What wire size for a 80 amp circuit?
All valid wire sizes for a 80 amp circuit
An 80 amp feeder is used for medium subpanels - larger than a basic 60A garage panel but smaller than a full 100A subpanel. The minimum wire is 4 AWG copper or 2 AWG aluminum. At this size, aluminum feeders become a practical and economical choice.
Any gauge with ampacity equal to or greater than 80A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.
| Gauge | Material | Capacity | Max distance (3% drop) | Conduit |
|---|---|---|---|---|
| 4 AWG (minimum) | Copper | 85A | 146 ft | 1" EMT |
| 3 AWG | Copper | 100A | 184 ft | 1" EMT |
| 2 AWG | Copper | 115A | 232 ft | 1" EMT |
| 1 AWG | Copper | 130A | 291 ft | 1-1/4" EMT |
| 1/0 AWG | Copper | 150A | 370 ft | 1-1/4" EMT |
| 2/0 AWG | Copper | 175A | 468 ft | 1-1/2" EMT |
| 3/0 AWG | Copper | 200A | 588 ft | 2" EMT |
| 4/0 AWG | Copper | 230A | 731 ft | 2" EMT |
| 2 AWG (minimum) | Aluminum | 90A | 140 ft | 1" EMT |
| 1 AWG | Aluminum | 100A | 177 ft | 1" EMT |
| 1/0 AWG | Aluminum | 120A | 223 ft | 1-1/4" EMT |
| 2/0 AWG | Aluminum | 135A | 283 ft | 1-1/4" EMT |
| 3/0 AWG | Aluminum | 155A | 357 ft | 1-1/2" EMT |
| 4/0 AWG | Aluminum | 180A | 447 ft | 2" EMT |
Maximum wire run distance
One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.
| Gauge | Material | 120V | 208V | 240V | 480V |
|---|---|---|---|---|---|
| 4 AWG | Copper | 72 ft | 126 ft | 146 ft | 291 ft |
| 3 AWG | Copper | 91 ft | 159 ft | 184 ft | 365 ft |
| 2 AWG | Copper | 115 ft | 201 ft | 232 ft | 461 ft |
| 1 AWG | Copper | 146 ft | 254 ft | 291 ft | 588 ft |
| 1/0 AWG | Copper | 184 ft | 319 ft | 370 ft | 731 ft |
| 2/0 AWG | Copper | 232 ft | 405 ft | 468 ft | 937 ft |
| 3/0 AWG | Copper | 294 ft | 508 ft | 588 ft | 1153 ft |
| 4/0 AWG | Copper | 370 ft | 638 ft | 731 ft | 1500 ft |
| 2 AWG | Aluminum | 70 ft | 122 ft | 140 ft | 283 ft |
| 1 AWG | Aluminum | 89 ft | 153 ft | 177 ft | 357 ft |
| 1/0 AWG | Aluminum | 111 ft | 193 ft | 223 ft | 447 ft |
| 2/0 AWG | Aluminum | 141 ft | 245 ft | 283 ft | 566 ft |
| 3/0 AWG | Aluminum | 178 ft | 309 ft | 357 ft | 714 ft |
| 4/0 AWG | Aluminum | 225 ft | 389 ft | 447 ft | 909 ft |
Common 80A circuit projects
- 80A subpanel (large addition)
- commercial kitchen equipment
Frequently asked questions
What is the minimum wire size for a 80 amp circuit?
The minimum wire size is 4 AWG copper or 2 AWG aluminum per NEC 2023 Table 310.16 with 110.14(C) termination limits applied. For long runs, you may need to upsize to account for voltage drop. See the max distance table above.
Can I use aluminum wire for a 80 amp circuit?
Yes. 2 AWG aluminum handles 80A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 4 AWG copper vs aluminum comparison.
How far can I run 4 AWG wire on a 80 amp circuit?
At 240V, 4 AWG copper can run approximately 146 feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.
What breaker size for a 80 amp circuit?
Use a 80A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).
Do I need GFCI on a 80 amp circuit?
GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.
Common products for 4 AWG Copper circuits
As an Amazon Associate we earn from qualifying purchases.
NEC 2023 references verified April 2026