ModerateNEC 2023 · 2026 · Updated Apr 2026

6 AWG XHHW-2 Copper Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.
6 AWG XHHW-2 copper is rated 75A at 90°C and 65A at 75°C per NEC 2023 Table 310.16. Most equipment terminations are rated 75°C, making 65A the practical limit. Suitable for 70A circuits.
90°C75A
75°C65A
Breaker70A
Conduit3/4" EMT
V-Drop/100ft2.7%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
75A
Temp Correction 86°F × 1.0
75A
Bundling ≤3 CCC × 1.0
75A
Termination 110.14(C)(1)(a)(2) 75°C
65A −13%
Usable Ampacity
65A
Common inspection failure: Using 75A (90°C) without accounting for the 75°C termination limit. Most panels and breakers are rated 75°C per 110.14(C). The usable ampacity is 65A, not 75A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 6 AWG copper XHHW-2 (90°C column) = 75A base. Assumes ≤3 CCC at 30°C ambient.

Base =75A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 90°C insulation.

After temp =75A × 1.0 = 75A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =75A × 1.0 = 75A
Step 4Termination Limit
110.14(C)(1)(a)(2)

Equipment termination governs the final ampacity. Circuits ≤100A: use 60°C column unless conductor + equipment both rated 75°C. Modern panels and breakers are listed for 75°C terminations, so the 75°C column value of 65A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =65A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 6 AWG copper carrying 65A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 6 AWG copper at 75°C is used from NEC Chapter 9 Table 8. At 65A and 100 ft, the drop is 6.4V (2.7%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =2.7% (6.4V at 240V)

Common Applications

6 AWG XHHW-2 copper at 65A covers subpanel feeders, electric range and oven connections on dedicated circuits, 3-4 ton air conditioning systems, hot tub circuits, and workshop welder feeds. Paired with a 50A or 60A breaker. For subpanel feeders to detached garages or workshops, 6 AWG Copper provides enough capacity for a 60A subpanel while keeping material costs manageable on runs under 100 feet. Hot tub and spa circuits require GFCI protection per NEC 680.44 regardless of voltage. When feeding a detached building, remember that 4 conductors are required (2 hots, neutral, ground) and the grounding electrode must be established at the outbuilding per 250.32. For 100A subpanels or runs exceeding 150 feet, upsize to 4 AWG to manage voltage drop.

Need more capacity? 4 AWG provides 85A. See also: copper vs aluminum.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
75°C
65A65A
90°C
75A75A
NEC 2020
Table 310.15(B)(16)
6 AWG Cu 75°C = 65A
6 AWG Cu 90°C = 75A
NEC 2023
Table 310.16 renumbered
6 AWG Cu 75°C = 65A
6 AWG Cu 90°C = 75A

Ampacity values for 6 AWG copper are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
6 AWG Copper TW60°C55AWet / underground
6 AWG Copper THW75°C65AStandard circuits
6 AWG Copper THHN90°C75ADerating start only
6 AWG Copper free air75/90°C95A / 105ATable 310.17
6 AWG Aluminum THHN75°C50AAluminum equivalent
NEC 2026: Ampacity values for 6 AWG copper are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 6 AWG Copper wire?

6 AWG XHHW-2 Copper has a base ampacity of 75A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 65A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 6 AWG copper wire?

Pair 6 AWG copper with a 70A breaker. The wire's usable ampacity of 65A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (56A on a 70A breaker). See the full ampacity table for all wire sizes.

Can I use 6 AWG wire in conduit?

Yes. 6 AWG XHHW-2 is rated for conduit installations including EMT, PVC, and rigid metal conduit. The 75A base ampacity applies in conduit with no more than 3 current-carrying conductors. If bundling more than 3 conductors, apply the bundling adjustment factors from NEC Table 310.15(C)(1).

How far can I run 6 AWG copper wire?

The maximum distance depends on load and voltage. For 6 AWG copper at 65A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Can I use aluminum instead of copper for 6 AWG?

Yes, but check the ampacity difference. 6 AWG aluminum XHHW-2 is rated at 50A versus 65A for copper. For equivalent capacity, you'll typically need to go up one or two gauge sizes in aluminum. See the 6 AWG copper vs aluminum comparison for cost and installation details.

Derating matrix: all conditions

Ampacity of 6 AWG copper XHHW-2 (75A base at 90°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 65A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)86A69A60A43A
15°C (59°F)84A67A58A42A
20°C (68°F)81A64A56A40A
25°C (77°F)78A62A54A39A
30°C (86°F)75A60A52A37A
35°C (95°F)72A57A50A36A
40°C (104°F)68A54A47A34A
45°C (113°F)65A52A45A32A
50°C (122°F)61A49A43A30A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50°C) with standard bundling, 6 AWG copper drops to 61A - a 18% loss from the 75A base rating. Worst case (50°C, 20 conductors) drops to 30A, a 60% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.