ComparisonNEC 2023 · 2026 · Updated

400 kcmil vs 500 kcmil Copper

400 kcmil copper carries 335A and takes a breaker up to 300A. 500 kcmil copper carries 380A and takes up to 350A. Those are 75°C values (NEC 110.14(C)); the larger 90°C figures below are only the starting point for derating.
400 kcmil335A
500 kcmil380A
Breakers300A / 350A

Going from 400 kcmil to 500 kcmil adds 45A of capacity and extends maximum wire run distance before hitting the 3% voltage drop limit. The trade-off is cost: 500 kcmil copper costs more per foot and fits in the same conduit (2-1/2" EMT).

Specification comparison

Side-by-side specifications per NEC 2023 for THHN copper conductors.

THHN copper, NEC 2023 Table 310.16. Conduit is one circuit: three conductors plus the equipment ground.
400 kcmil500 kcmil
90° (derating start)380A430A
Usable (75°)335A380A
Breaker, up to300A350A
EMT2-1/2"2-1/2"

Voltage drop crossover

At what distance does 400 kcmil fail the 3% recommendation and 500 kcmil still passes? This shows the distance where upsizing is required, not optional.

Load: 335A on 240V single-phase.

DistanceVerdict400 kcmil500 kcmil
25 ftEither works0.2%0.2%
50 ftEither works0.5%0.4%
75 ftEither works0.7%0.5%
100 ftEither works0.9%0.7%
125 ftEither works1.1%0.9%
150 ftEither works1.3%1.1%
200 ftEither works1.8%1.4%
250 ftEither works2.2%1.8%
300 ftEither works2.7%2.2%

When to upsize

Stay with 400 kcmil when

Upsize to 500 kcmil when

Detailed ampacity: 400 kcmil copper, 500 kcmil copper. Material comparison: 400 kcmil Cu vs Al, 500 kcmil Cu vs Al.

Frequently asked questions

Can I use 400 kcmil instead of 500 kcmil?

Only if your load is 335A or less and your wire run is short enough to stay within 3% voltage drop. 400 kcmil carries 335A maximum. If you need more than 335A, or your run exceeds the distance limit, you must use 500 kcmil or larger.

How much more does 500 kcmil cost than 400 kcmil?

500 kcmil typically costs 40-60% more per foot than 400 kcmil for the same insulation type. Both fit in 2-1/2" EMT for one circuit. However, the lower voltage drop can save energy on long runs.

What to buy

If you are buying wire for a new installation, consider your total project requirements. For 400 kcmil: buy NM-B cable for in-wall residential or individual THHN conductors for conduit. For 500 kcmil: same insulation types apply but expect approximately 40-60% higher cost per foot. When in doubt about which gauge, upsize: the cost of the wire is a small fraction of the total project cost (labor, conduit, breaker, permits), and upgrading later means repulling the entire run.

Common products for 500 kcmil Copper circuits

As an Amazon Associate we earn from qualifying purchases.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified February 2026 · Report a mistake

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.