Wire Size GuideNEC 2023 · 2026 · Updated Apr 2026

What wire size for a 500 amp circuit?

For a 500A circuit on a 500A breaker: Use N/A or N/A. Common applications: 500A commercial and industrial services.
Copper - AWG
Aluminum - AWG
Breaker500A
Voltage240V

All valid wire sizes for a 500 amp circuit

A 500 amp service is typical for medium commercial buildings. This amperage always uses parallel conductors. Common configurations include two sets of 300 kcmil aluminum or 250 kcmil copper.

500A is a standard breaker and fuse size. Parallel conductors per 310.10(H) are mandatory at this level. All parallel conductors must be the same length, size, material, insulation, and termination method. Bus duct may be more practical than conduit above 500A.

Any gauge with ampacity equal to or greater than 500A per NEC 2023 Table 310.16, after 110.14(C) termination limits are applied. Smaller gauge number means thicker wire, higher cost, but lower voltage drop.

GaugeMaterialCapacityMax distance (3% drop)Conduit

Maximum wire run distance

One-way distance in feet before voltage drop exceeds 3%, per NEC Chapter 9 Table 8 resistance values. If your run is longer than these distances, upsize one gauge.

GaugeMaterial120V208V240V480V

Common 500A circuit projects

Frequently asked questions

What is the minimum wire size for a 500 amp circuit?

Consult a licensed electrician for circuits at this amperage.

Can I use aluminum wire for a 500 amp circuit?

Not at common residential gauges. Aluminum handles 500A. Aluminum requires anti-oxidant compound and AL-rated terminals (marked AL/CU on the device). It costs roughly 40-60% less than copper but requires a larger gauge for equivalent ampacity. See the 12 AWG copper vs aluminum comparison.

How far can I run the minimum AWG wire on a 500 amp circuit?

At 240V, the minimum AWG copper can run approximately N/A feet before exceeding the 3% voltage drop recommendation. For longer distances, upsize to the next gauge. Use the voltage drop calculator for your exact scenario.

What breaker size for a 500 amp circuit?

Use a 500A breaker. The breaker must match the circuit rating, not the wire ampacity. For continuous loads (like EV chargers), the breaker must be rated at 125% of the load per NEC 210.19(A)(1).

Do I need GFCI on a 500 amp circuit?

GFCI requirements depend on location, not amperage. NEC 2023 requires GFCI in kitchens, bathrooms, garages, outdoors, basements, laundry areas, and near sinks. Check the GFCI requirements by room for your specific installation.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.