What wire size for a 50 amp circuit?
You\'re wiring a full-size electric range in a kitchen remodel, adding an RV hookup in the driveway, or installing a 40A EV charger that needs more power than the standard 32A unit. The 50A circuit is the heaviest single branch circuit most homeowners ever deal with.
All valid wire sizes for a 50 amp circuit
A 50 amp circuit is standard for full-size electric ranges, RV hookups, and 40A EV chargers. At 240V, 8 AWG copper handles up to about 90 feet before exceeding the 3% voltage drop limit. For longer runs, use 6 AWG copper (good to about 145 feet).
Any gauge with ampacity equal to or greater than 50A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.
| Gauge | Material | Capacity | Max distance (3% drop) | Conduit |
|---|---|---|---|---|
| 8 AWG (minimum) | Copper | 50A | 92 ft | 3/4" EMT |
| 6 AWG | Copper | 65A | 146 ft | 3/4" EMT |
| 4 AWG | Copper | 85A | 234 ft | 1" EMT |
| 3 AWG | Copper | 100A | 294 ft | 1" EMT |
| 2 AWG | Copper | 115A | 370 ft | 1" EMT |
| 1 AWG | Copper | 130A | 468 ft | 1-1/4" EMT |
| 1/0 AWG | Copper | 150A | 588 ft | 1-1/4" EMT |
| 2/0 AWG | Copper | 175A | 750 ft | 1-1/2" EMT |
| 3/0 AWG | Copper | 200A | 937 ft | 2" EMT |
| 4/0 AWG | Copper | 230A | 1200 ft | 2" EMT |
| 6 AWG (minimum) | Aluminum | 50A | 89 ft | 3/4" EMT |
| 4 AWG | Aluminum | 65A | 141 ft | 3/4" EMT |
| 3 AWG | Aluminum | 75A | 178 ft | 1" EMT |
| 2 AWG | Aluminum | 90A | 225 ft | 1" EMT |
| 1 AWG | Aluminum | 100A | 285 ft | 1" EMT |
| 1/0 AWG | Aluminum | 120A | 357 ft | 1-1/4" EMT |
| 2/0 AWG | Aluminum | 135A | 454 ft | 1-1/4" EMT |
| 3/0 AWG | Aluminum | 155A | 566 ft | 1-1/2" EMT |
| 4/0 AWG | Aluminum | 180A | 714 ft | 2" EMT |
Maximum wire run distance
One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.
| Gauge | Material | 120V | 208V | 240V | 480V |
|---|---|---|---|---|---|
| 8 AWG | Copper | 46 ft | 80 ft | 92 ft | 185 ft |
| 6 AWG | Copper | 73 ft | 127 ft | 146 ft | 294 ft |
| 4 AWG | Copper | 116 ft | 202 ft | 234 ft | 468 ft |
| 3 AWG | Copper | 147 ft | 254 ft | 294 ft | 588 ft |
| 2 AWG | Copper | 185 ft | 322 ft | 370 ft | 750 ft |
| 1 AWG | Copper | 234 ft | 405 ft | 468 ft | 937 ft |
| 1/0 AWG | Copper | 294 ft | 508 ft | 588 ft | 1200 ft |
| 2/0 AWG | Copper | 370 ft | 652 ft | 750 ft | 1500 ft |
| 3/0 AWG | Copper | 468 ft | 810 ft | 937 ft | 1875 ft |
| 4/0 AWG | Copper | 588 ft | 1034 ft | 1200 ft | 2307 ft |
| 6 AWG | Aluminum | 44 ft | 77 ft | 89 ft | 178 ft |
| 4 AWG | Aluminum | 70 ft | 122 ft | 141 ft | 283 ft |
| 3 AWG | Aluminum | 89 ft | 154 ft | 178 ft | 357 ft |
| 2 AWG | Aluminum | 112 ft | 196 ft | 225 ft | 454 ft |
| 1 AWG | Aluminum | 142 ft | 245 ft | 285 ft | 566 ft |
| 1/0 AWG | Aluminum | 178 ft | 309 ft | 357 ft | 714 ft |
| 2/0 AWG | Aluminum | 225 ft | 394 ft | 454 ft | 909 ft |
| 3/0 AWG | Aluminum | 285 ft | 491 ft | 566 ft | 1153 ft |
| 4/0 AWG | Aluminum | 361 ft | 625 ft | 714 ft | 1428 ft |
Common 50A circuit projects
electric range/oven
A full-size electric range needs a 50A/240V circuit with 6/3 NM-B to a NEMA 14-50R receptacle mounted behind the range. NEC Table 220.55 allows a single household range rated up to 12 kW to be calculated at 8 kW demand, which is why 6 AWG (55A capacity) works even though some ranges have 12+ kW nameplates. Leave 4-5 feet of cable slack behind the range for pulling it out to clean.
RV outlet (14-50R)
An RV hookup uses a NEMA 14-50R receptacle on a 50A/240V circuit. Run 6/3 NM-B indoors or 6 AWG THHN in PVC conduit outdoors. Mount the receptacle 18-24 inches above grade in a weatherproof box with an in-use cover. GFCI protection is required for outdoor receptacles. For the pedestal-style hookup, use a commercial RV power outlet rated for wet locations.
Level 2 EV charger (40A)
A 40A EV charger (like the Tesla Wall Connector at its highest 240V setting) adds about 37 miles of range per hour. This is a continuous load: 40A x 1.25 = 50A circuit. Run 6/3 NM-B or 6 AWG THHN in conduit. GFCI is required per NEC 625.54. If your panel is in the basement and the charger is in the garage, plan for a 40-60 foot run and check voltage drop.
Frequently asked questions
What is the minimum wire size for a 50 amp circuit?
The minimum wire size is 8 AWG copper or 6 AWG aluminum per NEC 2023 Table 310.16 with 110.14(C) termination limits applied. For long runs, you may need to upsize to account for voltage drop. See the max distance table above.
Can I use aluminum wire for a 50 amp circuit?
Yes. 6 AWG aluminum handles 50A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 8 AWG copper vs aluminum comparison.
How far can I run 8 AWG wire on a 50 amp circuit?
At 240V, 8 AWG copper can run approximately 92 feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.
What breaker size for a 50 amp circuit?
Use a 50A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).
Do I need GFCI on a 50 amp circuit?
GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.
Common products for 8 AWG Copper circuits
As an Amazon Associate we earn from qualifying purchases.
NEC 2023 references verified April 2026