ComparisonNEC 2023 · 2026 · Updated Apr 2026

10 AWG Copper vs Aluminum

10 AWG copper delivers 35A usable. 10 AWG aluminum delivers 30A usable. Aluminum carries 5A less in the same gauge.
Copper35A
Aluminum30A
Difference5A

At 10 AWG, aluminum wire carries 14% less current than copper but costs roughly 40-60% less per foot and weighs one-third as much. With copper prices rising, 10 AWG aluminum wire is increasingly common for feeders and service entrances where the cost savings are substantial.

Ampacity comparison

All values per NEC 2023 Table 310.16 for THHN insulation with 110.14(C) termination limits applied.

PropertyCopperAluminum
90°C ampacity40A35A
Usable (after 110.14(C))35A30A
Breaker30A25A
Conduit (EMT)3/4" EMT1/2" EMT

Voltage drop comparison

Voltage drop at 30A load (limited by aluminum capacity) on 240V single-phase.

DistanceCopperAluminum
50 ft1.6%2.5%
75 ft2.3%3.8%
100 ft3.1%5.1%
150 ft4.7%7.7%
200 ft6.2%10.2%

When to use each

Use 10 AWG copper when

Use 10 AWG aluminum when

What to buy

At 10 AWG, the copper vs aluminum cost gap becomes significant. For branch circuits under 50 feet, copper THHN in conduit is standard. For feeders to subpanels or outbuildings, aluminum THHN saves 40-60% on material. Always buy anti-oxidant compound (like Noalox) when using aluminum, and verify every device is AL-rated before purchasing.

Detailed ampacity: 10 AWG copper, 10 AWG aluminum. Wire size lookup: 30A circuit.

Frequently asked questions

Is 10 AWG aluminum safe to use?

Yes, when installed correctly. 10 AWG aluminum carries 30A and is common in feeder circuits. Use AL-rated terminals, apply anti-oxidant compound, and torque connections to manufacturer specs. Modern AA-8000 series aluminum is engineered for building wire.

How much less does 10 AWG aluminum carry than copper?

10 AWG aluminum carries 30A vs 35A for copper, a 5A difference (14% reduction). To match copper ampacity, you typically need to go up 2 gauge sizes in aluminum.

What size aluminum equals 10 AWG copper?

To match 10 AWG copper (35A), check the 30A wire size guide for the exact aluminum equivalent needed.

Can I mix copper and aluminum in the same circuit?

Not directly. Copper and aluminum must not touch at connections due to galvanic corrosion. Use approved bimetallic connectors (like Alumiconn) or AL/CU-rated panel lugs.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.