ComparisonNEC 2023 · 2026 · Updated Apr 2026

12 AWG Copper vs Aluminum

12 AWG copper delivers 25A usable. 12 AWG aluminum delivers 20A usable. Aluminum carries 5A less in the same gauge.
Copper25A
Aluminum20A
Difference5A

At 12 AWG, aluminum wire carries 20% less current than copper but costs roughly 40-60% less per foot and weighs one-third as much. With copper prices rising, 12 AWG aluminum wire is increasingly common for feeders and service entrances where the cost savings are substantial.

Ampacity comparison

All values per NEC 2023 Table 310.16 for THHN insulation with 110.14(C) termination limits applied.

PropertyCopperAluminum
90°C ampacity30A25A
Usable (after 110.14(C))25A20A
Breaker20A15A
Conduit (EMT)1/2" EMT1/2" EMT

Voltage drop comparison

Voltage drop at 20A load (limited by aluminum capacity) on 240V single-phase.

DistanceCopperAluminum
50 ft1.6%2.7%
75 ft2.5%4.1%
100 ft3.3%5.4%
150 ft5.0%8.1%
200 ft6.6%10.8%

When to use each

Use 12 AWG copper when

Use 12 AWG aluminum when

What to buy

For 12 AWG branch circuits, buy NM-B (Romex) cable for in-wall runs or THHN conductors for conduit. Copper is standard at this gauge since the cost premium over aluminum is small and most devices are copper-rated only. Buy 10-15% more wire than your measured run length to account for routing and termination tails.

Detailed ampacity: 12 AWG copper, 12 AWG aluminum. Wire size lookup: 20A circuit.

Frequently asked questions

Is 12 AWG aluminum safe to use?

Yes, when installed correctly. 12 AWG aluminum carries 20A and is common in feeder circuits. Use AL-rated terminals, apply anti-oxidant compound, and torque connections to manufacturer specs. Modern AA-8000 series aluminum is engineered for building wire.

How much less does 12 AWG aluminum carry than copper?

12 AWG aluminum carries 20A vs 25A for copper, a 5A difference (20% reduction). To match copper ampacity, you typically need to go up 2 gauge sizes in aluminum.

What size aluminum equals 12 AWG copper?

To match 12 AWG copper (25A), check the 20A wire size guide for the exact aluminum equivalent needed.

Can I mix copper and aluminum in the same circuit?

Not directly. Copper and aluminum must not touch at connections due to galvanic corrosion. Use approved bimetallic connectors (like Alumiconn) or AL/CU-rated panel lugs.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.