ComparisonNEC 2023 · 2026 · Updated Apr 2026

500 AWG vs 600 AWG Copper

500 AWG carries 380A. 600 AWG carries 420A. The larger wire adds 40A capacity and significantly extends maximum run distance.
500 AWG380A
600 AWG420A
Gain+40A

Going from 500 AWG to 600 AWG adds 40A of capacity and extends maximum wire run distance before hitting the 3% voltage drop limit. The trade-off is cost: 600 AWG copper costs more per foot and fits in the same conduit (2" EMT).

Specification comparison

Side-by-side specifications per NEC 2023 for THHN copper conductors.

Property500 AWG600 AWG
90°C ampacity430A475A
Usable ampacity380A420A
Standard breaker200A200A
Conduit (EMT)2" EMT2" EMT

Voltage drop crossover

At what distance does 500 AWG fail the 3% recommendation and 600 AWG still passes? This shows the distance where upsizing is required, not optional.

Load: 380A on 240V single-phase.

Distance500 AWG600 AWGVerdict
25 ft0.2%0.2%Either works
50 ft0.4%0.3%Either works
75 ft0.6%0.5%Either works
100 ft0.8%0.7%Either works
125 ft1.0%0.8%Either works
150 ft1.2%1.0%Either works
200 ft1.6%1.4%Either works
250 ft2.0%1.7%Either works
300 ft2.5%2.0%Either works

When to upsize

Stay with 500 AWG when

Upsize to 600 AWG when

Detailed ampacity: 500 kcmil copper, 600 kcmil copper. Material comparison: 500 kcmil Cu vs Al, 600 kcmil Cu vs Al.

Frequently asked questions

Can I use 500 kcmil instead of 600 kcmil?

Only if your load is 380A or less and your wire run is short enough to stay within 3% voltage drop. 500 kcmil carries 380A maximum. If you need more than 380A, or your run exceeds the distance limit, you must use 600 kcmil or larger.

How much more does 600 kcmil cost than 500 kcmil?

600 kcmil typically costs 40-60% more per foot than 500 kcmil for the same insulation type. The larger wire also requires larger conduit (2" EMT vs 2" EMT). However, the lower voltage drop can save energy on long runs.

What to buy

If you are buying wire for a new installation, consider your total project requirements. For 500 kcmil: buy NM-B cable for in-wall residential or individual THHN conductors for conduit. For 600 kcmil: same insulation types apply but expect approximately 40-60% higher cost per foot. When in doubt about which gauge, upsize: the cost of the wire is a small fraction of the total project cost (labor, conduit, breaker, permits), and upgrading later means repulling the entire run.

Common products for 600 AWG Copper circuits

As an Amazon Associate we earn from qualifying purchases.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.