Outdoor Landscape Lighting: Complete Wiring Guide
Bill of materials
Outdoor lighting comes in two categories: low-voltage (12V, governed by NEC Article 411) and line-voltage (120V, standard branch circuit rules). Low-voltage landscape lighting uses a transformer and 12-16 gauge landscape wire with no burial depth requirement. Line-voltage outdoor fixtures require GFCI, weatherproof boxes, and proper burial depth for underground runs.
Low-voltage (12V) landscape lighting: transformer must be listed for outdoor use, landscape wire (12-16 AWG direct burial) has no NEC burial depth requirement but 6 inches is recommended. Line-voltage (120V): all outdoor outlets require GFCI per 210.8(A)(3), underground wiring must meet 300.5 burial depths, use wet-rated fixtures and in-use covers. Photocells and timers simplify control. LED fixtures dramatically reduce wire sizing needs.
Low-voltage transformer (300W)
| Component | Specification | NEC basis |
|---|---|---|
| Wire (copper) | 12 AWG THHN | Table 310.16, 110.14(C) |
| Breaker | 20A double-pole | 240.4 |
| Voltage | 120V single-phase | |
| Conduit (EMT) | 1/2" EMT | Chapter 9 Table 4 |
| GFCI | Required (GFCI breaker or device) | 210.8(A)(3) |
| Max distance (3% VD) | 361 ft at 120V copper | 210.19(A) Note 4 |
Line-voltage outdoor circuit (20A)
| Component | Specification | NEC basis |
|---|---|---|
| Wire (copper) | 12 AWG THHN | Table 310.16, 110.14(C) |
| Breaker | 20A double-pole | 240.4 |
| Voltage | 120V single-phase | |
| Conduit (EMT) | 1/2" EMT | Chapter 9 Table 4 |
| GFCI | Required (GFCI breaker or device) | 210.8(A)(3) |
| Max distance (3% VD) | 56 ft at 120V copper | 210.19(A) Note 4 |
Installation notes
This project requires GFCI protection per NEC 210.8(A)(3). The simplest approach is a GFCI breaker at the panel, which protects the entire circuit. For 240V circuits, use a 2-pole GFCI breaker sized to match the circuit. GFCI breakers cost $40-80 depending on amperage.
Standard 120V circuits use NM-B cable with 12/2 cable (hot, neutral, ground). For conduit runs, pull individual 12 AWG THHN conductors. All connections must be made in accessible junction boxes.
Run length matters: every foot of wire adds voltage drop, reducing power to your equipment. The table below shows the exact voltage drop at common distances. If your run exceeds the 3% threshold, upsize one gauge.
Voltage drop by distance
Percentage voltage drop at common run lengths. NEC recommends 3% maximum for branch circuits and 5% for combined feeder plus branch.
| Distance | 12 AWG Co | 10 AWG Co |
|---|---|---|
| 25 ft | 0.2% | 0.1% |
| 50 ft | 0.4% | 0.3% |
| 75 ft | 0.6% | 0.4% |
| 100 ft | 0.8% | 0.5% |
| 150 ft | 1.2% | 0.8% |
| 200 ft | 1.6% | 1.0% |
Common products for 12 AWG Copper circuits
As an Amazon Associate we earn from qualifying purchases.
Related wire data
Detailed ampacity: 12 AWG copper. Wire size lookup: 20A circuit. Calculators: voltage drop Β· panel load calculator.
How NEC edition affects this project
Not every state uses the same NEC edition. The table below shows how requirements for this project differ depending on which edition your state has adopted. Find your state's edition here.
| Requirement | NEC 2023 | Earlier editions |
|---|---|---|
| GFCI for lighting | Outdoor lighting outlets now require GFCI per 210.8(A)(3) | GFCI only for outdoor receptacles, not lighting outlets |
| In-use covers | Extra-duty in-use covers required for all 15/20A outdoor outlets | Same as 2023 |
Currently, 17 states enforce NEC 2023, 21 use NEC 2020, 7 use NEC 2017, and 2 are still on NEC 2008. Three states (Arizona, Mississippi, Missouri) defer to local jurisdictions. Find your state to see which specific rules apply to your location.
Frequently asked questions
What wire size do I need for outdoor landscape lighting?
Use 12 AWG copper or 12 AWG aluminum on a 20A breaker at 120V. This is based on NEC 2023 Table 310.16 ampacity with 110.14(C) termination limits and 125% continuous load sizing per 210.19(A)(1).
Does outdoor landscape lighting require GFCI?
Yes. GFCI protection is required per NEC 210.8(A)(3).
NEC 2023 references verified April 2026