Project GuideNEC 2023 · 2026 · Updated Apr 2026

Well Pump: Complete Wiring Guide

Well Pump: Use 14 AWG copper on a 15A breaker at 240V.
Wire (Cu)14 AWG
Wire (Al)14 AWG
Breaker15A
GFCINot required

Bill of materials

Well pumps are motor loads governed by NEC Article 430. Wire sizing uses the motor FLC (full-load current) from NEC Table 430.248, not the nameplate current. The critical factor for well pumps is voltage drop: runs of 200-500 feet from the panel to the wellhead are common, and undersized wire causes motor damage.

Size wire using FLC from NEC Table 430.248, not nameplate amps. For long runs (200+ ft), voltage drop is the controlling factor - you may need to upsize 1-2 gauges above minimum ampacity. Use submersible pump cable rated for wet locations. The control box (for 3-wire systems) must be sized to the motor HP. GFCI is not required for well pump circuits but a disconnect within sight is required per 430.102.

1/2 HP submersible (10A 240V)

ComponentSpecificationNEC basis
Wire (copper)14 AWG THHNTable 310.16, 110.14(C)
Breaker15A double-pole240.4
Voltage240V single-phase
Conduit (EMT)1/2" EMTChapter 9 Table 4
Max distance (3% VD)143 ft at 240V copper210.19(A) Note 4

1 HP submersible (12A 240V)

ComponentSpecificationNEC basis
Wire (copper)12 AWG THHNTable 310.16, 110.14(C)
Breaker20A double-pole240.4
Voltage240V single-phase
Conduit (EMT)1/2" EMTChapter 9 Table 4
Max distance (3% VD)181 ft at 240V copper210.19(A) Note 4

2 HP submersible (20A 240V)

ComponentSpecificationNEC basis
Wire (copper)10 AWG THHNTable 310.16, 110.14(C)
Breaker25A double-pole240.4
Voltage240V single-phase
Conduit (EMT)1/2" EMTChapter 9 Table 4
Max distance (3% VD)181 ft at 240V copper210.19(A) Note 4

Installation notes

GFCI is not specifically required for this application by NEC, though local amendments may differ. Check with your local building department before starting work.

For the wire run, you have two options: NM-B cable (Romex) for interior runs through framing, or individual THHN conductors in conduit for exposed runs, outdoor installations, or runs through unfinished spaces. NM-B is faster to install but cannot be used outdoors or in conduit. For conduit, use EMT (metallic) or PVC Schedule 40.

Run length matters: every foot of wire adds voltage drop, reducing power to your equipment. The table below shows the exact voltage drop at common distances. If your run exceeds the 3% threshold, upsize one gauge.

Voltage drop by distance

Percentage voltage drop at common run lengths. NEC recommends 3% maximum for branch circuits and 5% for combined feeder plus branch.

Distance14 AWG Co12 AWG Co
25 ft0.5%0.3%
50 ft1.1%0.7%
75 ft1.6%1.0%
100 ft2.1%1.3%
150 ft3.1%2.0%
200 ft4.2%2.6%

Detailed ampacity: 14 AWG copper. Wire size lookup: 15A circuit. Calculators: voltage drop ยท panel load calculator.

Frequently asked questions

What wire size do I need for well pump?

Use 14 AWG copper or 14 AWG aluminum on a 15A breaker at 240V. This is based on NEC 2023 Table 310.16 ampacity with 110.14(C) termination limits and 125% continuous load sizing per 210.19(A)(1).

Does well pump require GFCI?

No. GFCI is not required for this application.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.