Free AirNEC 2023 · 2026 Table 310.17 · Updated Apr 2026

500 kcmil Free-Air Ampacity

500 kcmil in free air (single conductor, not in raceway): copper 700A at 90°C, 620A at 75°C. Free-air values are higher than in-raceway (Table 310.16) because heat dissipates more freely.
Cu 90°C700A
Cu 75°C620A

Free air vs in-raceway

75°C90°C
Free air (310.17)620A700A
In raceway (310.16) -A430A
Al free air485A545A

When to use free-air ratings

Table 310.17 applies when conductors are run in free air - not enclosed in conduit or cable tray with covers. Common scenarios for kcmil conductors include overhead service drops, open cable tray, and messenger-supported wiring.

For conductors in conduit or cable, use the in-raceway values from Table 310.16.

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026