What wire size for a 225 amp circuit?
All valid wire sizes for a 225 amp circuit
A 225 amp feeder is the first step above the standard 200A residential service. Used for commercial subpanels, multi-unit feeders, and large residential additions with heavy electrical loads. The minimum wire is 4/0 AWG copper or 250 kcmil aluminum.
Any gauge with ampacity equal to or greater than 225A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.
| Gauge | Material | Capacity | Max distance (3% drop) | Conduit |
|---|---|---|---|---|
| 4/0 AWG (minimum) | Copper | 230A | 263 ft | 2" EMT |
Maximum wire run distance
One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.
| Gauge | Material | 120V | 208V | 240V | 480V |
|---|---|---|---|---|---|
| 4/0 AWG | Copper | 131 ft | 227 ft | 263 ft | 526 ft |
Common 225A circuit projects
- 225A commercial subpanel
- multi-unit building feeder
Frequently asked questions
What is the minimum wire size for a 225 amp circuit?
The minimum wire size is 4/0 AWG copper or N/A AWG aluminum per NEC 2023 Table 310.16 with 110.14(C) termination limits applied. For long runs, you may need to upsize to account for voltage drop. See the max distance table above.
Can I use aluminum wire for a 225 amp circuit?
Not at common residential gauges. Aluminum handles 225A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 4/0 AWG copper vs aluminum comparison.
How far can I run 4/0 AWG wire on a 225 amp circuit?
At 240V, 4/0 AWG copper can run approximately 263 feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.
What breaker size for a 225 amp circuit?
Use a 225A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).
Do I need GFCI on a 225 amp circuit?
GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.
Common products for 4/0 AWG Copper circuits
As an Amazon Associate we earn from qualifying purchases.
NEC 2023 references verified April 2026