Breaker GuideNEC 2023 · 2026 · Updated Apr 2026

30 Amp Breaker: Wire Size and Uses

A 30A breaker requires minimum 10 AWG copper or 8 AWG aluminum at 240V. Maximum continuous load: 24A (80% rule). Standard size per NEC 240.6(A).
Copper10 AWG
Aluminum8 AWG
Voltage240V
Max continuous24A

Common uses for a 30A breaker

Electric dryers, water heaters, small AC units. 10 AWG limited to 30A per NEC 240.4(D). Most common 240V residential circuit.

The 30A/240V breaker is the standard for electric dryers and water heaters. It uses a double-pole breaker that occupies two slots in the panel. The NEMA 14-30R receptacle (4-prong dryer outlet) is the standard for this circuit. New dryer circuits must be 4-wire (two hots, neutral, ground) per NEC 250.140.

Wire size for a 30A breaker

The wire must have an ampacity that meets or exceeds the breaker rating at the appropriate temperature column. Here are the minimum wire sizes:

MaterialMinimum wireDetails
Copper10 AWGStandard for residential branch circuits
Aluminum8 AWGCommon for feeders and above and larger

These sizes assume 75ยฐC termination temperature per NEC 110.14(C), which is the standard for most residential breakers and devices. For long wire runs, check voltage drop - you may need to upsize the wire even though the ampacity is adequate.

Continuous load rule (80% maximum)

For continuous loads - any load expected to run for 3 hours or more - the NEC requires that the load not exceed 80% of the breaker rating (NEC 210.20(A)). On a 30A breaker, the maximum continuous load is 24A.

This is why sizing often seems counterintuitive:

Installation notes

Breaker type: A 30A breaker is a double-pole (240V) breaker. Double-pole breakers occupy two adjacent slots in the panel and provide 240V between the two hot conductors. Both poles must trip simultaneously - never use two single-pole breakers tied together with a handle tie for 240V circuits (except as explicitly allowed for specific multi-wire branch circuits).

Ground wire: A 30A circuit requires a minimum 10 AWG copper equipment grounding conductor per NEC Table 250.122.

Standard sizes: 30A is a standard breaker size per NEC 240.6(A). Standard residential breaker sizes are: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200. Non-standard sizes should never be used.

Why does my 30A breaker keep tripping?

A 30A breaker tripping on a dryer circuit usually means one of two things: the heating element has a partial short to ground (causing a ground fault that trips GFCI-protected circuits), or the vent is clogged and the thermal fuse keeps cycling the element on and off rapidly. Start with the vent - a clogged dryer vent causes the element to overheat and draw more current. For water heaters, a tripping 30A breaker often indicates a failing heating element where the nichrome wire has cracked and is arcing to the tank wall.

Frequently asked questions

What wire size for a 30 amp breaker?

10 AWG copper or 8 AWG aluminum minimum. The wire must have an ampacity at the 75ยฐC column that meets or exceeds 30A. For long runs, you may need to upsize for voltage drop.

What can a 30 amp breaker handle?

Electric dryers, water heaters, small AC units. For continuous loads (3+ hours), the maximum is 24A (80% of 30A). For non-continuous loads, the full 30A is available.

Can I put a 30A breaker on 10 AWG wire?

The breaker must not exceed the wire ampacity. 10 AWG copper supports a 30A breaker. Never put a larger breaker on wire that cannot handle it - this defeats the safety purpose of the breaker.

Is 30A a standard breaker size?

Yes. 30A is a standard breaker size per NEC 240.6(A). It is widely available from all major breaker manufacturers (Square D, Eaton, Siemens, GE). Always use the correct breaker brand for your panel - breakers are not interchangeable between panel brands.

What to buy

As an Amazon Associate we earn from qualifying purchases.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026