Wire Size GuideNEC 2023 · 2026 · Updated Apr 2026

What wire size for a 20 amp circuit?

For a 20A circuit on a 20A breaker: Use 12 AWG copper (25A capacity) or 10 AWG aluminum (30A capacity). Common applications: kitchen countertop outlets, bathrooms, garages, and dedicated appliance circuits.
Copper12 AWG
Aluminum10 AWG
Breaker20A
Voltage120V

You\'re adding a kitchen circuit during a remodel, wiring a bathroom that needs its own 20A per code, or running a dedicated outlet for a window AC unit that keeps tripping the shared circuit. The 20A circuit is where most residential wiring projects start.

All valid wire sizes for a 20 amp circuit

A 20 amp circuit handles higher-draw appliances and is required by code in kitchens, bathrooms, garages, and laundry areas. The minimum wire is 12 AWG copper, limited to 20A per NEC 240.4(D).

NEC 210.11(C) requires dedicated 20A circuits for bathrooms, kitchens (minimum two small-appliance circuits), and laundry. These cannot share loads with other rooms.
Common mistake: The most common 20A mistake is running 14 AWG wire and putting it on a 20A breaker. NEC 240.4(D) prohibits this - 14 AWG is limited to 15A maximum overcurrent protection. The second most common: forgetting that kitchen, bathroom, and laundry 20A circuits cannot serve other rooms per 210.11(C).

Any gauge with ampacity equal to or greater than 20A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.

GaugeMaterialCapacityMax distance (3% drop)Conduit
12 AWG (minimum)Copper25A45 ft1/2" EMT
10 AWGCopper35A72 ft3/4" EMT
8 AWGCopper50A115 ft3/4" EMT
6 AWGCopper65A182 ft3/4" EMT
4 AWGCopper85A291 ft1" EMT
3 AWGCopper100A365 ft1" EMT
2 AWGCopper115A461 ft1" EMT
1 AWGCopper130A588 ft1-1/4" EMT
1/0 AWGCopper150A731 ft1-1/4" EMT
2/0 AWGCopper175A937 ft1-1/2" EMT
3/0 AWGCopper200A1153 ft2" EMT
4/0 AWGCopper230A1500 ft2" EMT
10 AWG (minimum)Aluminum30A44 ft1/2" EMT
8 AWGAluminum40A70 ft3/4" EMT
6 AWGAluminum50A111 ft3/4" EMT
4 AWGAluminum65A177 ft3/4" EMT
3 AWGAluminum75A223 ft1" EMT
2 AWGAluminum90A283 ft1" EMT
1 AWGAluminum100A357 ft1" EMT
1/0 AWGAluminum120A447 ft1-1/4" EMT
2/0 AWGAluminum135A566 ft1-1/4" EMT
3/0 AWGAluminum155A714 ft1-1/2" EMT
4/0 AWGAluminum180A909 ft2" EMT

Maximum wire run distance

One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.

GaugeMaterial120V208V240V480V
12 AWGCopper45 ft78 ft90 ft181 ft
10 AWGCopper72 ft126 ft144 ft291 ft
8 AWGCopper115 ft200 ft230 ft461 ft
6 AWGCopper182 ft319 ft365 ft731 ft
4 AWGCopper291 ft508 ft588 ft1153 ft
3 AWGCopper365 ft638 ft731 ft1500 ft
2 AWGCopper461 ft810 ft937 ft1875 ft
1 AWGCopper588 ft1000 ft1153 ft2307 ft
1/0 AWGCopper731 ft1304 ft1500 ft3000 ft
2/0 AWGCopper937 ft1578 ft1875 ft3750 ft
3/0 AWGCopper1153 ft2000 ft2307 ft5000 ft
4/0 AWGCopper1500 ft2500 ft3000 ft6000 ft
10 AWGAluminum44 ft76 ft88 ft176 ft
8 AWGAluminum70 ft121 ft140 ft280 ft
6 AWGAluminum111 ft193 ft222 ft447 ft
4 AWGAluminum177 ft306 ft352 ft714 ft
3 AWGAluminum223 ft384 ft447 ft882 ft
2 AWGAluminum283 ft491 ft566 ft1111 ft
1 AWGAluminum357 ft612 ft714 ft1428 ft
1/0 AWGAluminum447 ft769 ft882 ft1764 ft
2/0 AWGAluminum566 ft967 ft1111 ft2307 ft
3/0 AWGAluminum714 ft1250 ft1428 ft3000 ft
4/0 AWGAluminum909 ft1578 ft1764 ft3750 ft

Common 20A circuit projects

kitchen small appliance circuit

NEC 210.11(C)(1) requires at least two 20A small-appliance circuits serving kitchen countertop receptacles. These circuits can only serve the kitchen and dining area countertop outlets - no refrigerator, no dishwasher, no other rooms. Run 12/2 NM-B from the panel to the first kitchen outlet, then daisy-chain to additional outlets.

bathroom outlet

Every bathroom needs at least one dedicated 20A circuit per 210.11(C)(3). This circuit can serve one or multiple bathrooms but cannot serve any other room. Use 12/2 NM-B with a GFCI breaker or GFCI at the first receptacle. The receptacle must be within 3 feet of the outside edge of each sink basin.

garage outlets

Garage circuits are typically 20A with 12/2 NM-B. All garage receptacles require GFCI protection, including the ceiling outlet for the garage door opener. For workshops, consider running two 20A circuits to avoid tripping when running a compressor and a saw simultaneously.

outdoor outlets

Outdoor receptacles require GFCI protection per 210.8(A)(3) and weather-resistant (WR) receptacles with in-use covers. Run 12/2 NM-B to the exterior wall, transition to weatherproof box through conduit or LB fitting. Two outdoor receptacles are required - one front, one back - per 210.52(E).

Frequently asked questions

What is the minimum wire size for a 20 amp circuit?

The minimum wire size is 12 AWG copper or 10 AWG aluminum per NEC 2023 Table 310.16 with 110.14(C) termination limits applied. For long runs, you may need to upsize to account for voltage drop. See the max distance table above.

Can I use aluminum wire for a 20 amp circuit?

Yes. 10 AWG aluminum handles 20A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 12 AWG copper vs aluminum comparison.

How far can I run 12 AWG wire on a 20 amp circuit?

At 120V, 12 AWG copper can run approximately 45 feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.

What breaker size for a 20 amp circuit?

Use a 20A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).

Do I need GFCI on a 20 amp circuit?

GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.