THHW Wire
Specifications
| Property | Value |
|---|---|
| Full name | Thermoplastic High Heat-resistant Water-resistant |
| Insulation material | PVC |
| Outer covering | None (single layer) |
| Temperature rating (dry) | 90°C (194°F) |
| Temperature rating (wet) | 75°C (167°F) |
| Voltage rating | 600VV |
| Approved locations | Dry, Wet |
Advantages and limitations
When to use THHW wire
General purpose in raceway. Dual-rated: 90C dry (90C column), 75C wet (75C column) in Table 310.16.
Common applications for THHW:
- Specialized applications - THHW is used where its specific temperature and environment ratings are required
- See manufacturer specifications for approved installation methods
NEC code references for THHW
The NEC defines wire insulation types in Table 310.4(1) (formerly Table 310.104(A)). Key sections that apply:
- Table 310.4(1) - lists THHW with its temperature rating, insulation material, and approved locations
- Table 310.16 - ampacity values for conductors in raceway, cable, or earth (the values shown in our ampacity table above)
- Section 110.14(C) - termination temperature limits that determine real-world usable ampacity
- Section 310.15(C)(1) - adjustment factors for more than 3 current-carrying conductors in a raceway
Frequently asked questions about THHW wire
Where can I use THHW wire?
THHW is approved for use in dry, wet per NEC Table 310.4(1). It has a dry temperature rating of 90°C and a wet rating of 75°C. Always verify that your specific installation meets the approved location requirements.
What is the temperature rating of THHW?
THHW is rated 90°C in dry locations and 75°C in wet locations. The ampacity values in NEC Table 310.16 use the 90°C column for conductors rated at or above 90°C, but actual usable ampacity is limited by the termination temperature (typically 75°C per 110.14(C)).