CommercialNEC 2023 · 2026 · Updated Apr 2026

500 kcmil THHN Copper Ampacity

500 kcmil copper THHN: 430A base at 90°C, 380A usable after 110.14(C) termination limit.
Base430A
Usable380A
NEC Table310.16

Full derating calculation

Applications

500 kcmil copper is commonly used for large service entrance (320-380A), paralleled feeder sets, and switchgear connections.

Voltage drop by distance

Distance (ft)240V Drop% DropVerdict
50 ft1.0V0.4%OK
75 ft1.5V0.6%OK
100 ft2.0V0.8%OK
150 ft2.9V1.2%OK
200 ft3.9V1.6%OK
250 ft4.9V2.0%OK
300 ft5.9V2.5%OK
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026