TW Wire
NEC Quick Answer
Conductors with Type TW insulation have a temperature rating of 60C (140F). TW is a moisture-resistant thermoplastic insulation rated for dry and wet locations. Its ampacity values are found in the 60C column of NEC Table 310.16.
NEC 2023: Table 310.16, Section 310.4(A)
Specifications
| Property | Value |
|---|---|
| Full name | Thermoplastic moisture-resistant |
| Insulation material | PVC |
| Outer covering | None |
| Temperature rating (dry) | 60°C (140°F) |
| Temperature rating (wet) | 60°C (140°F) |
| Voltage rating | 600V |
| Approved locations | dry, wet |
TW wire ampacity chart
Amps for TW by size from NEC 2023 Table 310.16. TW is rated 60°C, so only that column applies.
| Size | Copper | Aluminum |
|---|---|---|
| 60° | 60° | |
| 14 | 15 | - |
| 12 | 20 | 15 |
| 10 | 30 | 25 |
| 8 | 40 | 35 |
| 6 | 55 | 40 |
| 4 | 70 | 55 |
| 3 | 85 | 65 |
| 2 | 95 | 75 |
| 1 | 110 | 85 |
| 1/0 | 125 | 100 |
| 2/0 | 145 | 115 |
| 3/0 | 165 | 130 |
| 4/0 | 195 | 150 |
| 250k | 215 | 170 |
| 300k | 240 | 195 |
| 350k | 260 | 210 |
| 400k | 280 | 225 |
| 500k | 320 | 260 |
* 240.4(D) limits the breaker on small conductors, whatever the column says: 14 AWG copper 15A, 12 AWG copper 20A, 10 AWG copper 30A, 12 AWG aluminum 15A, 10 AWG aluminum 25A.
TW is rated 60°C dry, so it can use the columns of NEC 2023 Table 310.16 up to 60°C. The column you actually size with is set by the terminations, per 110.14(C): terminations on circuits of 100A or less, or marked for 14 AWG through 1 AWG, use the 60°C column unless the equipment is listed and marked for 75°C; terminations on larger circuits and conductors use 75°C.
When to use TW wire
Basic low-temp wire. Rarely used today - THWN-2 is preferred.
Common applications for TW:
- Specialized applications - TW is used where its specific temperature and environment ratings are required
- See manufacturer specifications for approved installation methods
NEC code references for TW
The NEC defines wire insulation types in Table 310.4(1) (formerly Table 310.104(A)). Key sections that apply:
- Table 310.4(1) - lists TW with its temperature rating, insulation material, and approved locations
- Table 310.16 - ampacity values for conductors in raceway, cable, or earth (the values shown in our ampacity table above)
- Section 110.14(C) - termination temperature limits that determine real-world usable ampacity
- Section 310.15(C)(1) - adjustment factors for more than 3 current-carrying conductors in a raceway
Frequently asked questions about TW wire
Where can I use TW wire?
TW is approved for use in dry, wet per NEC Table 310.4(1). It has a dry temperature rating of 60°C and a wet rating of 60°C. Always verify that your specific installation meets the approved location requirements.
What is the temperature rating of TW?
TW is rated 60°C in dry locations and 60°C in wet locations. The ampacity values in NEC Table 310.16 use the 90°C column for conductors rated at or above 90°C, but actual usable ampacity is limited by the termination temperature (typically 75°C per 110.14(C)).