ComparisonNEC 2023 · 2026 · Updated Apr 2026

600 AWG vs 700 AWG Copper

600 AWG carries 420A. 700 AWG carries 460A. The larger wire adds 40A capacity and significantly extends maximum run distance.
600 AWG420A
700 AWG460A
Gain+40A

Going from 600 AWG to 700 AWG adds 40A of capacity and extends maximum wire run distance before hitting the 3% voltage drop limit. The trade-off is cost: 700 AWG copper costs more per foot and fits in the same conduit (2" EMT).

Specification comparison

Side-by-side specifications per NEC 2023 for THHN copper conductors.

Property600 AWG700 AWG
90°C ampacity475A520A
Usable ampacity420A460A
Standard breaker200A200A
Conduit (EMT)2" EMT2" EMT

Voltage drop crossover

At what distance does 600 AWG fail the 3% recommendation and 700 AWG still passes? This shows the distance where upsizing is required, not optional.

Load: 420A on 240V single-phase.

Distance600 AWG700 AWGVerdict
25 ft0.2%0.0%Either works
50 ft0.4%0.0%Either works
75 ft0.6%0.0%Either works
100 ft0.8%0.0%Either works
125 ft0.9%0.0%Either works
150 ft1.1%0.0%Either works
200 ft1.5%0.0%Either works
250 ft1.9%0.0%Either works
300 ft2.2%0.0%Either works

When to upsize

Stay with 600 AWG when

Upsize to 700 AWG when

Detailed ampacity: 600 kcmil copper, 700 kcmil copper. Material comparison: 600 kcmil Cu vs Al, 700 kcmil Cu vs Al.

Frequently asked questions

Can I use 600 kcmil instead of 700 kcmil?

Only if your load is 420A or less and your wire run is short enough to stay within 3% voltage drop. 600 kcmil carries 420A maximum. If you need more than 420A, or your run exceeds the distance limit, you must use 700 kcmil or larger.

How much more does 700 kcmil cost than 600 kcmil?

700 kcmil typically costs 40-60% more per foot than 600 kcmil for the same insulation type. The larger wire also requires larger conduit (2" EMT vs 2" EMT). However, the lower voltage drop can save energy on long runs.

What to buy

If you are buying wire for a new installation, consider your total project requirements. For 600 kcmil: buy NM-B cable for in-wall residential or individual THHN conductors for conduit. For 700 kcmil: same insulation types apply but expect approximately 40-60% higher cost per foot. When in doubt about which gauge, upsize: the cost of the wire is a small fraction of the total project cost (labor, conduit, breaker, permits), and upgrading later means repulling the entire run.

Common products for 700 AWG Copper circuits

As an Amazon Associate we earn from qualifying purchases.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.