
| 4 | 85A | 90A | Next size up |
| 3 | 100A | 100A | Exact match |
| 2 | 115A | 125A | Next size up |
| 1 | 130A | 150A | Next size up |
| 1/0 | 150A | 150A | Exact match |
| 2/0 | 175A | 175A | Exact match |
| 3/0 | 200A | 200A | Exact match |
| 4/0 | 230A | 250A | Next size up |
Sizes are AWG. 14, 12 and 10 AWG copper are not in this table because NEC 240.4(D) limits their breakers to 15A, 20A and 30A. On circuits of 100A or less, use the 60°C ampacity unless the wire and every terminal are rated 75°C (110.14(C)); see the ampacity chart.
MCA and MOCP on an equipment nameplate
Air conditioners, heat pumps and similar equipment print two numbers on the nameplate. Minimum circuit ampacity (MCA) is the smallest wire ampacity allowed. Maximum overcurrent protection (MOCP, or MOP) is the largest breaker or fuse allowed. Size the wire from MCA and pick a standard breaker no larger than MOCP; do not round MOCP up to the next standard size. For an example, see the mini-split circuit guide.
Where to go next
If you know the breaker and need the wire, use the breaker wire size chart. If you are feeding a second panel, the sub panel wire size chart covers 30A to 200A by run length. The rules behind this page are in NEC Article 240: overcurrent protection.
Frequently asked questions
What are the standard breaker sizes?
NEC Table 240.6(A) lists 38 standard ratings: 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000 and 6000 amps.
What are the standard breaker sizes for a house panel?
The standard ratings up to 200A are 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175 and 200 amps (NEC 240.6(A)). Which of them fit your panel depends on the breakers its label lists.
Is 10A a standard breaker size?
Yes. 10A is the smallest standard rating in the NEC 2023 table; earlier editions started at 15A.
What are the standard breaker sizes over 3000 amps?
4000, 5000 and 6000 amps. 6000A is the largest standard rating in NEC 240.6(A).
Is there a 55 amp breaker?
55, 65 and 75 amps are not standard ratings in NEC 240.6(A). The standard sizes around them are 50A and 60A, 60A and 70A, and 70A and 80A. Nonstandard ratings are permitted, but most panels only list the standard ones.
Can I always go up to the next breaker size?
No. NEC 240.4(B) allows the next standard size above the wire’s ampacity only when the ampacity does not match a standard rating, the next size is 800A or less, and the circuit is not a multi-receptacle branch circuit for cord-and-plug loads. It never applies to 14, 12 or 10 AWG copper, which 240.4(D) holds to 15A, 20A and 30A.
NEC 2023 references verified February 2026