What wire size for a 175 amp circuit?
All valid wire sizes for a 175 amp circuit
A 175 amp feeder bridges the gap between 150A and 200A service sizes. The minimum wire is 2/0 AWG copper or 4/0 AWG aluminum. This size is common for large detached buildings and commercial feeders.
Any gauge with ampacity equal to or greater than 175A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.
| Gauge | Material | Capacity | Max distance (3% drop) | Conduit |
|---|---|---|---|---|
| 2/0 AWG (minimum) | Copper | 175A | 212 ft | 1-1/2" EMT |
| 3/0 AWG | Copper | 200A | 267 ft | 2" EMT |
| 4/0 AWG | Copper | 230A | 337 ft | 2" EMT |
| 4/0 AWG (minimum) | Aluminum | 180A | 205 ft | 2" EMT |
| 1/0 AWG (310.15(B)(7)) | Copper | 175A | 168 ft | 1-1/2" EMT |
| 3/0 AWG (310.15(B)(7)) | Aluminum | 175A | 163 ft | 1-1/2" EMT |
Maximum wire run distance
One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.
| Gauge | Material | 120V | 208V | 240V | 480V |
|---|---|---|---|---|---|
| 2/0 AWG | Copper | 106 ft | 184 ft | 212 ft | 422 ft |
| 3/0 AWG | Copper | 134 ft | 232 ft | 267 ft | 535 ft |
| 4/0 AWG | Copper | 169 ft | 294 ft | 337 ft | 681 ft |
| 4/0 AWG | Aluminum | 102 ft | 178 ft | 205 ft | 410 ft |
| 1/0 AWG | Copper | 84 ft | 146 ft | 168 ft | 337 ft |
| 3/0 AWG | Aluminum | 81 ft | 141 ft | 163 ft | 326 ft |
Common 175A circuit projects
- 175A subpanel
- large detached building
- commercial feeder
Frequently asked questions
What is the minimum wire size for a 175 amp circuit?
The minimum wire size is 2/0 AWG copper or 4/0 AWG aluminum per NEC 2023 Table 310.16 with 110.14(C) termination limits applied. For long runs, you may need to upsize to account for voltage drop. See the max distance table above.
Can I use aluminum wire for a 175 amp circuit?
Yes. 4/0 AWG aluminum handles 175A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 2/0 AWG copper vs aluminum comparison.
How far can I run 2/0 AWG wire on a 175 amp circuit?
At 240V, 2/0 AWG copper can run approximately 212 feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.
What breaker size for a 175 amp circuit?
Use a 175A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).
Do I need GFCI on a 175 amp circuit?
GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.
Common products for 2/0 AWG Copper circuits
As an Amazon Associate we earn from qualifying purchases.
NEC 2023 references verified April 2026