ComparisonNEC 2023 · 2026 · Updated Apr 2026

300 kcmil Copper vs Aluminum

300 AWG copper delivers 285A usable. 300 AWG aluminum delivers 230A usable. Aluminum carries 55A less in the same gauge.
Copper285A
Aluminum230A
Difference55A

At 300 kcmil, aluminum wire carries 19% less current than copper but costs roughly 40-60% less per foot and weighs one-third as much. With copper prices rising, 300 kcmil aluminum wire is increasingly common for feeders and service entrances where the cost savings are substantial.

Ampacity comparison

All values per NEC 2023 Table 310.16 for THHN insulation with 110.14(C) termination limits applied.

PropertyCopperAluminum
90°C ampacity320A260A
Usable (after 110.14(C))285A230A
Breaker200A200A
Conduit (EMT)2" EMT2" EMT

Voltage drop comparison

Voltage drop at 230A load (limited by aluminum capacity) on 240V single-phase.

DistanceCopperAluminum
50 ft0.4%0.7%
75 ft0.6%1.0%
100 ft0.8%1.4%
150 ft1.2%2.0%
200 ft1.6%2.7%

When to use each

Use 300 AWG copper when

Use 300 AWG aluminum when

What to buy

At 300 AWG, aluminum is the industry default for feeders and service entrance conductors. Material savings are substantial: roughly half the per-foot cost of copper. Buy AA-8000 series aluminum. For service entrance, SER cable bundles conductors with a bare ground. For conduit, buy individual THHN or XHHW-2. Anti-oxidant compound and a calibrated torque wrench are mandatory accessories at this size.

Detailed ampacity: 300 kcmil copper, 300 kcmil aluminum. Wire size lookup: 200A circuit.

Frequently asked questions

Is 300 AWG aluminum safe to use?

Yes, when installed correctly. 300 AWG aluminum carries 230A and is common in feeder circuits. Use AL-rated terminals, apply anti-oxidant compound, and torque connections to manufacturer specs. Modern AA-8000 series aluminum is engineered for building wire.

How much less does 300 AWG aluminum carry than copper?

300 AWG aluminum carries 230A vs 285A for copper, a 55A difference (19% reduction). To match copper ampacity, you typically need to go up 2 gauge sizes in aluminum.

What size aluminum equals 300 AWG copper?

To match 300 AWG copper (285A), check the 200A wire size guide for the exact aluminum equivalent needed.

Can I mix copper and aluminum in the same circuit?

Not directly. Copper and aluminum must not touch at connections due to galvanic corrosion. Use approved bimetallic connectors (like Alumiconn) or AL/CU-rated panel lugs.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.