ModerateNEC 2023 · 2026 · Updated Apr 2026

4/0 AWG XHHW-2 Copper Ampacity & Derating

Table 310.16 values are identical across NEC 2017, 2020, and 2023 editions.
4/0 AWG XHHW-2 copper is rated 260A at 90°C and 230A at 75°C per NEC 2023 Table 310.16. Most equipment terminations are rated 75°C, making 230A the practical limit. Suitable for 200A circuits.
90°C260A
75°C230A
Breaker200A
Conduit2" EMT
V-Drop/100ft1.2%
Ampacity Derating Walkthrough
Base Ampacity Table 310.16, 90°C
260A
Temp Correction 86°F × 1.0
260A
Bundling ≤3 CCC × 1.0
260A
Termination 110.14(C)(1)(b) 75°C
230A −12%
Usable Ampacity
230A
Common inspection failure: Using 260A (90°C) without accounting for the 75°C termination limit. Most panels and breakers are rated 75°C per 110.14(C). The usable ampacity is 230A, not 260A.

Calculation Walkthrough

Step 1Look Up Base Ampacity
Table 310.16

Per NEC 2023 Table 310.16, 4/0 AWG copper XHHW-2 (90°C column) = 260A base. Assumes ≤3 CCC at 30°C ambient.

Base =260A
Step 2Temperature Correction
Table 310.15(B)(1)

At 30.0°C (86°F), factor = 1.0. No reduction. At 50°C attic: factor drops to ~0.82 for 90°C insulation.

After temp =260A × 1.0 = 260A
Step 3Bundling Adjustment
Table 310.15(C)(1)

≤3 CCC = factor 1.0. EGC + neutral (unbalanced) not counted per 310.15(E). Typical 240V circuit: 2 hots + N + G = 2 CCC.

After bundling =260A × 1.0 = 260A
Step 4Termination Limit
110.14(C)(1)(b)

Equipment termination governs the final ampacity. Circuits >100A: 75°C column applies per 110.14(C)(1)(b). Modern panels and breakers are listed for 75°C terminations, so the 75°C column value of 230A becomes the ceiling. The 90°C rating is only used as the starting point for temperature correction and bundling derating. After all adjustments, the result cannot exceed the termination column value. This is the single most commonly failed inspection item.

Final =230A
Step 5Voltage Drop at 100 ft
210.19(A) Note 4

NEC recommends limiting voltage drop to 3% on branch circuits and 5% total (branch + feeder combined). For 4/0 AWG copper carrying 230A at 240V single-phase over a 100-foot one-way run: Vd = (2 × L × I × R) / 1000. The resistance per 1000 ft for 4/0 AWG copper at 75°C is used from NEC Chapter 9 Table 8. At 230A and 100 ft, the drop is 2.8V (1.2%). For longer runs or higher loads, use the voltage drop calculator with your specific distance and load.

V-Drop =1.2% (2.8V at 240V)

Common Applications

4/0 AWG XHHW-2 copper at 230A covers 195-230A feeders and is commonly used for 200A residential services, though NEC Table 310.15(B)(7) allows 2/0 AWG copper as the minimum for dwelling services. Paired with a 200A main breaker. 4/0 AWG provides headroom above the 200A rating (230A at 75ยฐC) which helps with voltage drop on longer runs. The aluminum equivalent for 200A dwelling service is 4/0 AWG aluminum per Table 310.15(B)(7), or 250 kcmil aluminum per the general Table 310.16. For service entrance cables (SE cable), verify the cable assembly rating matches the installation environment. Utility companies may specify minimum conductor sizes that exceed NEC requirements, so check with the local utility before ordering materials.

NEC 2020 vs NEC 2023

Feature
20202023
Table #
310.15(B)(16)310.16
75°C
230A230A
90°C
260A260A
NEC 2020
Table 310.15(B)(16)
4/0 AWG Cu 75°C = 230A
4/0 AWG Cu 90°C = 260A
NEC 2023
Table 310.16 renumbered
4/0 AWG Cu 75°C = 230A
4/0 AWG Cu 90°C = 260A

Ampacity values for 4/0 AWG copper are identical across NEC 2017, 2020, and 2023 editions. The only change affecting this conductor is the table renumbering from Table 310.15(B)(16) to Table 310.16 in the 2023 edition. This renumbering was part of a broader reorganization of Article 310 that also moved temperature correction factors from Table 310.15(B)(2)(a) to Table 310.15(B)(1) and bundling adjustment factors from Table 310.15(B)(3)(a) to Table 310.15(C)(1). When citing NEC references on permits or inspection reports, use the table numbers that match your state's adopted code year. States on NEC 2020 or earlier should cite Table 310.15(B)(16); states that have adopted NEC 2023 should cite Table 310.16.

Quick Reference

ConductorTempAmpsUse
4/0 AWG Copper TW60°C195AWet / underground
4/0 AWG Copper THW75°C230AStandard circuits
4/0 AWG Copper THHN90°C260ADerating start only
4/0 AWG Copper free air75/90°C360A / 405ATable 310.17
4/0 AWG Aluminum THHN75°C180AAluminum equivalent
NEC 2026: Ampacity values for 4/0 AWG copper are unchanged. Table renumbering from 2023 is retained. See NEC 2026 changes for Article 310 updates as states begin adoption.

Frequently asked questions

What is the ampacity of 4/0 AWG Copper wire?

4/0 AWG XHHW-2 Copper has a base ampacity of 260A at 90°C per NEC 2023 Table 310.16. After applying the 110.14(C) termination temperature limit, the usable ampacity is 230A for most installations. This is the value you use for circuit sizing and breaker selection.

What size breaker do I need for 4/0 AWG copper wire?

Pair 4/0 AWG copper with a 200A breaker. The wire's usable ampacity of 230A must equal or exceed the breaker rating. For continuous loads (running 3+ hours), the load must not exceed 80% of the breaker rating (160A on a 200A breaker). See the full ampacity table for all wire sizes.

Can I use 4/0 AWG wire in conduit?

Yes. 4/0 AWG XHHW-2 is rated for conduit installations including EMT, PVC, and rigid metal conduit. The 260A base ampacity applies in conduit with no more than 3 current-carrying conductors. If bundling more than 3 conductors, apply the bundling adjustment factors from NEC Table 310.15(C)(1).

How far can I run 4/0 AWG copper wire?

The maximum distance depends on load and voltage. For 4/0 AWG copper at 230A on a 240V circuit, use the voltage drop calculator with your specific distance. As a rule of thumb, keep voltage drop under 3% for branch circuits. Longer runs may require upsizing the conductor.

Can I use aluminum instead of copper for 4/0 AWG?

Yes, but check the ampacity difference. 4/0 AWG aluminum XHHW-2 is rated at 180A versus 230A for copper. For equivalent capacity, you'll typically need to go up one or two gauge sizes in aluminum. See the 4/0 AWG copper vs aluminum comparison for cost and installation details.

Derating matrix: all conditions

Ampacity of 4/0 AWG copper XHHW-2 (260A base at 90°C) after temperature correction per 310.15(B)(1) and bundling adjustment per 310.15(C)(1). The usable limit after 110.14(C) is 230A.

Ambient °C1-3 CCC4-6 CCC7-9 CCC10-20 CCC
10°C (50°F)299A239A209A149A
15°C (59°F)291A232A203A145A
20°C (68°F)280A224A196A140A
25°C (77°F)270A216A189A135A
30°C (86°F)260A208A182A130A
35°C (95°F)249A199A174A124A
40°C (104°F)236A189A165A118A
45°C (113°F)226A180A158A113A
50°C (122°F)213A170A149A106A

At/above usable limit Below limit Severely restricted

Bottom line: In a hot attic (50ยฐC) with standard bundling, 4/0 AWG copper drops to 213A - a 18% loss from the 260A base rating. Worst case (50ยฐC, 20 conductors) drops to 106A, a 59% reduction. Use the ampacity calculator to check your exact conditions.
Requirements vary by state. NEC edition, licensing, permits, and GFCI rules differ by jurisdiction. Check your state or pick it below for personalized info across WireRef.
Important: For reference only. Not a substitute for a licensed electrician. Electrical work can cause serious injury, death, fire, or property damage if performed incorrectly. Always hire a licensed electrician for electrical work, especially for service upgrades, panel work, and 240V circuits. Values are derived from NFPA 70 (NEC) for educational purposes. Always verify against your locally adopted NEC edition and amendments - local jurisdictions may enforce stricter requirements. WireRef provides reference information only and is not responsible for work performed based on this content. NEC® is a registered trademark of the National Fire Protection Association. Free NEC access via NFPA · OSHA Electrical Safety · Terms of use.

NEC 2023 references verified April 2026

As an Amazon Associate, WireRef earns from qualifying purchases. Product links do not affect the reference data or recommendations on this site. Terms of use.