Wire Size GuideNEC 2023 · 2026 · Updated Apr 2026

What wire size for a 40 amp circuit?

For a 40A circuit on a 40A breaker: Use 8 AWG copper (50A capacity) or 8 AWG aluminum (40A capacity). Common applications: electric ranges, cooktops, and Level 2 EV chargers (32A continuous).
Copper8 AWG
Aluminum8 AWG
Breaker40A
Voltage240V

You\'re installing a cooktop separate from a wall oven, wiring a 32A EV charger like a Tesla Wall Connector, or running a circuit for a small electric range. The 40A circuit is the point where wire cost starts to matter - 8 AWG copper is noticeably more expensive than 10 AWG.

All valid wire sizes for a 40 amp circuit

A 40 amp circuit serves cooktops, small electric ranges, and 32A Level 2 EV chargers. The minimum wire is 8 AWG copper. EV chargers are continuous loads: a 32A charger requires 40A circuit (32 x 1.25).

EV charger continuous load: 32A x 125% = 40A circuit. The 8 AWG conductor at 50A provides headroom above the breaker rating per 210.19(A)(1).
Common mistake: The biggest 40A mistake is undersizing the wire for an EV charger because the nameplate says 32A. A 32A EV charger is a continuous load - it runs for 3+ hours - so NEC 210.19(A)(1) requires conductors rated at 125% of the load. That means 40A minimum circuit, not 32A. Inspectors catch this constantly on DIY EV installations.

Any gauge with ampacity equal to or greater than 40A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.

GaugeMaterialCapacityMax distance (3% drop)Conduit
8 AWG (minimum)Copper50A115 ft3/4" EMT
6 AWGCopper65A182 ft3/4" EMT
4 AWGCopper85A291 ft1" EMT
3 AWGCopper100A365 ft1" EMT
2 AWGCopper115A461 ft1" EMT
1 AWGCopper130A588 ft1-1/4" EMT
1/0 AWGCopper150A731 ft1-1/4" EMT
2/0 AWGCopper175A937 ft1-1/2" EMT
3/0 AWGCopper200A1153 ft2" EMT
4/0 AWGCopper230A1500 ft2" EMT
8 AWG (minimum)Aluminum40A70 ft3/4" EMT
6 AWGAluminum50A111 ft3/4" EMT
4 AWGAluminum65A177 ft3/4" EMT
3 AWGAluminum75A223 ft1" EMT
2 AWGAluminum90A283 ft1" EMT
1 AWGAluminum100A357 ft1" EMT
1/0 AWGAluminum120A447 ft1-1/4" EMT
2/0 AWGAluminum135A566 ft1-1/4" EMT
3/0 AWGAluminum155A714 ft1-1/2" EMT
4/0 AWGAluminum180A909 ft2" EMT

Maximum wire run distance

One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.

GaugeMaterial120V208V240V480V
8 AWGCopper57 ft100 ft115 ft230 ft
6 AWGCopper91 ft158 ft182 ft365 ft
4 AWGCopper146 ft254 ft291 ft588 ft
3 AWGCopper184 ft319 ft365 ft731 ft
2 AWGCopper232 ft400 ft461 ft937 ft
1 AWGCopper291 ft508 ft588 ft1153 ft
1/0 AWGCopper370 ft638 ft731 ft1500 ft
2/0 AWGCopper468 ft810 ft937 ft1875 ft
3/0 AWGCopper588 ft1034 ft1153 ft2307 ft
4/0 AWGCopper731 ft1304 ft1500 ft3000 ft
8 AWGAluminum35 ft60 ft70 ft140 ft
6 AWGAluminum55 ft96 ft111 ft222 ft
4 AWGAluminum88 ft153 ft177 ft352 ft
3 AWGAluminum111 ft193 ft223 ft447 ft
2 AWGAluminum140 ft243 ft283 ft566 ft
1 AWGAluminum177 ft309 ft357 ft714 ft
1/0 AWGAluminum223 ft389 ft447 ft882 ft
2/0 AWGAluminum283 ft491 ft566 ft1111 ft
3/0 AWGAluminum357 ft625 ft714 ft1428 ft
4/0 AWGAluminum447 ft789 ft909 ft1764 ft

Common 40A circuit projects

electric cooktop

A separate cooktop (no oven below) typically draws 30-36A and needs a 40A circuit. Run 8/3 NM-B for a hardwired connection or to a junction box behind the cooktop. Some cooktops are hardwired; others use a pigtail cord. Check the manufacturer\'s installation instructions for the exact circuit requirement - larger induction cooktops may need 50A.

Level 2 EV charger (32A)

A 32A charger like the standard Tesla Wall Connector adds about 30 miles of range per hour. Run 8/2 NM-B (or 8 AWG THHN in conduit for garage installations) to a NEMA 14-50R or hardwired connection. NEC 625.54 requires GFCI protection. Mount the charger within cord reach of the parking spot and plan the cable route to avoid vehicle traffic.

small range

Smaller electric ranges (compact or apartment-size) often specify a 40A circuit. Use 8/3 NM-B to a NEMA 14-50R receptacle - yes, a 50A receptacle on a 40A breaker is standard practice here because NEC Table 220.55 allows range demand calculations. Check the range nameplate: if it\'s over 8.75 kW, you likely need a 50A circuit instead.

Frequently asked questions

What is the minimum wire size for a 40 amp circuit?

The minimum wire size is 8 AWG copper or 8 AWG aluminum per NEC 2023 Table 310.16 with 110.14(C) termination limits applied. For long runs, you may need to upsize to account for voltage drop. See the max distance table above.

Can I use aluminum wire for a 40 amp circuit?

Yes. 8 AWG aluminum handles 40A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 8 AWG copper vs aluminum comparison.

How far can I run 8 AWG wire on a 40 amp circuit?

At 240V, 8 AWG copper can run approximately 115 feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.

What breaker size for a 40 amp circuit?

Use a 40A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).

Do I need GFCI on a 40 amp circuit?

GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.