ComparisonNEC 2023 · 2026 · Updated Apr 2026

300 AWG vs 350 AWG Copper

300 AWG carries 285A. 350 AWG carries 310A. The larger wire adds 25A capacity and significantly extends maximum run distance.
300 AWG285A
350 AWG310A
Gain+25A

Going from 300 AWG to 350 AWG adds 25A of capacity and extends maximum wire run distance before hitting the 3% voltage drop limit. The trade-off is cost: 350 AWG copper costs more per foot and fits in the same conduit (2" EMT).

Specification comparison

Side-by-side specifications per NEC 2023 for THHN copper conductors.

Property300 AWG350 AWG
90°C ampacity320A350A
Usable ampacity285A310A
Standard breaker200A200A
Conduit (EMT)2" EMT2" EMT

Voltage drop crossover

At what distance does 300 AWG fail the 3% recommendation and 350 AWG still passes? This shows the distance where upsizing is required, not optional.

Load: 285A on 240V single-phase.

Distance300 AWG350 AWGVerdict
25 ft0.2%0.2%Either works
50 ft0.5%0.4%Either works
75 ft0.8%0.7%Either works
100 ft1.0%0.9%Either works
125 ft1.3%1.1%Either works
150 ft1.5%1.3%Either works
200 ft2.0%1.7%Either works
250 ft2.5%2.2%Either works
300 ft3.1%2.6%Upsize to 350

When to upsize

Stay with 300 AWG when

Upsize to 350 AWG when

Detailed ampacity: 300 kcmil copper, 350 kcmil copper. Material comparison: 300 kcmil Cu vs Al, 350 kcmil Cu vs Al.

Frequently asked questions

Can I use 300 kcmil instead of 350 kcmil?

Only if your load is 285A or less and your wire run is short enough to stay within 3% voltage drop. 300 kcmil carries 285A maximum. If you need more than 285A, or your run exceeds the distance limit, you must use 350 kcmil or larger.

How much more does 350 kcmil cost than 300 kcmil?

350 kcmil typically costs 40-60% more per foot than 300 kcmil for the same insulation type. The larger wire also requires larger conduit (2" EMT vs 2" EMT). However, the lower voltage drop can save energy on long runs.

What to buy

If you are buying wire for a new installation, consider your total project requirements. For 300 kcmil: buy NM-B cable for in-wall residential or individual THHN conductors for conduit. For 350 kcmil: same insulation types apply but expect approximately 40-60% higher cost per foot. When in doubt about which gauge, upsize: the cost of the wire is a small fraction of the total project cost (labor, conduit, breaker, permits), and upgrading later means repulling the entire run.

Common products for 350 AWG Copper circuits

As an Amazon Associate we earn from qualifying purchases.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.