ModerateNEC 2023 · 2026 · Updated Apr 2026

6 AWG NM-B Copper Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.
6 AWG NM-B copper is rated 75A at 90°C and 55A at 60°C per NEC 2023 Table 310.16. Most equipment terminations are rated 60°C, making 55A the practical limit. Suitable for 60A circuits.
90°C75A
60°C55A
Breaker60A
Conduit3/4" EMT
V-Drop/100ft2.2%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
75A
Temp Correction 86°F × 1.0
75A
Bundling ≤3 CCC × 1.0
75A
Termination 334.80 60°C
55A −27%
Usable Ampacity
55A
Common inspection failure: Using 75A (90°C) without accounting for the 60°C termination limit. Most panels and breakers are rated 60°C per 110.14(C). The usable ampacity is 55A, not 75A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 6 AWG copper NM-B (90°C column) = 75A base. Assumes ≤3 CCC at 30°C ambient.

Base =75A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 60°C insulation.

After temp =75A × 1.0 = 75A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =75A × 1.0 = 75A
Step 4Termination Limit
334.80

Equipment termination governs the final ampacity. Circuits ≤100A: use 60°C column unless conductor + equipment both rated 75°C. Modern panels and breakers are listed for 60°C terminations, so the 60°C column value of 55A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =55A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 6 AWG copper carrying 55A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 6 AWG copper at 75°C is used from NEC Chapter 9 Table 8. At 55A and 100 ft, the drop is 5.4V (2.2%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =2.2% (5.4V at 240V)

Common Applications

6 AWG NM-B copper at 55A covers subpanel feeders, electric range and oven connections on dedicated circuits, 3-4 ton air conditioning systems, hot tub circuits, and workshop welder feeds. Paired with a 50A or 60A breaker. For subpanel feeders to detached garages or workshops, 6 AWG Copper provides enough capacity for a 60A subpanel while keeping material costs manageable on runs under 100 feet. Hot tub and spa circuits require GFCI protection per NEC 680.44 regardless of voltage. When feeding a detached building, remember that 4 conductors are required (2 hots, neutral, ground) and the grounding electrode must be established at the outbuilding per 250.32. For 100A subpanels or runs exceeding 150 feet, upsize to 4 AWG to manage voltage drop.

Need more capacity? 4 AWG provides 70A. See also: copper vs aluminum.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
60°C
55A55A
90°C
75A75A
NEC 2020
Table 310.15(B)(16)
6 AWG Cu 60°C = 55A
6 AWG Cu 90°C = 75A
NEC 2023
Table 310.16 renumbered
6 AWG Cu 60°C = 55A
6 AWG Cu 90°C = 75A

Ampacity values for 6 AWG copper are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
6 AWG Copper TW60°C55AWet / underground
6 AWG Copper THW75°C65AStandard circuits
6 AWG Copper THHN90°C75ADerating start only
6 AWG Copper free air75/90°C95A / 105ATable 310.17
6 AWG Aluminum THHN75°C50AAluminum equivalent
NEC 2026: Ampacity values for 6 AWG copper are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 6 AWG Copper wire?

6 AWG NM-B Copper has a base ampacity of 75A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 55A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 6 AWG copper wire?

Pair 6 AWG copper with a 60A breaker. The wire's usable ampacity of 55A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (48A on a 60A breaker). See the full ampacity table for all wire sizes.

Can I use 6 AWG wire in conduit?

NM-B cable can be sleeved through short sections of conduit for physical protection per NEC 334.15(B), but it is not a standard conduit wiring method. For conduit installations, use individual THHN or XHHW-2 conductors instead. See Romex vs conduit and 6 AWG THHN for conduit ampacity.

How far can I run 6 AWG copper wire?

The maximum distance depends on load and voltage. For 6 AWG copper at 55A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Can I use aluminum instead of copper for 6 AWG?

Yes, but check the ampacity difference. 6 AWG aluminum NM-B is rated at 40A versus 55A for copper. For equivalent capacity, you'll typically need to go up one or two gauge sizes in aluminum. See the 6 AWG copper vs aluminum comparison for cost and installation details.

Derating matrix: all conditions

Ampacity of 6 AWG copper NM-B (75A base at 60°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 55A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)96A77A67A48A
15°C (59°F)91A73A64A45A
20°C (68°F)86A69A60A43A
25°C (77°F)81A64A56A40A
30°C (86°F)75A60A52A37A
35°C (95°F)68A54A47A34A
40°C (104°F)61A49A43A30A
45°C (113°F)53A42A37A26A
50°C (122°F)43A34A30A21A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50°C) with standard bundling, 6 AWG copper drops to 43A - a 42% loss from the 75A base rating. Worst case (50°C, 20 conductors) drops to 21A, a 72% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.