Laundry GFCI Requirements
NEC Quick Answer
NEC 2023 requires GFCI protection for all 125V through 250V laundry area receptacles per 210.8(A)(10). At least one dedicated 20A branch circuit is required for laundry receptacles per 210.11(C)(2). Both the washer receptacle and dryer receptacle now require GFCI protection under the 2023 expansion.
NEC 2023: 210.8(A)(10), 210.11(C)(2)
Laundry Requirements (NEC 2023)
Field Notes: Laundry GFCI
Laundry GFCI is a 2020 NEC addition (expanded in 2023) and is the most complained-about GFCI requirement among electricians and homeowners.
The washing machine problem: Many front-load washers have electronic lid locks with DC actuators. When the lock engages, it can create a small current path through the frame to ground that trips GFCI. This is a known issue with several major brands.
What works: Dual-function breakers resolve most washing machine GFCI trips. The combination of GFCI sensing with AFCI filtering handles the DC component better than a standalone GFCI receptacle. If a DF breaker still trips, the washer may have a genuine ground fault (degraded insulation on the heating element or pump motor) that warrants service.
Dryer note: Electric dryers on 240V/30A circuits did not require GFCI under 2020 code (laundry GFCI was limited to 120V). Under 2023, the voltage expansion to 250V means the dryer circuit may now require GFCI depending on your jurisdiction's adopted code year.
How Laundry GFCI Changed
What electricians see in the field
Laundry GFCI was added in NEC 2020 at 210.8(A)(11). In 2020, it covered 125V through 250V receptacles (single-phase, 150V to ground, 50A or less). The scope hasn't changed in 2023, but the 210.8(D) appliance list expansion means the washer itself now explicitly requires GFCI regardless of the laundry area requirement.
For existing homes, laundry GFCI applies when new circuits are installed or existing circuits are modified under a permit. Simply replacing a washer does not trigger the GFCI requirement in most jurisdictions. But replacing the panel or the laundry circuit breaker might, depending on the AHJ.
The required laundry circuit per 210.11(C)(2) is at least one 20A branch circuit for the laundry area. This circuit must not serve other areas.
Laundry wiring details
Laundry GFCI evolved in two stages: NEC 2005 added GFCI for receptacles within 6 feet of laundry sinks. NEC 2020 expanded this to ALL laundry area receptacles regardless of sink proximity, including the 240V dryer receptacle. The washing machine and dryer both require GFCI under current code.
How to add GFCI and AFCI protection
Because laundry circuits require both GFCI and AFCI, the simplest approach is a dual-function AFCI/GFCI breaker at the panel. This single device satisfies both code requirements and protects every outlet on the circuit. Dual-function breakers cost $35-50 and eliminate the need for individual GFCI receptacles. For existing circuits, swapping the standard breaker for a dual-function breaker is typically a 10-minute job.
GFCI devices should be tested monthly using the built-in test/reset buttons. Replace any GFCI device that fails to trip when tested or that is more than 15 years old. Modern GFCI breakers are self-testing and will indicate end-of-life when they can no longer protect.
Frequently asked questions
Do I need GFCI outlets in my laundry?
Yes. NEC 2023 Section 210.8(A)(10) requires GFCI and AFCI protection for laundry receptacles. This applies to all new construction and renovations where circuits are modified. Existing receptacles in older homes are not required to be upgraded unless the circuit is altered, but adding GFCI protection is strongly recommended for safety.
What NEC code section covers laundry GFCI requirements?
NEC 2023 Section 210.8(A)(10) covers GFCI requirements for laundry receptacles. The 2023 edition expanded coverage to include 250V receptacles in addition to 125V. See the code timeline above for how requirements have changed across NEC editions.
Does a washing machine outlet need GFCI?
Yes under NEC 2023. Section 210.8(A)(10) requires GFCI protection for laundry area receptacles. The dedicated 20A laundry circuit required by 210.11(C)(2) must have GFCI protection. Electric dryer circuits (typically 10 AWG 30A 240V) also now require GFCI.
Does an electric dryer need GFCI?
Yes under NEC 2023. Electric dryer circuits (typically 30A/240V using 10 AWG copper) now require GFCI protection per 210.8(A)(10). Use a 2-pole 30A GFCI breaker. See the dryer wiring guide for the complete bill of materials.
What happens if I don't have GFCI in my laundry?
Without GFCI protection, there is a risk of electrical shock, especially in areas near water. From a code compliance standpoint, new installations and renovations will fail electrical inspection without required GFCI protection. Insurance claims may also be affected if an incident occurs in an area where GFCI was required but not installed. Retrofitting GFCI is straightforward. A GFCI breaker in the panel protects the entire circuit without replacing individual receptacles.
GFCI products for laundry circuits
As an Amazon Associate we earn from qualifying purchases.
NEC 2023 references verified April 2026
As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.