ComparisonNEC 2023 · 2026 · Updated

3 AWG vs 2 AWG Copper

3 AWG copper carries 100A and takes a breaker up to 100A. 2 AWG copper carries 115A and takes up to 110A. Those are 75°C values (NEC 110.14(C)); the larger 90°C figures below are only the starting point for derating.
3 AWG100A
2 AWG115A
Breakers100A / 110A

Going from 3 AWG to 2 AWG adds 15A of capacity and extends maximum wire run distance before hitting the 3% voltage drop limit. The trade-off is cost: 2 AWG copper costs more per foot and requires a larger conduit (1-1/4" EMT vs 1" EMT).

Specification comparison

Side-by-side specifications per NEC 2023 for THHN copper conductors.

THHN copper, NEC 2023 Table 310.16. Conduit is one circuit: three conductors plus the equipment ground.
3 AWG2 AWG
90° (derating start)115A130A
Usable (75°)100A115A
Breaker, up to100A110A
EMT1"1-1/4"

Voltage drop crossover

At what distance does 3 AWG fail the 3% recommendation and 2 AWG still passes? This shows the distance where upsizing is required, not optional.

Load: 100A on 240V single-phase.

DistanceVerdict3 AWG2 AWG
25 ftEither works0.5%0.4%
50 ftEither works1.0%0.8%
75 ftEither works1.5%1.2%
100 ftEither works2.0%1.6%
125 ftEither works2.5%2.0%
150 ftUpsize to 2 AWG3.1%2.4%
200 ftBoth exceed 3%4.1%3.2%
250 ftBoth exceed 3%5.1%4.0%
300 ftBoth exceed 3%6.1%4.8%

When to upsize

Stay with 3 AWG when

Upsize to 2 AWG when

Detailed ampacity: 3 AWG copper, 2 AWG copper. Material comparison: 3 AWG Cu vs Al, 2 AWG Cu vs Al.

Frequently asked questions

Can I use 3 AWG instead of 2 AWG?

Only if your load is 100A or less and your wire run is short enough to stay within 3% voltage drop. 3 AWG carries 100A maximum. If you need more than 100A, or your run exceeds the distance limit, you must use 2 AWG or larger.

How much more does 2 AWG cost than 3 AWG?

2 AWG typically costs 40-60% more per foot than 3 AWG for the same insulation type. The larger wire also needs larger conduit (1-1/4" EMT vs 1" EMT). However, the lower voltage drop can save energy on long runs.

What to buy

If you are buying wire for a new installation, consider your total project requirements. For 3 AWG: buy NM-B cable for in-wall residential or individual THHN conductors for conduit. For 2 AWG: same insulation types apply but expect approximately 40-60% higher cost per foot. When in doubt about which gauge, upsize: the cost of the wire is a small fraction of the total project cost (labor, conduit, breaker, permits), and upgrading later means repulling the entire run.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.