TW Wire

NEC Quick Answer

Conductors with Type TW insulation have a temperature rating of 60C (140F). TW is a moisture-resistant thermoplastic insulation rated for dry and wet locations. Its ampacity values are found in the 60C column of NEC Table 310.16.

NEC 2023: Table 310.16, Section 310.4(A)

TW stands for Thermoplastic moisture-resistant. Basic low-temp wire. Rarely used today - THWN-2 is preferred.
Dry rating60°C
Wet rating60°C
Voltage600V
Locationsdry, wet

Specifications

PropertyValue
Full nameThermoplastic moisture-resistant
Insulation materialPVC
Outer coveringNone
Temperature rating (dry)60°C (140°F)
Temperature rating (wet)60°C (140°F)
Voltage rating600V
Approved locationsdry, wet

TW wire ampacity chart

Amps for TW by size from NEC 2023 Table 310.16. TW is rated 60°C, so only that column applies.

TW ampacity in amperes, NEC 2023 Table 310.16: not more than three current-carrying conductors, 30°C (86°F) ambient. Sizes are AWG; “k” means kcmil.
SizeCopperAluminum
60°60°
1415 -
122015
103025
84035
65540
47055
38565
29575
111085
1/0125100
2/0145115
3/0165130
4/0195150
250k215170
300k240195
350k260210
400k280225
500k320260

* 240.4(D) limits the breaker on small conductors, whatever the column says: 14 AWG copper 15A, 12 AWG copper 20A, 10 AWG copper 30A, 12 AWG aluminum 15A, 10 AWG aluminum 25A.

TW is rated 60°C dry, so it can use the columns of NEC 2023 Table 310.16 up to 60°C. The column you actually size with is set by the terminations, per 110.14(C): terminations on circuits of 100A or less, or marked for 14 AWG through 1 AWG, use the 60°C column unless the equipment is listed and marked for 75°C; terminations on larger circuits and conductors use 75°C.

When to use TW wire

Basic low-temp wire. Rarely used today - THWN-2 is preferred.

Common applications for TW:

NEC code references for TW

The NEC defines wire insulation types in Table 310.4(1) (formerly Table 310.104(A)). Key sections that apply:

Frequently asked questions about TW wire

Where can I use TW wire?

TW is approved for use in dry, wet per NEC Table 310.4(1). It has a dry temperature rating of 60°C and a wet rating of 60°C. Always verify that your specific installation meets the approved location requirements.

What is the temperature rating of TW?

TW is rated 60°C in dry locations and 60°C in wet locations. The ampacity values in NEC Table 310.16 use the 90°C column for conductors rated at or above 90°C, but actual usable ampacity is limited by the termination temperature (typically 75°C per 110.14(C)).

Other wire insulation types

THHN 90°CTHWN 75°CTHWN-2 90°CXHHW 90°CXHHW-2 90°CRHH 90°CRHW-2 90°CUSE-2NM-B 60°CUF-B 60°CMC Cable 90°CAC Cable (BX) 90°CSER/SEU 75°CPV Wire 90°CTHHW 90°CTHW 75°CTHW-2 90°CRHW 75°CMI 90°CUF 60°CXHH 90°CFEP 90°CSIS 90°C
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.