Free-Air Ampacity (Table 310.17)

Ampacity for single conductors in free air - not in conduit or cable. Values are higher than Table 310.16 (in-raceway) because heat dissipates more freely.

Copper

Wire60°C75°C90°C
14 AWG25A30A35A
12 AWG30A35A40A
10 AWG40A50A55A
8 AWG60A70A80A
6 AWG80A95A105A
4 AWG105A125A140A
3 AWG120A145A165A
2 AWG140A170A190A
1 AWG165A195A220A
1/0 AWG195A230A260A
2/0 AWG225A265A300A
3/0 AWG260A310A350A
4/0 AWG300A360A405A
250 kcmil340A405A455A
300 kcmil375A445A500A
350 kcmil420A505A570A
400 kcmil455A545A615A
500 kcmil515A620A700A
600 kcmil575A690A780A
700 kcmil630A755A850A
750 kcmil655A785A885A

Aluminum

Wire60°C75°C90°C
12 AWG25A30A35A
10 AWG35A40A45A
8 AWG45A55A60A
6 AWG60A75A85A
4 AWG80A100A115A
3 AWG95A115A130A
2 AWG110A135A150A
1 AWG130A155A175A
1/0 AWG150A180A205A
2/0 AWG175A210A235A
3/0 AWG200A240A270A
4/0 AWG235A280A315A

Back to in-raceway ampacity tables (Table 310.16)

Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026