What wire size for a 70 amp circuit?
All valid wire sizes for a 70 amp circuit
A 70 amp circuit is typically used for subpanels serving workshops or additions. The minimum wire is 4 AWG copper or 3 AWG aluminum.
Any gauge with ampacity equal to or greater than 70A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.
| Gauge | Material | Capacity | Max distance (3% drop) | Conduit |
|---|---|---|---|---|
| 4 AWG (minimum) | Copper | 85A | 166 ft | 1" EMT |
| 3 AWG | Copper | 100A | 209 ft | 1" EMT |
| 2 AWG | Copper | 115A | 265 ft | 1" EMT |
| 1 AWG | Copper | 130A | 333 ft | 1-1/4" EMT |
| 1/0 AWG | Copper | 150A | 422 ft | 1-1/4" EMT |
| 2/0 AWG | Copper | 175A | 535 ft | 1-1/2" EMT |
| 3/0 AWG | Copper | 200A | 666 ft | 2" EMT |
| 4/0 AWG | Copper | 230A | 857 ft | 2" EMT |
| 3 AWG (minimum) | Aluminum | 75A | 127 ft | 1" EMT |
| 2 AWG | Aluminum | 90A | 161 ft | 1" EMT |
| 1 AWG | Aluminum | 100A | 202 ft | 1" EMT |
| 1/0 AWG | Aluminum | 120A | 256 ft | 1-1/4" EMT |
| 2/0 AWG | Aluminum | 135A | 322 ft | 1-1/4" EMT |
| 3/0 AWG | Aluminum | 155A | 410 ft | 1-1/2" EMT |
| 4/0 AWG | Aluminum | 180A | 517 ft | 2" EMT |
Maximum wire run distance
One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.
| Gauge | Material | 120V | 208V | 240V | 480V |
|---|---|---|---|---|---|
| 4 AWG | Copper | 83 ft | 144 ft | 166 ft | 333 ft |
| 3 AWG | Copper | 104 ft | 181 ft | 209 ft | 422 ft |
| 2 AWG | Copper | 132 ft | 229 ft | 265 ft | 526 ft |
| 1 AWG | Copper | 166 ft | 288 ft | 333 ft | 666 ft |
| 1/0 AWG | Copper | 211 ft | 365 ft | 422 ft | 833 ft |
| 2/0 AWG | Copper | 265 ft | 461 ft | 535 ft | 1071 ft |
| 3/0 AWG | Copper | 337 ft | 576 ft | 666 ft | 1363 ft |
| 4/0 AWG | Copper | 422 ft | 731 ft | 857 ft | 1666 ft |
| 3 AWG | Aluminum | 63 ft | 110 ft | 127 ft | 254 ft |
| 2 AWG | Aluminum | 80 ft | 139 ft | 161 ft | 322 ft |
| 1 AWG | Aluminum | 101 ft | 176 ft | 202 ft | 405 ft |
| 1/0 AWG | Aluminum | 127 ft | 222 ft | 256 ft | 508 ft |
| 2/0 AWG | Aluminum | 162 ft | 280 ft | 322 ft | 652 ft |
| 3/0 AWG | Aluminum | 204 ft | 352 ft | 410 ft | 810 ft |
| 4/0 AWG | Aluminum | 256 ft | 447 ft | 517 ft | 1034 ft |
Common 70A circuit projects
- 70A subpanel
- large tankless water heater (29kW)
- heavy workshop feeder
Frequently asked questions
What is the minimum wire size for a 70 amp circuit?
The minimum wire size is 4 AWG copper or 3 AWG aluminum per NEC 2023 Table 310.16 with 110.14(C) termination limits applied. For long runs, you may need to upsize to account for voltage drop. See the max distance table above.
Can I use aluminum wire for a 70 amp circuit?
Yes. 3 AWG aluminum handles 70A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 4 AWG copper vs aluminum comparison.
How far can I run 4 AWG wire on a 70 amp circuit?
At 240V, 4 AWG copper can run approximately 166 feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.
What breaker size for a 70 amp circuit?
Use a 70A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).
Do I need GFCI on a 70 amp circuit?
GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.
Common products for 4 AWG Copper circuits
As an Amazon Associate we earn from qualifying purchases.
NEC 2023 references verified April 2026