XHH Wire
XHH stands for Cross-linked polyethylene High Heat-resistant. Dry locations where 90C rating needed. XHHW/XHHW-2 preferred when wet rating also needed.
Dry rating90°C
Voltage600VV
LocationsDry only
Specifications
| Property | Value |
|---|---|
| Full name | Cross-linked polyethylene High Heat-resistant |
| Insulation material | Cross-linked polyethylene (XLPE) |
| Outer covering | None |
| Temperature rating (dry) | 90°C (194°F) |
| Voltage rating | 600VV |
| Approved locations | Dry only |
Advantages and limitations
Advantages: ['90C dry rating', 'Good chemical resistance']
Limitations: ['Dry locations only', 'XHHW-2 is more versatile']
When to use XHH wire
Dry locations where 90C rating needed. XHHW/XHHW-2 preferred when wet rating also needed.
Common applications for XHH:
- Specialized applications - XHH is used where its specific temperature and environment ratings are required
- See manufacturer specifications for approved installation methods
NEC code references for XHH
The NEC defines wire insulation types in Table 310.4(1) (formerly Table 310.104(A)). Key sections that apply:
- Table 310.4(1) - lists XHH with its temperature rating, insulation material, and approved locations
- Table 310.16 - ampacity values for conductors in raceway, cable, or earth (the values shown in our ampacity table above)
- Section 110.14(C) - termination temperature limits that determine real-world usable ampacity
- Section 310.15(C)(1) - adjustment factors for more than 3 current-carrying conductors in a raceway
Frequently asked questions about XHH wire
Where can I use XHH wire?
XHH is approved for use in dry only per NEC Table 310.4(1). It has a dry temperature rating of 90°C. Always verify that your specific installation meets the approved location requirements.
What is the temperature rating of XHH?
XHH is rated 90°C in dry locations. The ampacity values in NEC Table 310.16 use the 90°C column for conductors rated at or above 90°C, but actual usable ampacity is limited by the termination temperature (typically 75°C per 110.14(C)).
Other wire insulation types
THHN 90°CTHWN 75°CTHWN-2 90°CXHHW 90°CXHHW-2 90°CRHH 90°CRHW-2 90°CUSE-2TW 60°CNM-B 60°CUF-B 60°CMC Cable 90°CAC Cable (BX) 90°CSER/SEU 75°CPV Wire 90°CTHHW 90°CTHW 75°CTHW-2 90°CRHW 75°CMI 90°CUF 60°CFEP 90°CSIS 90°C
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.
NEC 2023 references verified April 2026