NEC Article 210: Branch Circuit Requirements
Practice exam questions Ten exam-style questions from the NEC tables, each answer cited.
What Is a Branch Circuit?
NEC Article 100 defines a branch circuit as the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s). In a house, that is the run from a breaker in the panel to the receptacles, lights or appliance it serves.
The conductors that feed a panel are a feeder, not a branch circuit. An individual branch circuit supplies only one piece of utilization equipment, such as a range or a water heater; a multioutlet branch circuit supplies two or more outlets.
210.18 Branch Circuit Ratings
A branch circuit is rated by its overcurrent device, not by its wire: a 20A breaker on 12 AWG makes a 20A branch circuit, and if larger wire is used the breaker rating still sets the circuit rating. Branch circuits other than individual branch circuits are rated 10, 15, 20, 30, 40 or 50 amperes (210.18).
The 10A rating is new in NEC 2023, and a 10A branch circuit may not supply receptacle outlets. For continuous loads (running 3 hours or more), the breaker must be rated at least 125% of the continuous load, which is why a 16A continuous load needs a 20A circuit.
A multiwire branch circuit, two or more hots sharing a neutral, needs a means that disconnects all of its ungrounded conductors at the same time where it starts (210.4(B)); 240.15(B) covers the common-trip breakers and identified handle ties used for that.
210.11 Required Circuits
Dwellings require specific circuits regardless of actual load: at least two 20A small-appliance branch circuits for kitchen countertop and dining receptacles (210.11(C)(1)), at least one 20A laundry circuit with no other outlets (210.11(C)(2)), one or more 20A circuits for bathroom receptacle outlets with no other outlets (210.11(C)(3)), and at least one 120V 20A circuit for garage receptacle outlets (210.11(C)(4)).
Where one 20A circuit supplies a single bathroom, it may also supply other equipment in that same bathroom. The general lighting load is calculated at 3 VA per square foot of dwelling floor area (220.41 in NEC 2023).
210.12 AFCI Protection
Arc-fault circuit interrupters detect arcing that can start a fire. NEC 2023 210.12(B) requires AFCI protection for all 120V, single-phase, 10A, 15A and 20A branch circuits supplying outlets or devices in dwelling kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas and similar areas.
Garages and bathrooms are not on the NEC 2023 list. NEC 2026 rewrites 210.12(B); check the edition your area enforces before relying on the 2023 list. AFCI protection can come from an AFCI breaker or an outlet-branch-circuit AFCI device, and a dual-function AFCI/GFCI breaker covers rooms that need both.
210.52 Dwelling Receptacle Requirements
Wall receptacles per 210.52(A): every wall space 2 feet or wider needs a receptacle, placed so no point along the floor line is more than 6 feet from an outlet, which works out to a receptacle at least every 12 feet. Countertop receptacles per 210.52(C): no point along the wall line more than 24 inches from an outlet.
Islands and peninsulas: NEC 2023 no longer requires a receptacle there; if none is installed, provisions for adding one later must be provided at the island or peninsula (210.52(C)(2)). Hallways 10 feet or longer need at least one receptacle (210.52(H)).
Outdoors, a one-family dwelling and each unit of a two-family dwelling at grade need at least one receptacle at the front and one at the back, readily accessible from grade and not more than 6-1/2 feet above it (210.52(E)(1)).
210.8 GFCI Requirements
In dwellings, 210.8(A) requires GFCI protection for 125V through 250V receptacles in bathrooms, garages, outdoors, crawl spaces, basements, kitchens, areas within 6 feet of a sink, and several other locations. The 125V-250V scope came in NEC 2020. NEC 2023 removed the old countertop-only limit for kitchens, so every kitchen receptacle now needs GFCI, and added electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers and microwave ovens to the specific appliances in 210.8(D), which already included dishwashers.
GFCI can be provided by a GFCI breaker, a GFCI receptacle, or a GFCI device upstream. See GFCI requirements by room.
Key NEC Tables Referenced
- Table 210.2 - Branch circuit requirements
- Table 210.24 - Summary of branch-circuit requirements
Related WireRef Guides
Frequently Asked Questions
What does NEC Article 210 cover?
Article 210 covers branch circuits requirements. Key sections include What Is a Branch Circuit? and 210.18 Branch Circuit Ratings. It is enforced wherever your state or city has adopted the NEC; see the state code pages for which edition applies to you.
Which NEC edition of Article 210 applies to me?
The edition your state or city has adopted. As of November 2026, 10 states enforce NEC 2026, 21 enforce NEC 2023 and 11 enforce NEC 2020; the rest use an older edition or leave adoption to local jurisdictions. Check your state on our state code pages.
How many circuits does a kitchen need?
At minimum: two 20A small-appliance circuits for countertop receptacles per 210.11(C)(1), plus dedicated circuits for the range, dishwasher, disposal, and refrigerator. Under NEC 2023, all kitchen receptacles require both GFCI and AFCI protection.
Do bedrooms require AFCI?
Yes. NEC 2023 210.12(B) lists bedrooms, so all 120V, single-phase 10A, 15A and 20A branch circuits supplying outlets or devices there need arc-fault protection, from an AFCI breaker or a listed outlet-branch-circuit AFCI device.
What is a branch circuit?
NEC Article 100 defines a branch circuit as the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s): the wire from a breaker in the panel to the receptacles, lights or equipment it serves. The wires that feed a panel are a feeder.
NEC references verified February 2026 · Report a mistake