8 AWG THHN Aluminum Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.

NEC Quick Answer

8 AWG aluminum THHN has a base ampacity of 45A at 90C per NEC Table 310.16. Usable ampacity is 40A at the 75C termination limit, or 30A if equipment terminals are rated 60C only. Always verify terminal temperature ratings per NEC 110.14(C).

NEC 2023: Table 310.16, Section 110.14(C)

8 AWG THHN aluminum is rated 45A at 90°C and 40A at 75°C per NEC 2023 Table 310.16. Most equipment terminations are rated 75°C, making 40A the practical limit. Suitable for 40A circuits.
90°C45A
75°C40A
Breaker40A
Conduit3/4" EMT
V-Drop/100ft4.3%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
45A
Temp Correction 86°F × 1.0
45A
Bundling ≤3 CCC × 1.0
45A
Termination 110.14(C)(1)(a)(2) 75°C
40A −11%
Usable Ampacity
40A
Common inspection failure: Using 45A (90°C) without accounting for the 75°C termination limit. Most panels and breakers are rated 75°C per 110.14(C). The usable ampacity is 40A, not 45A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 8 AWG aluminum THHN (90°C column) = 45A base. Assumes ≤3 CCC at 30°C ambient.

Base =45A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 90°C insulation.

After temp =45A × 1.0 = 45A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =45A × 1.0 = 45A
Step 4Termination Limit
110.14(C)(1)(a)(2)

Equipment termination governs the final ampacity. Circuits ≤100A: use 60°C column unless conductor + equipment both rated 75°C. Modern panels and breakers are listed for 75°C terminations, so the 75°C column value of 40A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =40A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 8 AWG aluminum carrying 40A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 8 AWG aluminum at 75°C is used from NEC Chapter 9 Table 8. At 40A and 100 ft, the drop is 10.2V (4.3%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =4.3% (10.2V at 240V)

Common Applications

8 AWG THHN aluminum at 40A covers 40-50A circuits including electric ranges, cooktops, large central air conditioning units (3-5 ton), and Level 2 EV charger installations rated at 40A. Paired with a 40A or 50A breaker depending on the connected load. For electric ranges, the NEC permits a demand factor calculation under 220.55 that often allows 8 AWG for ranges rated up to 12 kW. Hot tub installations typically require 8 AWG minimum with mandatory GFCI protection per 680.44. EV chargers drawing 40A continuous require a 50A breaker (125% continuous load rule per 210.20) and 8 AWG meets this requirement. For loads above 50A or long runs with voltage drop concerns, upsize to 6 AWG.

Need more capacity? 6 AWG provides 50A. See also: copper vs aluminum.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
75°C
40A40A
90°C
45A45A
NEC 2020
Table 310.15(B)(16)
8 AWG Au 75°C = 40A
8 AWG Au 90°C = 45A
NEC 2023
Table 310.16 renumbered
8 AWG Au 75°C = 40A
8 AWG Au 90°C = 45A

Ampacity values for 8 AWG aluminum are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
8 AWG Aluminum TW60°C35AWet / underground
8 AWG Aluminum THW75°C40AStandard circuits
8 AWG Aluminum THHN90°C45ADerating start only
8 AWG Aluminum free air75/90°C55A / 60ATable 310.17
8 AWG Copper THHN75°C50ACopper equivalent
NEC 2026: Ampacity values for 8 AWG aluminum are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 8 AWG Aluminum wire?

8 AWG THHN Aluminum has a base ampacity of 45A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 40A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 8 AWG aluminum wire?

Pair 8 AWG aluminum with a 40A breaker. The wire's usable ampacity of 40A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (32A on a 40A breaker). See the full ampacity table for all wire sizes.

Can I use 8 AWG wire in conduit?

Yes. 8 AWG THHN is rated for conduit installations including EMT, PVC, and rigid metal conduit. The 45A base ampacity applies in conduit with no more than 3 current-carrying conductors. If bundling more than 3 conductors, apply the bundling adjustment factors from NEC Table 310.15(C)(1).

How far can I run 8 AWG aluminum wire?

The maximum distance depends on load and voltage. For 8 AWG aluminum at 40A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Derating matrix: all conditions

Ampacity of 8 AWG aluminum THHN (45A base at 90°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 40A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)51A41A36A25A
15°C (59°F)50A40A35A25A
20°C (68°F)48A38A34A24A
25°C (77°F)46A37A32A23A
30°C (86°F)45A36A31A22A
35°C (95°F)43A34A30A21A
40°C (104°F)40A32A28A20A
45°C (113°F)39A31A27A19A
50°C (122°F)36A29A25A18A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50°C) with standard bundling, 8 AWG aluminum drops to 36A - a 19% loss from the 45A base rating. Worst case (50°C, 20 conductors) drops to 18A, a 60% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.