Project GuideNEC 2023 · 2026 · Updated Apr 2026

Ductless Mini-Split: Complete Wiring Guide

Ductless Mini-Split: Use 14 AWG copper on a 15A breaker at 240V.
Wire (Cu)14 AWG
Wire (Al)14 AWG
Breaker15A
GFCINot required

Bill of materials

Ductless mini-splits are one of the most common residential electrical additions. Most single-zone units (9-18k BTU) run on a 15A or 20A/240V circuit. Multi-zone units may require 25-30A. Always check the nameplate MCA and MOCP - these override generic sizing charts.

Mini-splits require a dedicated circuit with a disconnect within sight of the outdoor unit per 440.14. Most 9-12k BTU units specify 14 AWG on 15A. The communication wire between indoor and outdoor units is typically 14/4 stranded (4-conductor, 14 AWG) but check the installation manual. Run the communication wire alongside the refrigerant lines but not inside the same conduit as the power wires.

9,000 BTU mini-split (15A)

ComponentSpecificationNEC basis
Wire (copper)14 AWG THHNTable 310.16, 110.14(C)
Breaker15A double-pole240.4
Voltage240V single-phase
Conduit (EMT)1/2" EMTChapter 9 Table 4
Max distance (3% VD)163 ft at 240V copper210.19(A) Note 4

12,000 BTU mini-split (15A)

ComponentSpecificationNEC basis
Wire (copper)14 AWG THHNTable 310.16, 110.14(C)
Breaker15A double-pole240.4
Voltage240V single-phase
Conduit (EMT)1/2" EMTChapter 9 Table 4
Max distance (3% VD)114 ft at 240V copper210.19(A) Note 4

24,000 BTU mini-split (25A)

ComponentSpecificationNEC basis
Wire (copper)10 AWG THHNTable 310.16, 110.14(C)
Wire (aluminum alt.)8 AWG THHNTable 310.16, 110.14(C)
Breaker25A double-pole240.4
Voltage240V single-phase
Conduit (EMT)1/2" EMTChapter 9 Table 4
Max distance (3% VD)181 ft at 240V copper210.19(A) Note 4

36,000 BTU multi-zone (30A)

ComponentSpecificationNEC basis
Wire (copper)10 AWG THHNTable 310.16, 110.14(C)
Wire (aluminum alt.)8 AWG THHNTable 310.16, 110.14(C)
Breaker30A double-pole240.4
Voltage240V single-phase
Conduit (EMT)1/2" EMTChapter 9 Table 4
Max distance (3% VD)132 ft at 240V copper210.19(A) Note 4

Installation notes

GFCI is not specifically required for this application by NEC, though local amendments may differ. Check with your local building department before starting work.

For the wire run, you have two options: NM-B cable (Romex) for interior runs through framing, or individual THHN conductors in conduit for exposed runs, outdoor installations, or runs through unfinished spaces. NM-B is faster to install but cannot be used outdoors or in conduit. For conduit, use EMT (metallic) or PVC Schedule 40.

Run length matters: every foot of wire adds voltage drop, reducing power to your equipment. The table below shows the exact voltage drop at common distances. If your run exceeds the 3% threshold, upsize one gauge.

Voltage drop by distance

Percentage voltage drop at common run lengths. NEC recommends 3% maximum for branch circuits and 5% for combined feeder plus branch.

Distance14 AWG Co12 AWG Co
25 ft0.5%0.3%
50 ft0.9%0.6%
75 ft1.4%0.9%
100 ft1.8%1.2%
150 ft2.8%1.7%
200 ft3.7%2.3%

Detailed ampacity: 14 AWG copper. Wire size lookup: 15A circuit. Calculators: voltage drop ยท panel load calculator.

Frequently asked questions

What wire size do I need for ductless mini-split?

Use 14 AWG copper or 14 AWG aluminum on a 15A breaker at 240V. This is based on NEC 2023 Table 310.16 ampacity with 110.14(C) termination limits and 125% continuous load sizing per 210.19(A)(1).

Does ductless mini-split require GFCI?

No. GFCI is not required for this application.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.