Wire Size GuideNEC 2023 · 2026 · Updated Apr 2026

What wire size for a 25 amp circuit?

For a 25A circuit on a 25A breaker: Use 10 AWG copper (35A capacity) or 10 AWG aluminum (30A capacity). Common applications: dedicated appliance circuits where 20A is insufficient and 30A is oversized.
Copper10 AWG
Aluminum10 AWG
Breaker25A
Voltage240V

All valid wire sizes for a 25 amp circuit

A 25 amp circuit is less common than 20A or 30A but is used for specific appliances where 20A is too small and 30A is oversized. The minimum wire is 10 AWG copper. Common applications include ductless mini-split outdoor units and small tankless water heaters.

25A breakers are standard but not as common as 20A or 30A. Use 10 AWG copper per NEC Table 310.16 (35A at 75ยฐC, well above 25A). Some mini-split manufacturers specify a 25A maximum overcurrent device.

Any gauge with ampacity equal to or greater than 25A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.

GaugeMaterialCapacityMax distance (3% drop)Conduit
10 AWG (minimum)Copper35A116 ft3/4" EMT
8 AWGCopper50A185 ft3/4" EMT
6 AWGCopper65A294 ft3/4" EMT
4 AWGCopper85A468 ft1" EMT
3 AWGCopper100A588 ft1" EMT
2 AWGCopper115A750 ft1" EMT
1 AWGCopper130A937 ft1-1/4" EMT
1/0 AWGCopper150A1200 ft1-1/4" EMT
2/0 AWGCopper175A1500 ft1-1/2" EMT
3/0 AWGCopper200A1875 ft2" EMT
4/0 AWGCopper230A2307 ft2" EMT
10 AWG (minimum)Aluminum30A70 ft1/2" EMT
8 AWGAluminum40A112 ft3/4" EMT
6 AWGAluminum50A178 ft3/4" EMT
4 AWGAluminum65A283 ft3/4" EMT
3 AWGAluminum75A357 ft1" EMT
2 AWGAluminum90A454 ft1" EMT
1 AWGAluminum100A566 ft1" EMT
1/0 AWGAluminum120A714 ft1-1/4" EMT
2/0 AWGAluminum135A909 ft1-1/4" EMT
3/0 AWGAluminum155A1153 ft1-1/2" EMT
4/0 AWGAluminum180A1428 ft2" EMT

Maximum wire run distance

One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.

GaugeMaterial120V208V240V480V
10 AWGCopper58 ft100 ft116 ft232 ft
8 AWGCopper92 ft160 ft185 ft370 ft
6 AWGCopper146 ft254 ft294 ft588 ft
4 AWGCopper234 ft405 ft468 ft937 ft
3 AWGCopper294 ft508 ft588 ft1153 ft
2 AWGCopper370 ft638 ft750 ft1500 ft
1 AWGCopper468 ft810 ft937 ft1875 ft
1/0 AWGCopper588 ft1034 ft1200 ft2307 ft
2/0 AWGCopper750 ft1304 ft1500 ft3000 ft
3/0 AWGCopper937 ft1666 ft1875 ft3750 ft
4/0 AWGCopper1200 ft2000 ft2307 ft5000 ft
10 AWGAluminum35 ft61 ft70 ft141 ft
8 AWGAluminum56 ft97 ft112 ft225 ft
6 AWGAluminum89 ft154 ft178 ft357 ft
4 AWGAluminum141 ft245 ft283 ft566 ft
3 AWGAluminum178 ft309 ft357 ft714 ft
2 AWGAluminum225 ft389 ft454 ft909 ft
1 AWGAluminum285 ft491 ft566 ft1153 ft
1/0 AWGAluminum357 ft625 ft714 ft1428 ft
2/0 AWGAluminum454 ft789 ft909 ft1764 ft
3/0 AWGAluminum566 ft1000 ft1153 ft2307 ft
4/0 AWGAluminum714 ft1250 ft1428 ft3000 ft

Common 25A circuit projects

Frequently asked questions

What is the minimum wire size for a 25 amp circuit?

The minimum wire size is 10 AWG copper or 10 AWG aluminum per NEC 2023 Table 310.16 with 110.14(C) termination limits applied. For long runs, you may need to upsize to account for voltage drop. See the max distance table above.

Can I use aluminum wire for a 25 amp circuit?

Yes. 10 AWG aluminum handles 25A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 10 AWG copper vs aluminum comparison.

How far can I run 10 AWG wire on a 25 amp circuit?

At 240V, 10 AWG copper can run approximately 116 feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.

What breaker size for a 25 amp circuit?

Use a 25A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).

Do I need GFCI on a 25 amp circuit?

GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.