UF-B Wire

NEC Quick Answer

UF-B cable ampacity is determined using the 60C column of NEC Table 310.16, same as NM-B. The individual conductors within UF-B have 90C-rated insulation, which can be used as a starting point for derating calculations per NEC 340.80. The cable itself is rated for wet, dry, and direct burial locations.

NEC 2023: Table 310.16, Section 340.80

UF-B stands for Underground Feeder Cable. Direct burial outdoor circuits. Similar to NM-B but moisture-proof. Ampacity limited to 60°C column.
Dry rating60°C
Wet rating60°C
Voltage600V
Locationsdry, damp, wet, direct burial

Specifications

PropertyValue
Full nameUnderground Feeder Cable
Insulation materialPVC integral with jacket (solid)
Outer coveringIntegral moisture-resistant PVC
Temperature rating (dry)60°C (140°F)
Temperature rating (wet)60°C (140°F)
Voltage rating600V
Approved locationsdry, damp, wet, direct burial

Ampacity by gauge

The table below shows NEC Table 310.16 ampacity for UF-B conductors. Values shown reflect the 110.14(C) termination temperature limit, which determines the real-world usable ampacity - not just the insulation rating. Click any gauge to see the full derating chain.

GaugeCopperAluminum
14 AWGSee page -
12 AWGSee page -
10 AWGSee page -
8 AWGSee page -
6 AWGSee page -
4 AWG - -
3 AWG - -
2 AWG - -
1 AWG - -
1/0 AWG - -
2/0 AWG - -
3/0 AWG - -
4/0 AWG - -

When to use UF-B wire

Direct burial outdoor circuits. Similar to NM-B but moisture-proof. Ampacity limited to 60°C column.

Choose UF-B when:

Don't use UF-B when:

Common applications for UF-B:

NEC code references for UF-B

The NEC defines wire insulation types in Table 310.4(1) (formerly Table 310.104(A)). Key sections that apply:

Frequently asked questions about UF-B wire

Can UF-B be buried without conduit?

Yes - UF-B is approved for direct burial per NEC 340.10. Minimum burial depth depends on the circuit voltage and whether GFCI protection is provided: 24 inches for 120V non-GFCI, 18 inches for 120V with GFCI, and 12 inches under a 4-inch concrete pad. See our burial depth guide for the complete table.

What is the difference between UF-B and NM-B?

UF-B has a solid PVC jacket molded around the conductors, making it waterproof and suitable for underground burial. NM-B has a loose paper-wrapped jacket that is not water-resistant. UF-B can be used anywhere NM-B can, plus wet locations and underground. UF-B is harder to strip because the jacket is bonded to the conductors.

Other wire insulation types

THHN 90°CTHWN 75°CTHWN-2 90°CXHHW 90°CXHHW-2 90°CRHH 90°CRHW-2 90°CUSE-2TW 60°CNM-B 60°CMC Cable 90°CAC Cable (BX) 90°CSER/SEU 75°CPV Wire 90°CTHHW 90°CTHW 75°CTHW-2 90°CRHW 75°CMI 90°CUF 60°CXHH 90°CFEP 90°CSIS 90°C
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026