What wire size for a 30 amp circuit?
You\'re replacing a dryer outlet, adding a water heater circuit, or an inspector flagged your existing 30A wiring during a remodel. Most 30A questions come from the dryer circuit - it\'s the first 240V circuit most homeowners encounter.
All valid wire sizes for a 30 amp circuit
The 30 amp wire size is 10 AWG copper or 8 AWG aluminum. A 30 amp/240V circuit is the standard for electric dryers and many water heaters. NEC 2023 now requires GFCI for laundry circuits per 210.8(A)(10).
Any gauge with ampacity equal to or greater than 30A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.
| Gauge | Material | Capacity | Max distance (3% drop) | Conduit |
|---|---|---|---|---|
| 10 AWG (minimum) | Copper | 35A | 96 ft | 3/4" EMT |
| 8 AWG | Copper | 50A | 153 ft | 3/4" EMT |
| 6 AWG | Copper | 65A | 243 ft | 3/4" EMT |
| 4 AWG | Copper | 85A | 389 ft | 1" EMT |
| 3 AWG | Copper | 100A | 491 ft | 1" EMT |
| 2 AWG | Copper | 115A | 625 ft | 1" EMT |
| 1 AWG | Copper | 130A | 769 ft | 1-1/4" EMT |
| 1/0 AWG | Copper | 150A | 1000 ft | 1-1/4" EMT |
| 2/0 AWG | Copper | 175A | 1250 ft | 1-1/2" EMT |
| 3/0 AWG | Copper | 200A | 1578 ft | 2" EMT |
| 4/0 AWG | Copper | 230A | 2000 ft | 2" EMT |
| 8 AWG (minimum) | Aluminum | 40A | 93 ft | 3/4" EMT |
| 6 AWG | Aluminum | 50A | 148 ft | 3/4" EMT |
| 4 AWG | Aluminum | 65A | 236 ft | 3/4" EMT |
| 3 AWG | Aluminum | 75A | 297 ft | 1" EMT |
| 2 AWG | Aluminum | 90A | 375 ft | 1" EMT |
| 1 AWG | Aluminum | 100A | 476 ft | 1" EMT |
| 1/0 AWG | Aluminum | 120A | 600 ft | 1-1/4" EMT |
| 2/0 AWG | Aluminum | 135A | 750 ft | 1-1/4" EMT |
| 3/0 AWG | Aluminum | 155A | 937 ft | 1-1/2" EMT |
| 4/0 AWG | Aluminum | 180A | 1200 ft | 2" EMT |
Maximum wire run distance
One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.
| Gauge | Material | 120V | 208V | 240V | 480V |
|---|---|---|---|---|---|
| 10 AWG | Copper | 48 ft | 83 ft | 96 ft | 193 ft |
| 8 AWG | Copper | 77 ft | 133 ft | 153 ft | 309 ft |
| 6 AWG | Copper | 121 ft | 211 ft | 243 ft | 491 ft |
| 4 AWG | Copper | 194 ft | 337 ft | 389 ft | 769 ft |
| 3 AWG | Copper | 243 ft | 422 ft | 491 ft | 967 ft |
| 2 AWG | Copper | 309 ft | 535 ft | 625 ft | 1250 ft |
| 1 AWG | Copper | 389 ft | 681 ft | 769 ft | 1578 ft |
| 1/0 AWG | Copper | 491 ft | 857 ft | 1000 ft | 2000 ft |
| 2/0 AWG | Copper | 625 ft | 1071 ft | 1250 ft | 2500 ft |
| 3/0 AWG | Copper | 789 ft | 1363 ft | 1578 ft | 3000 ft |
| 4/0 AWG | Copper | 1000 ft | 1666 ft | 2000 ft | 3750 ft |
| 8 AWG | Aluminum | 46 ft | 81 ft | 93 ft | 187 ft |
| 6 AWG | Aluminum | 74 ft | 128 ft | 148 ft | 297 ft |
| 4 AWG | Aluminum | 118 ft | 204 ft | 236 ft | 468 ft |
| 3 AWG | Aluminum | 148 ft | 258 ft | 297 ft | 600 ft |
| 2 AWG | Aluminum | 188 ft | 326 ft | 375 ft | 750 ft |
| 1 AWG | Aluminum | 238 ft | 410 ft | 476 ft | 937 ft |
| 1/0 AWG | Aluminum | 300 ft | 517 ft | 600 ft | 1200 ft |
| 2/0 AWG | Aluminum | 375 ft | 652 ft | 750 ft | 1500 ft |
| 3/0 AWG | Aluminum | 476 ft | 833 ft | 937 ft | 1875 ft |
| 4/0 AWG | Aluminum | 600 ft | 1034 ft | 1200 ft | 2500 ft |
Common 30A circuit projects
electric dryer
A 240V dryer circuit uses a 30A double-pole breaker with 10/3 NM-B (two hots, neutral, ground). The receptacle is a NEMA 14-30R. NEC 2023 requires GFCI protection on laundry circuits per 210.8(A)(10). Run the cable from the panel to a box mounted at dryer-outlet height, typically 12 inches above the floor behind the dryer.
tankless water heater
Most tank-style water heaters draw 18-22A on a 30A/240V circuit. Use 10/2 NM-B (no neutral needed - water heaters are 240V-only loads). The disconnect can be the breaker itself if the panel is within sight, otherwise install a disconnect within sight of the unit. Check the nameplate - some larger units need 40A or dual circuits.
window AC unit (large)
A 240V window AC in the 15,000-25,000 BTU range typically needs a dedicated 30A circuit. Use 10/2 NM-B to a NEMA 6-30R or hardwired disconnect. The unit\'s nameplate will specify the minimum circuit ampacity and maximum breaker size. GFCI protection is required if the receptacle is within 6 feet of a sink.
Frequently asked questions
What is the minimum wire size for a 30 amp circuit?
The minimum wire size is 10 AWG copper or 8 AWG aluminum per NEC 2023 Table 310.16 with 110.14(C) termination limits applied. For long runs, you may need to upsize to account for voltage drop. See the max distance table above.
Can I use aluminum wire for a 30 amp circuit?
Yes. 8 AWG aluminum handles 30A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 10 AWG copper vs aluminum comparison.
How far can I run 10 AWG wire on a 30 amp circuit?
At 240V, 10 AWG copper can run approximately 96 feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.
What breaker size for a 30 amp circuit?
Use a 30A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).
Do I need GFCI on a 30 amp circuit?
GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.
Common products for 10 AWG Copper circuits
As an Amazon Associate we earn from qualifying purchases.
NEC 2023 references verified April 2026